Chapter 10. Relief Sizing

The learning objectives for this chapter are to understand relief sizing for:

  1. Liquid and vapor service.

  2. Two-phase flow.

  3. Fire exposure.

  4. Liquid thermal expansion.

Relief sizing calculations are performed to determine the vent area of the relief device. Relief sizing is a complex subject with many important subtleties too numerous to present here–experts in this area must be consulted. This chapter presents only a few simple cases. Also, relief sizing technology continues to evolve with time, particularly with respect to two-phase relief sizing.

Relief devices are considered preventive safeguards since they protect process equipment from the effects of high pressure. The pressure relief device might never be used, but it must operate properly every time it is required. Plant personnel must have confidence that all pressure relief systems are sized properly.

The relief sizing calculation uses an appropriate equation based on fundamental hydrodynamic principles to determine the relief device vent area. The relief vent area calculation depends on the specific application, the type of flow (liquid, vapor, or two-phase), and the type of relief device selected. See Section 9-4 and Table 9-2 for more details on the complete relief design procedure.

Figure 9-1 shows that the relief device begins to open at the relief set pressure, with the pressure then continuing to rise past the set pressure. A relief designed to maintain the pressure at the set pressure would require a very large and impractical relief area. The relief overpressure is a design feature of the device and must be specified prior to relief sizing.

Figure 10-1 shows that the relief vent area is reduced substantially as the overpressure increases. As mentioned in Chapter 9, the main purpose of a relief is to remove energy from the process. As the overpressure increases, the pressure driving force through the relief increases and the energy density of the fluid being discharged increases. Collectively, these changes result in a smaller vent area.

A graph of vent area versus overpressure for two-phase flow is shown.
Figure 10-1 Required vent area as a function of overpressure for two-phase flow. The vent area is decreased appreciably as the overpressure increases. Data from J. C. Leung. “Simplified Vent Sizing Equations for Emergency Relief Requirements in Reactors and Storage Vessels.” AICHE Journal 32, no. 10 (1986): 1622.

Spring-operated relief devices typically require a minimum flow to maintain the valve seat in the open position. Lower flows may result in “chattering,” caused by rapid opening and closing of the valve disc (see Section 9-5). This can lead to destruction of the relief device and a hazardous situation. A relief device with an area that is too large for the required flow is likely to chatter. In addition, the cost of the relief device increases dramatically with its size. For these reasons, reliefs must be designed with the proper vent area, neither too small nor too large. It is essential that the relief be sized properly to provide confidence that it will operate correctly when required.

This chapter presents methods for calculating the relief device vent areas for the following configurations:

  • Reliefs in liquid or vapor–gas service

  • Two-phase flow during runaway reactor relief

  • Dust and vapor explosions

  • Fires external to process vessels

  • Thermal expansion of process fluids

This chapter does not include relief sizing for atmospheric or low-pressure storage vessels. These reliefs, which are called conservation vents, have a completely different design and sizing basis.

10-1 Set Pressure and Accumulation Limits for Reliefs

Figure 9-3 shows the code requirements for the set pressure and accumulation limits for relief devices. These limits are summarized in Table 10-1. All percentages are with respect to the maximum allowable working pressure (MAWP) of the protected equipment. In the table, the accumulated pressure is the maximum pressure at the inlet to the relief device during the entire relief process expressed as a percentage of the MAWP.

Table 10-1 Set pressure and accumulation limits code requirements for pressure-­relieving devices. (Source: Adapted from API RP 520, Recommended Practice for the Sizing, Selection, and Installation of Pressure-Relieving Systems in Refineries, 9th ed. (Washington, DC: American Petroleum Institute, 2014).)

Relief configuration

Single relief device installation

Multiple relief device installation

Maximum set pressure (% of MAWP)

Maximum accumulated pressure (% of MAWP)

Maximum set pressure (% of MAWP)

Maximum accumulated pressure (% of MAWP)

Nonfire Scenario

 

 

 

 

Primary relief device

100

110

100

116

Additional devices

105

116

Fire Scenario

 

 

 

 

Primary relief device

100

121

100

121

Additional devices

105

121

Supplemental devicea

110

121

aIn addition to a nonfire relief device.

Two relief scenarios are shown in Table 10-1: nonfire and fire. The fire scenario considers reliefs for fires external to equipment (discussed in more detail in Section 10-6). Reliefs for fire scenarios are typically much larger in size to handle the large heat flux from the external fire. The primary relief would be sized for a nonfire scenario while the supplemental fire relief would be sized separately for the fire scenario.

As shown in Figure 9-3 and Table 10-1, the set pressure for a primary relief device must never exceed the MAWP.

Example 10-1

Consider a process vessel with a MAWP of 100 psig. For the nonfire case, determine the maximum accumulated pressure, the allowable overpressure, and the maximum relieving pressure for a set pressure of (a) 100 psig and (b) 90 psig.

Solution

The answers are provided in Table 10-1. The results are shown here.

  1. Set pressure at 100 psig equal to the MAWP.

    Maximum accumulated pressure: 110.0 psig (110% of MAWP; see Table 10-1)

    Allowable overpressure: 10.0 psi (maximum accumulated pressure – set pressure)

    Maximum relieving pressure: 110.0 psig (set pressure + allowable overpressure)

  2. Set pressure at 90 psig, which is below the MAWP.

    Maximum accumulated pressure: 110.0 psig (110% of MAWP; see Table 10-1)

    Allowable overpressure: 20.0 psi (maximum accumulated pressure – set pressure)

    Maximum relieving pressure: 110.0 psig (set pressure + allowable overpressure)

Even though the set pressure is lower in (b), the maximum relieving pressure is the same as in (a) because it is based on the MAWP.

Example 10-2

Rework Example 10-1 (a), but now add another nonfire relief device.

Solution

The answers are provided in Table 10-1. The results are shown here.

First relief device:

Relief set pressure: 100.0 psig (equal to the MAWP)

Maximum accumulated pressure: 116.0 psig (116% of MAWP; see Table 10-1)

Allowable overpressure: 16.0 psig (maximum accumulated pressure – set pressure

Maximum relieving pressure: 116.0 psig (set pressure + allowable overpressure)

Additional nonfire relief device:

Relief set pressure:105.0 psig (105% of MAWP; see Table 10-1)

Maximum accumulated pressure: 116.0 psig (116% of MAWP; see Table 10-1)

Allowable overpressure: 11.0 psi (maximum accumulated pressure – set pressure)

Maximum relieving pressure:116.0 psig (set pressure + allowable overpressure)

A few comments about Examples 10-1 and 10-2:

  1. For primary and additional relief devices, the maximum set pressure for the primary relief is set at the MAWP and the maximum set pressure for the additional relief is increased to 105% of the MAWP. The primary relief will open first.

  2. Adding another relief device increases the maximum accumulated pressure for the primary relief device from 110% to 116% of the MAWP. The maximum accumulated pressure for the additional relief device is also at 116% of the MAWP.

  3. The primary relief device is usually smaller in size to handle more routine relief scenarios, such as a regulator failure. The supplemental device might have a much larger area for a more robust relief scenario, such as a runaway reaction.

10-2 Relief Sizing for Liquid Service

Flow through spring-type reliefs is approximated as flow through an orifice. An equation representing this flow is derived from the mechanical energy balance (Equation 4-1). The result is similar to Equation 4-6, except that the pressure is represented by a pressure difference across the valve seat:

ˉu=Co2gcΔPρ(10-1)u¯=Co2gcΔPρ(10-1)

where

ū is the liquid velocity through the spring relief (distance/time),

Co is the discharge coefficient (unitless),

ΔP is the pressure drop across the valve seat (force/area), and

ρ is the liquid density (mass/volume).

The volumetric flow, Qv, of the liquid is the product of the velocity times the area, or ūA. Substituting the liquid velocity, u, from Equation 10-1 into the equation for Qv and solving for the vent area A of the relief, we obtain

A=QvCo2gcρΔP(10-2)A=QvCo2gcρΔP(10-2)

A working equation with fixed units is derived from Equation 10-2 by (1) replacing the density ρ with the specific gravity (ρ /ρref) and (2) making the appropriate substitutions for the specific unit conversions. The result is

A=[in2(psi)1/238.0gpm]QvCo(ρ/ρref)ΔP(10-3)A=[in2(psi)1/238.0gpm]QvCo(ρ/ρref)ΔP(10-3)

where

A is the computed relief area (in2),

Qv is the volumetric flow through the relief (gpm),

Co is the discharge coefficient (unitless),

(ρ /ρref) is the specific gravity of the liquid (unitless), and

ΔP is the pressure drop across the spring relief (lbf /in2).

Equation 10-3 represents flow through an orifice. A true orifice has a constant, fixed area. However, flow through a spring-type relief is actually flow through an annulus. As the pressure increases, the relief spring is compressed, increasing the annulus discharge area and increasing the flow.

Equation 10-3 also does not consider the viscosity of the fluid. Many process fluids have high viscosities; in such a case, the relief vent area must increase as the fluid viscosity increases.

Finally, Equation 10-3 does not consider the special case of a balanced bellows type of relief.

The American Society of Mechanical Engineers (ASME) pressure vessel code1 now requires all pressure relief valves (PRVs) in liquid service to be flow certified. ASME-certified relief valves are required to reach full rated capacity at 10% or less of overpressure. Relief valves are certified by the National Board of Boiler and Pressure Vessel Inspectors. The ASME code provides valve flow testing methods for code certification.

1ASME Boiler and Pressure Vessel Code (New York, NY: American Society of Mechanical Engineers, 2017).

For capacity certified valves, the following sizing equation applies:2

2API RP 520, Sizing, Selection, and Installation of Pressure-Relieving Devices in Refineries, 6th ed. (Washington, DC: American Petroleum Institute, 2017).

A=[in2(psi)1/238.0gpm]QvCoKbKcKv(ρ/ρref)P1P2    (10-4)A=[in2(psi)1/238.0gpm]QvCoKbKcKv(ρ/ρref)P1P2    (10-4)

where

A is the computed relief area (in2),

Qv is the volumetric flow through the relief (gpm),

Co is the rated discharge coefficient (unitless),

Kb is the backpressure correction (unitless),

Kc is the combination correction factor (unitless),

Kv is the viscosity correction (unitless),

(ρ /ρref) is the specific gravity of the liquid (unitless),

P1 is the gauge upstream relieving pressure (lbf /in2), which is the set pressure plus the allowable overpressure, and

P2 is the total gauge backpressure (lbf /in2).

The metric equivalent to Equation 10-4 is

A=[(bar)1/2s14.16m]QvCoKbKcKv(ρ/ρref)P1P2 (10-5)A=[(bar)1/2s14.16m]QvCoKbKcKv(ρ/ρref)P1P2 (10-5)

where the variables have the same meaning as Equation 10-4 but with the following units:

A: m2Qv: m3/sCo, Kb, Kc, Kv: unitless(ρ/ρref): unitlessP1, P2: barA: m2Qv: m3/sCo, Kb, Kc, Kv: unitless(ρ/ρref): unitlessP1, P2: bar

The capacity correction factors in Equations 10-4 and 10-5 are defined as follows:

  1. Co is the discharge coefficient and should be obtained from the valve manufacturer. For preliminary sizing, an effective discharge coefficient can be selected as follows: 0.65 for a spring-operated relief installed with or without a rupture disc in combination and 0.62 for a rupture disc.

  2. Kb is the backpressure correction. For conventional and pilot-operated valves, use a value of 1.0. If the backpressure is atmospheric, use a value of 1.0. Balanced bellows valves require a correction factor determined from Figure 10-2.

    A graph of backpressure correction (k subscript p) versus gauge backpressure (p subscript g) is drawn.
    Figure 10-2 Backpressure correction Kb for 25% overpressure on balanced bellows reliefs in liquid service. For metric units, barg can be used for psig. This is drawn using the equation Kb = 1.165 − 0.01PG, derived from data from API RP 520, Recommended Practice for the ­Sizing, ­Selection, and Installation of Pressure-Relieving Systems in Refineries, 9th ed. (Washington, DC: ­American Petroleum Institute, 2014).
  3. Kc is the combination correction factor; it corrects for installations with a rupture disc upstream of the PRV. Use a value of 1.0 if a rupture disc is not installed. Use a value of 0.9 if a rupture disc is installed with the PRV.

  4. Kv is the viscosity correction; it corrects for the additional frictional losses resulting from flow of higher-viscosity material through the valve. This correction is given in Figure 10-3. The required relief vent area becomes larger as the viscosity of the liquid increases (lower Reynolds numbers). Since the Reynolds number is required to determine the viscosity correction and because the vent area is required to calculate the Reynolds number, the procedure is iterative. For most reliefs, the Reynolds number is greater than 16,000 and the correction is near 1. This assumption is frequently used as an initial estimate to begin the calculations.

    The viscosity correction factor (K subscript v) versus Reynolds number is graphed.
    Figure 10-3 Viscosity correction factor Kv for conventional and balanced bellows reliefs in liquid service. This is drawn using the equation In Kv = 0.08547 − 0.9541/ln R − 35.571/R using data from API RP 520, Recommended Practice for the Sizing, Selection, and Installation of Pressure-Relieving Systems in Refineries, 9th ed. (Washington, DC: American Petroleum Institute, 2014).

Darby and Molavi developed an equation to represent the viscosity correction factor shown in Figure 10-3.3 This equation applies only to Reynolds numbers greater than 100:

3R. Darby and K. Molavi. “Viscosity Correction Factor for Safety Relief Valves.” Process Safety Progress 16, no. 2 (2004), pp. 80-82.

Kv=0.9751170Re+0.98 (10-6)Kv=0.9751170Re+0.98 (10-6)

where

Kv is the viscosity correction factor (unitless) and

Re is the Reynolds number (unitless).

Prior to ASME requiring capacity certification, a modified form of Equation 10-4 was used. An overpressure correction factor, Kp, is required for relieving pressures other than 25% overpressure. This results in the following equation:

A=[in2(psi)1/238.0gpm]QvCoKbKcKvKp(ρ/ρref)1.25PsP2 (10-7)A=[in2(psi)1/238.0gpm]QvCoKbKcKvKp(ρ/ρref)1.25PsP2 (10-7)

where

A is the computed relief area (in2),

Qv is the volumetric flow through the relief (gpm),

Co is the discharge coefficient (unitless),

Kb is the backpressure correction (unitless),

Kc is the combination correction factor (unitless),

Kv is the viscosity correction (unitless),

Kp is the overpressure correction (unitless),

(ρ /ρref) is the specific gravity of the liquid at standard conditions (unitless),

Ps is the gauge set pressure (lbf/in2), and

P2 is the total gauge backpressure (lbf/in2).

Equation 10-7 was the only liquid sizing equation used in previous editions of this textbook.

The metric equivalent to Equation 10-7 is

A=[(bar)1/2s14.16 m]QvCoKbKcKvKp(ρ/ρref)1.25PsP2 (10-8)A=[(bar)1/2s14.16 m]QvCoKbKcKvKp(ρ/ρref)1.25PsP2 (10-8)

where the variables have the same meaning as Equation 10-3 but with the following units:

A: m2Qv: m3/sCo, Kb, Kc, Kv, Kp: unitless(ρ/ρref): unitlessPs, P2: barA: m2Qv: m3/sCo, Kb, Kc, Kv, Kp: unitless(ρ/ρref): unitlessPs, P2: bar

The capacity correction factors in Equations 10-7 and 10-8 are defined as follows:

  1. Co is the discharge coefficient and should be obtained from the valve manufacturer. For preliminary sizing, an effective discharge coefficient of 0.62 is used.

  2. Kb is the backpressure correction factor. For conventional spring-operated and pilot-operated valves, use a value of 1.0. If the backpressure is atmospheric, use a value of 1.0. Balanced bellows valves require a correction factor determined from Figure 10-2.

  3. Kc is the combination correction factor; it corrects for installations with a rupture disc upstream of the PRV. Use a value of 1.0 if a rupture disc is not installed. If a rupture disc is installed, see API RP 510 for details.

  4. Kv is the viscosity correction; it corrects for the additional frictional losses resulting from flow of high-viscosity material through the valve. See note 4 below Equation 10-5. This correction is given by Figure 10-3 or Equation 10-6.

  5. Kp is the overpressure correction and has a value of 1.0 at 25% overpressure. For overpressures other than 25%, use Figure 10-4.

A graph of overpressure correction (K subscript p) versus overpressure (p0) is shown.
Figure 10-4 Overpressure correction Kp for spring-operated reliefs (conventional and balanced bellows) in uncertified liquid service. This is drawn using the equations shown, derived from data from API RP 520, Recommended Practice for the Sizing, Selection, and Installation of Pressure-Relieving Systems in Refineries, 9th ed. (Washington, DC: American Petroleum Institute, 2014).

Example 10-3

A positive displacement pump is rated for 200 gpm at a pressure of 200 psig. Because a deadheaded positive displacement pump can be easily damaged, compute the area for a capacity-certified spring-operated relief required to protect the pump. The rated pressure for the pump is 250 psig. The superimposed backpressure is 20 psig and constant. Determine the required relief area assuming an overpressure of 25 psig.

Solution

Equation 10-4 applies for capacity-certified liquid relief.

The set pressure is 250 psig. P1 is the set pressure plus the overpressure,

P1 = 250 psig + 25 psig = 275 psig.

P2 is the total gauge backpressure, 20 psig.

For water, (ρ/ρref = 1.0.

The quantity of material relieved is the capacity of the pump, so Qv = 200 gpm.

The discharge coefficient Co is not specified. However, for preliminary sizing purposes, a value of 0.65 is used.

Since this is a conventional spring-operated relief, the backpressure correction is Kb = 1.0.

Pumps do not normally have a spring relief coupled with a rupture disc combination. Thus, the combination correction factor, Kc, has a value of 1.0.

The Reynolds number through the relief device is not known since the relief area is to be determined. However, at 200 gpm, the Reynolds number is assumed to be greater than 16,000. Thus, the viscosity correction is Kv = 1.0.

These numbers are substituted into Equation 10-4:

A=[in2(psi)1/238.0gpm]QvCoKbKcKv(ρ/ρref)P1P2=[in2(psi)1/238.0gpm]200 gpm(0.65)(1.0)(1.0)(1.0)1.0(27520) psig=0.507 in2(104)A=[in2(psi)1/238.0gpm]QvCoKbKcKv(ρ/ρref)P1P2=[in2(psi)1/238.0gpm]200 gpm(0.65)(1.0)(1.0)(1.0)1.0(27520) psig=0.507 in2(104)

The diameter of the relief is

d=4Aπ=4(0.507 in2)3.14=0.80 ind=4Aπ=4(0.507 in2)3.14=0.80 in

Manufacturers do not provide relief devices to the nearest 0.01 in. Thus, a selection must be made depending on the relief device sizes available commercially. The valve will open only enough to deliver the 200 gpm flow. The next largest available size–with a higher capacity–is therefore selected.

10-3 Relief Sizing for Vapor and Gas Service

For most vapor or gas discharges through reliefs, the flow is critical. However, the downstream pressure must be checked to ensure that it is less than the choked pressure computed using Equation 4-49. Thus, for an ideal gas Equation 4-50 is valid:

(Qm)choked=CoAPγgcMRgT(2γ+1)(γ+1)/(γ1)(450)(Qm)choked=CoAPγgcMRgT(2γ+1)(γ+1)/(γ1)(450)

where

(Qm)choked is the discharge mass flow (mass/time),

Co is the discharge coefficient (unitless),

A is the area of the discharge (area),

P is the absolute upstream relieving pressure, equal to the set pressure plus the overpressure (force/area),

γ is the heat capacity ratio for the gas (unitless),

gc is the gravitational constant (length mass/force time2)

M is the molecular weight of the gas (mass/mole)

Rg is the ideal gas constant, and

T is the absolute temperature of the discharge (degree).

Equation 4-50 is solved for the area of the relief vent given a specified mass flow rate Qm:

A=QmCoPT/MγgcRg(2γ+1)(γ+1)/(γ1)(10-9)A=QmCoPT/MγgcRg(2γ+1)(γ+1)/(γ1)(10-9)

Equation 10-9 is simplified by defining a function χ:

χ=γgcRg(2γ+1)(γ+1)/(γ1)(10-10)χ=γgcRg(2γ+1)(γ+1)/(γ1)(10-10)

Then the required relief vent area for an ideal gas is computed using a simplified form of Equation 10-9:

A=QmCoχPTM(10-11)A=QmCoχPTM(10-11)

Equation 10-11 is modified by (1) including the compressibility factor z to represent a nonideal gas; (2) including a backpressure correction Kb; and (3) including a combination correction factor Kc to account for the presence of a rupture disc below the spring relief. The result is4

4API RP 520, Sizing, Selection, and Installation of Pressure-Relieving Devices in Refineries, 6th ed. (Washington, DC: American Petroleum Institute, 2017).

A=QmχCoKbKcPTzM(10-12)A=QmχCoKbKcPTzM(10-12)

where

A is the area of the relief vent (area),

Qm is the discharge mass flow (mass/time),

Co is the effective discharge coefficient (unitless),

Kb is the backpressure correction (unitless),

Kc is the combination correction factor (unitless),

P is the upstream relieving pressure, equal to the set pressure plus the allowable overpressure (force/area, absolute),

T is the absolute temperature (degrees),

z is the compressibility factor (unitless), and

M is the average molecular weight of the discharge material (mass/mole).

Note that Equation 10-12 does not include a downstream pressure since critical flow through an orifice is independent of the downstream pressure.

The constant χ is calculated using Equation 10-10. It is conveniently calculated using the following fixed-unit expressions:

χ=[519.5(lb-mole lbmoR)1/2lbfhr]γ(2γ+1)(γ+1)/(γ1)(10-13)χ=[519.5(lb-mole lbmoR)1/2lbfhr]γ(2γ+1)(γ+1)/(γ1)(10-13)

If Equation 10-13 is used with Equation 10-12, then the following fixed units must be used: Qm in lbm/hr, P in psia, T in °R, and M in lbm/lb-mole. The area computed is in in2.

The metric equivalent to Equation 10-13 is:

χ=[3.468×104(mol kg K)1/2bar s m2]γ(2γ+1)(γ+1)/(γ1)(10-14)χ=[3.468×104(mol kg K)1/2bar s m2]γ(2γ+1)(γ+1)/(γ1)(10-14)

If Equation 10-14 is used with Equation 10-12, then the following fixed units must be used: Qm in kg/s, P in bar, T in K, and M in kg/mol. The area computed is in m2.

The capacity correction factors in Equation 10-12 are defined as follows:

  1. Co is the discharge coefficient and should be provided by the manufacturer. For preliminary sizing, the following values are used:

    • When the PRV is installed with or without a rupture disc in combination: 0.975

    • When sizing for a rupture disc alone: 0.62

  2. Kb is the capacity correction factor for backpressure and should be obtained from the manufacturer. For preliminary sizing, use Figure 10-5 for balanced bellows valves only. For conventional and pilot-operated valves, use a value of 1.0.

    A graph of backpressure (k subscript b) with gauge pressure is depicted.
    Figure 10-5 Backpressure correction Kb for balanced-bellows reliefs in vapor or gas service. For metric units, barg can be used for psig. This is drawn using the equations provided. Data from API RP 520, Recommended Practice for the Sizing, Selection, and Installation of Pressure-Relieving Systems in Refineries, 9th ed. (Washington, DC: American Petroleum Institute, 2014).
  3. Kc is the combination correction factor for a rupture disc upstream of the valve. If no rupture disc is upstream, use a value of 1.0. Use 0.9 when a rupture disc is installed in combination with the PRV and the combination does not have a certified value; see API RP 520 for more details.

Subcritical Vapor/Gas Flow

Critical flow of vapors/gases through relief devices is the usual case, but subcritical flow is also possible. See Sections 4-5 and 4-6 to determine whether subcritical or critical flow occurs in your particular case. For subcritical flows through relief devices, consult API RP 520 (2014), page 66.

Steam Flow Relief Sizing

Steam is a specific case of vapor flow and the physical properties of steam are well known. API RP 520 has a dedicated relief sizing procedure for steam (page 72 of the standard). Consult this reference for steam relief applications.

Rupture Disc Sizing

Rupture discs may be used as the primary relief device for gas, vapor, liquid, or multiphase flow. There are two accepted methods for rupture disc sizing, according to API RP 520.

The first method uses the equations already presented here for liquid and vapor service. Use Equation 10-4 or Equation 10-7 for liquid service and Equation 10-12 for vapor service. A coefficient of discharge, Co, of 0.62 must be used. This method may only be used in the following scenarios:

  1. When the rupture disc discharges directly to the atmosphere

  2. When the rupture disc is installed within eight pipe diameters from the vessel entry nozzle

  3. When the rupture disc has a length of discharge no greater than five pipe diameters

  4. When the inlet and outlet discharge piping is equal to or greater than the diameter of the rupture disc

Consult API RP 520, page 81, for additional details.

The second method for rupture disc sizing is to use the flow resistance method outlined in Section 4-4 with the velocity head method. This approach must include the rupture disc device, piping and other piping components, entrance and exit losses, elbows, tees, reducers, valves, and other piping components. The calculated relieving capacity should be multiplied by 0.90 or less to allow for uncertainties in this method. Consult API RP 520, page 81, for more details.

Pilot-Operated Relief Sizing

For pilot-operated valves, neither the set pressure nor the capacity is affected by backpressure since the valve lift is not affected by backpressure.

Buckling Pin Relief Sizing

See UG-127(b) and UG-138 of the ASME Code for sizing, application, and minimum requirements for buckling pin devices.

Example 10-4

One high pressure scenario identified for a reactor vessel is the failure of a nitrogen regulator, allowing high-pressure nitrogen to enter the reactor through a 10-cm-diameter supply pipe. The source of the nitrogen is at 25°C and 10 barg. The reactor vessel MAWP is 3.0 barg. Determine the diameter of a balanced bellows spring-type vapor relief required to protect the reactor from this incident. Assume a constant superimposed backpressure of 0.5 bar.

Solution

From Table 10-1, the maximun set pressure is equal to the vessel MAWP at 3.0 barg. The maximum accumulated pressure is 1.10 × 3.0 barg = 3.3 barg = 4.3 bara.

The nitrogen source is at 10 barg = 11.01 bara. If the regulator fails, the nitrogen will flood the reactor, increasing the pressure and exceeding the MAWP. A relief vent must be installed to vent the nitrogen as fast as it is supplied through the 10-cm pipe. Because no other information on the piping system is provided, the flow from the pipe is assumed to be represented by critical flow through an orifice. Equation 4-50 applies:

(Qm)choked=CoAPγgcMRgT(2γ+1)(γ+1)/(γ1)(4-50)(Qm)choked=CoAPγgcMRgT(2γ+1)(γ+1)/(γ1)(4-50)

First, however, the choked pressure across the pipe must be determined to ensure critical flow. For diatomic gases, the choked pressure is given as (see Section 4-5)

Pchoked=0.528P=(0.528)(11.01 bara)=5.8 baraPchoked=0.528P=(0.528)(11.01 bara)=5.8 bara

The maximum accumulated pressure in the reactor vessel during the relief venting is 4.3 bara. Thus, the pressure in the reactor is less than the choked pressure and the flow through the 10-cm line into the reactor vessel will be sonic. The required quantities for Equation 4-50 are

A=πd24=(3.14)(0.10 m)24=7.85×103m2P=11.01baraγ=1.40for diatomic gasesT=25oC+273=298 KM=0.028 kg/mol(2γ+1)(γ+1)/(γ1)=(21.4+1)(2.4/0.4)=0.335APγTM(2γ+1)(γ+1)/(γ1)=πd24=(3.14)(0.10 m)24=7.85×103m2=11.01bara=1.40for diatomic gases=25oC+273=298 K=0.028 kg/mol=(21.4+1)(2.4/0.4)=0.335

The discharge coefficient Co is assumed to be 1.0 for sonic flow through the pipe.

Substituting into Equation 4-50, we obtain

(Qm)choked=(1.0)(7.85×103m2)(11.01 bara)(105 N/m2bar)×(1.4)(1.0kg m/N s2)(0.028 kg/mol)(0.335)(8.314×105 bar m3/mol K)(298 K)(105 N/m2bar)=(8.64×103 N)5.30×106 kg2/N2s2=19.9 kg/s(Qm)choked=(1.0)(7.85×103m2)(11.01 bara)(105 N/m2bar)×(1.4)(1.0kg m/N s2)(0.028 kg/mol)(0.335)(8.314×105 bar m3/mol K)(298 K)(105 N/m2bar)=(8.64×103 N)5.30×106 kg2/N2s2=19.9 kg/s

The area of the relief vent is computed using Equations 10-12 and 10-14 with a backpressure correction Kb determined from Figure 10-5. The backpressure is 0.5 barg. Thus,

(backpressure, bargset pressure, barg)×100=(0.5 barg3.0 barg)×100=16.7%(backpressure, bargset pressure, barg)×100=(0.5 barg3.0 barg)×100=16.7%

From Figure 10-5, Kb = 1.0.

The effective discharge coefficient Co for the relief is 0.975.

The gas compressibility factor z is 1 at these pressures.

The pressure P is the upstream relieving pressure, which is the set pressure plus the superimposed backpressure or 3.0 barg + 0.5 barg = 3.5 barg = 4.51 bara.

The constant χ is computed from Equation 10-14:

χ=[3.468×104(mol kg K)1/2bar s m2]γ(2γ+1)(γ+1)/(γ1)=[3.468×104(mol kg K)1/2bar s m2](1.4)(0.335)=2.37×104(mol kg K)1/2bar s m2χ=[3.468×104(mol kg K)1/2bar s m2]γ(2γ+1)(γ+1)/(γ1)=[3.468×104(mol kg K)1/2bar s m2](1.4)(0.335)=2.37×104(mol kg K)1/2bar s m2

The required vent area is computed using Equation 10-9:

A=QmCoχKbPTzM=19.9 kg/s(0.975)[2.37×104(mol kg K)1/2bar s m2](1.0)(4.51 bara)(298 K)(1.0)0.028 kg / mol=1.97×102 m2A=QmCoχKbPTzM=19.9 kg/s(0.975)[2.37×104(mol kg K)1/2bar s m2](1.0)(4.51 bara)(298 K)(1.0)0.028 kg / mol=1.97×102 m2

The required vent diameter is

d=4Aπ=4(1.97×102 m2)3.14=0.16 m=16 cmd=4Aπ=4(1.97×102 m2)3.14=0.16 m=16 cm

The next largest valve size is selected from the manufacturer. If the vapor relief valve is pop-acting, then the valve will be open for a period of time and then closed for a period of time. The average flow over the open/closed intervals equals the required nitrogen flow.

Example 10-5

Compute the rupture disc vent diameter required to protect the vessel described in Example 10-4.

Solution

Since we do not know any information regarding the actual plumbing, we will use the capacity discharge correction method and assume that all the conditions listed are satisfied. The solution is provided by Equation 10-12. The solution is identical to Example 10-4, but with the discharge coefficient Co = 0.62. The area is therefore

A=(1.97×102 m2)(0.9750.62)=3.05×102m2A=(1.97×102 m2)(0.9750.62)=3.05×102m2

The rupture disc diameter is

d=4Aπ=4(3.05×102m2)3.14=0.197 m=19.7md=4Aπ=4(3.05×102m2)3.14=0.197 m=19.7m

This compares to a spring relief diameter of 16 cm.

10-4 Two-Phase Flow during Runaway Reaction Relief

Two-phase flow is normally expected during the relief process when a runaway reaction occurs within a reactor vessel. A detailed study using one or more of the calorimeters described in Table 8-8 provides the much-needed data for two-phase relief area sizing. Two-phase flow must be confirmed and the complex flow regimes identified using these calorimeters.

Two-phase flow through reliefs is much more complex than the introduction provided here might suggest. Furthermore, the technology is still undergoing substantial development.

There are three dominant methods currently available for two-phase relief sizing:

  • Leung method

  • Fauske method

  • API method

Specific references are available at the end of this chapter for each of these methods. Only the Leung method is presented here.

Figure 10-6 shows the most common type of reactor system, called a tempered reactor. It is called “tempered” because the reactor contains a volatile liquid that vaporizes or flashes during the relieving process. This vaporization removes energy by means of the heat of vaporization and tempers the rate of temperature rise resulting from the exothermic reaction.

A tempered reaction system presents the most important energy terms.
Figure 10-6 A tempered reaction system showing the important energy terms.

The runaway reactor is treated as entirely adiabatic. The energy terms include (1) the energy accumulation resulting from the sensible heat of the reactor fluid as a result of its increased temperature due to overpressure and (2) the energy removal resulting from the vaporization of liquid in the reactor and subsequent discharge through the relief vent.

The first step in the relief sizing calculation for two-phase vents is to determine the mass flux through the relief. This is computed using Equation 4-105, representing choked two-phase flow through a hole:

Qm=ΔHvAvfggcTsCP(4-105)Qm=ΔHvAvfggcTsCP(4-105)

The heat losses through the reactor walls are assumed to be negligible where, for this case,

Qm is the mass flow through the relief (mass/time),

ΔHV is the heat of vaporization of the fluid (energy/mass),

A is the area of the hole (area),

vfg is the change of specific volume of the flashing liquid (volume/mass),

CP is the heat capacity of the fluid (energy/mass degrees), and

Ts is the absolute saturation temperature of the fluid at the set pressure (degrees).

The mass flux GT is given by

GT=QmA=ΔHVvfggcTsCP(10-15)GT=QmA=ΔHVvfggcTsCP(10-15)

Equation 10-15 applies to two-phase relief through a hole. For two-phase flow through pipes, an overall dimensionless discharge coefficient ψ is applied. Equation 10-15 is the so-called equilibrium rate model (ERM) for low-quality choked flow.5 Leung showed that Equation 10-15 must be multiplied by a factor of 0.9 to bring the value in line with the classic homogeneous equilibrium model (HEM).6 The result should be generally applicable to homogeneous venting of a reactor (low quality, not restricted to just liquid inlet condition):

5H. K. Fauske. “Flashing Flows or Some Practical Guidelines for Emergency Releases.” Plant Operations Progress 4, no. 3 (July 1985), pp. 132-134.

6J. C. Leung. “Simplified Vent Sizing Equations for Emergency Relief Requirements in Reactors and Storage Vessels.” AICHE Journal 32, no. 10 (1986): 1622.

GT=QmA=0.9ψΔHVvfggcTsCP(10-16)GT=QmA=0.9ψΔHVvfggcTsCP(10-16)

Values for ψ are provided in Figure 10-7. For a pipe of length 0, ψ = 1. As the pipe length increases, the value of ψ decreases.

A graph compares the correction factor (psi) and L over D for two-phase flashing flow through pipes.
Figure 10-7 Correction factor ψ correcting for two-phase flashing flow through pipes. Data from J. C. Leung and M. A. Grolmes. “The Discharge of Two-Phase Flashing Flow in a Horizontal Duct,” AICHE Journal 33, no. 3 (1987): 524–527.

A somewhat more convenient expression is derived by rearranging Equation 4-103 to yield

ΔHVvfg=TsdPdT(10-17)ΔHVvfg=TsdPdT(10-17)

Substituting into Equation 10-16, we obtain

GT=0.9ψdPdTgcTsCP(10-18)GT=0.9ψdPdTgcTsCP(10-18)

The exact derivative is approximated by a finite-difference derivative to yield

GT0.9ψΔPΔTgcTsCP(10-19)GT0.9ψΔPΔTgcTsCP(10-19)

where

ΔP is the overpressure (force/area), and

ΔT is temperature rise corresponding to the overpressure (degrees).

The required vent area is computed by solving a particular form of the dynamic energy balance. Details are provided elsewhere.7 The result is

7J. C. Leung. “Simplified Vent Sizing Equations for Emergency Relief Requirements in Reactors and Storage Vessels.” AICHE Journal 32, no. 10 (1986): 1622.

A=moqGT(VmoΔHVvfg+CVΔT)2(10-20)A=moqGT(VmoΔHVvfg+CVΔT)2(10-20)

An alternative form is derived by applying Equation 10-17:

A=moqGT(VmoTsdPdT+CvΔT)2(10-21)A=moqGT(VmoTsdPdT+CvΔT)2(10-21)

For Equations 10-20 and 10-21, the following additional variables are defined:

mo is the total mass contained within the reactor vessel before relief (mass),

q is the exothermic heat release rate per unit mass (energy/time),

V is the volume of the vessel (volume), and

Cv is the liquid heat capacity at constant volume (energy/mass degrees).

For both Equations 10-20 and 10-21, the relief area is based on the total heat added to the system (numerator) and the heat removed or absorbed (denominator). The first term in the denominator corresponds to the net heat removed by the liquid and vapor leaving the system; the second term corresponds to the heat absorbed as a result of increasing the temperature of the liquid because of the overpressure.

The heat input q resulting from an exothermic reaction is determined using fundamental kinetic information or from a calorimeter (see Table 8-8). For data obtained using the Vent Sizing Package (VSP), the equation

q=12Cv[(dTdt)s+(dTdt)m](10-22)q=12Cv[(dTdt)s+(dTdt)m](10-22)

is applied, where the derivative denoted by the subscript “s” corresponds to the heating rate at the set pressure and the derivative denoted by the subscript “m” corresponds to the temperature rise at the maximum turnaround pressure. Both derivatives are determined experimentally using the VSP.

The equations include the following assumptions:

  1. Uniform froth or homogeneous vessel venting occurs.

  2. The mass flux GT varies little during the relief.

  3. The reaction energy per unit mass q is treated as a constant.

  4. The physical properties CV, ΔHV, and vfg are constant.

  5. The system is a tempered reactor system. This applies to most reaction systems.

Units are a particular problem when using the two-phase equations. The best procedure is to convert all energy units to their mechanical equivalents before solving for the relief area, particularly when English engineering units are used.

Example 10-6

Leung8 reported on the data of Huff 9 involving a 3500-gal reactor with styrene monomer undergoing adiabatic polymerization after being heated inadvertently to 70°C. The MAWP of the vessel is 5 bar. Given the following data, determine the relief vent diameter required. Assume a set pressure of 4.5 bar and a maximum pressure of 5.4 bar absolute:

8J. C. Leung. “Simplified Vent Sizing Equations for Emergency Relief Requirements in Reactors and Storage Vessels.” AICHE Journal 32, no. 10 (1986): 1622.

9J. E. Huff. “Emergency Venting Requirements.” Plant/Operations Progress 1, no. 4 (1982): 211.

Data:

Volume (V ): 3500 gal = 13.16 m3

Reaction mass (mo): 9500 kg

Set temperature (Ts): 209.4°C = 482.5 K

Data from VSP:

Maximum temperature (Tm): 219.5°C = 492.7 K

(dT/dt)s = 29.6°C/min = 0.493 K/s

(dT/dt)m = 39.7°C/min = 0.662 K/s

Physical Property Data:

 

4.5-Bar set

5.4-Bar peak

vf (m3/kg)

0.001388

0.001414

vg (m3/kg)

0.08553

0.07278

CP (kJ/kg K)

2.470

2.514

ΔHV (kJ/kg)

310.6

302.3

Solution

The heating rate q is determined using Equation 10-22:

q=12CV[(dTdr)s+(dTdt)m](10-22)q=12CV[(dTdr)s+(dTdt)m](10-22)

Assuming that CV = CP, we have

q=12(2.470kJ/kgK)(0.493+0.662)(K/s)=1.426kJ/kg sq=12(2.470kJ/kgK)(0.493+0.662)(K/s)=1.426kJ/kg s

The mass flux is given by Equation 10-16. Assuming L/D = 0, ψ = 1.0:

GT=0.9ψΔHVνfggcTsCP=(0.9)(1.0)(310,600J/kg)(1Nm/J)(0.085530.001388)m3/kg×[1(kgm/s2)/N](2470 J/kg K)(482.5K)[1Nm/J]=3043 kg/m2sGT=0.9ψΔHVνfggcTsCP=(0.9)(1.0)(310,600J/kg)(1Nm/J)(0.085530.001388)m3/kg×[1(kgm/s2)/N](2470 J/kg K)(482.5K)[1Nm/J]=3043 kg/m2s

The relief vent area is determined from Equation 10-20. The change in temperature ΔT is TmTs = 492.7 – 482.5 = 10.2 K:

A=moqGT(VmoΔHVνfg+CVΔT)2=(9500kg)(1426 J/kgs)(1 N m/J)3043kg/m2s×((13.16m39500kg){(310,600J/kg)(1 N m/J)0.084l4m3/kg}+(2470J/kgK)(10.2K)(1 N m/J))2=0.084m2

The required relief diameter is

d=4Aπ=(4)(0.084m2)314=0.327m

Suppose that all vapor relief was assumed. The size of the required vapor-phase rupture disc is determined by assuming that all the heat energy is absorbed by the vaporization of the liquid. At the set temperature, the heat release rate q is

=CV(dTdt)s=(2.470kJ/kgK)(0.493K/s)=1.218kJ/kg s

The vapor mass flow through the relief is then

Qm=qmoΔHv=(1218 J/kgs)(9500kg)(310,600J/kg)=37.2kg/s

Equation 10-9 provides the required relief area. The molecular weight of styrene is 104. Assume that γ = 1.32 and Co = 1.0. Then,

A=QmCoPRgTγgcM(2γ+1)(γ+1)/(1γ)=37.2kg/s(1.0)(4.5bar)(100,000Pa/bar)[1(N/m2)/Pa]×(8314Pam3/kg-moleK)(482.5K)[1(N/m2)/Pa)(1.32)[1(kg m/s2)/N](104kg/kg-mole)×(22.32)232/(032)=0.0242m2

This requires a relief device with a diameter of 0.176 m, a significantly smaller diameter than for two-phase flow. Thus, if the relief were sized assuming all-vapor relief, the result would be physically incorrect and the relief would be inadequate to protect the reactor.

10-5 Deflagration Venting for Dust and Vapor Explosions

An uncontrolled dust or gas/vapor explosion in a warehouse, storage bin, or processing unit can eject high-velocity structural debris over a considerable area, propagating the accident and resulting in increased injuries. Deflagration venting reduces the impact of dust and vapor cloud explosions by controlling the release of the explosion energy. The energy of the explosion is directed away from plant personnel and equipment. Deflagration vents are considered mitigative safeguards since they reduce the magnitude of the incident.

Deflagration venting in buildings and process vessels is achieved by using blowout panels, as shown in Figure 10-8. The blowout panel is designed to have less strength than the walls of the structure. Thus, during an explosion, the blowout panels are preferentially detached and the explosive energy is vented. Damage to the remaining structure and equipment is minimized. For particularly explosive dusts or vapors, it is not unusual for the walls (and perhaps roof) of the entire structure to be constructed of blowout panels.

A figure depicts the deflagration vents for structures and process vessels.
Figure 10-8 Deflagration vents for structures and process vessels.

The actual construction details of blowout panels are beyond the scope of this text. A detached blowout panel moving at high velocity can cause considerable damage. Therefore, a mechanism must be provided to retain the panel during the deflagration process. Furthermore, thermal insulation of panels is required for heating and cooling. Construction details are available in manufacturers’ literature.

Blowout panels must be sized to provide the proper relief area. The relief sizing depends on many factors that impact the design of these vents. A partial list includes:

  • The physical state of the material combusting, including flammable dusts, gases/vapors, or a combination (hybrid) mixture.

  • The combustion behavior of the material combusting:

    For gases/vapors, this includes the flammable limits, the maximum pressure during combustion, and the deflagration index, KG.

    For dusts, this includes the particle size and shape, the dust loading, the maximum pressure during combustion, and the deflagration index, KSt.

  • The geometry of the structure being protected, including the volume, surface area, and structure shape.

  • The congestion inside the structure due to equipment. Equipment within the structure will result in turbulence augmentation during the combustion, which will increase the robustness of the combustion.

  • The strength of the structure being protected.

  • The strength and inertia of the vent panel.

Deflagration vent design is segregated into two categories: (1) gases, vapors, and mists and (2) dusts and hybrid mixtures.

Vents for Gases/Vapors and Mists

Vent design for gases/vapors and mists is based on the Runes (pronounced “Roo-ness”) equation:10

10NFPA 68, Guide for Venting of Deflagrations (Quincy, MA: National Fire Protection Association, 2018).

Av=AsCPred(10-23)

where

Av is the required vent area (area),

As is the internal surface area of the structure being protected, including the walls and ceiling (area),

C is a vent constant that depends on the nature of the combustible material (pressure)1/2, and

Pred is the maximum internal pressure developed in the structure during the venting process (pressure). It is based on the pressure rating of the weakest element of the structure (force/area).

The vent constant, C, is estimated using the following equation:

C=Suρuλ2GuCd[(Pmax+1Po+1)1/γb1](Po+1)1/2(10-24)

where

Su is the burning parameter, discussed later in this section (m/s),

ρu is the mass density of the unburned gas–air mixture (kg/m3),

λ is the turbulent augmentation factor (unitless),

Gu is the unburned gas–air mixture sonic flow mass flux (kg/m2s),

Cd is the vent flow discharge coefficient (unitless),

Pmax is the maximum unvented explosion pressure by ignition of the same gas–air mixture (barg),

Po is the initial pressure in the enclosure prior to ignition (barg), and

γb is the heat capacity ratio for the burned gas–air mixture.

More details on how to estimate these parameters are provided in NFPA 68.

Equations 10-23 and 10-24 apply only for Pred ≤ 0.1 barg (1.5 psig) and PstatPred = 0.024 barg, where Pstat is the pressure at which the vent activates. NFPA 68 provides equations for other conditions.

The turbulent augmentation factor, λ, is estimated using an arduous procedure provided in NFPA 68. It accounts for enhancement of the combustion due to induced turbulence by objects within the structure. Such objects may include piping, conduit, structural columns and beams, stairways and railings and any other equipment. Turbulence enhancement will require a much larger vent area. Without turbulence enhancement, the turbulent augmentation factor has a value of 1.

It is always best to use experimentally determined values for C. However, for estimation purposes, for Pmax less than 9 barg and a fuel concentration less than 10% of the stoichiometric concentration, the following equation can be used:

C=0.0223λSu(10-25)

where

C is the vent constant (bar),

λ is the turbulent augmentation factor (unitless), and

Su is the burning parameter (m/s).

Table 10-2 provides burning parameters, Su for various gases.

Table 10-2 Burning parameters, Su, for a variety of gases.

Gas

Burning parameter (cm/s)

Acetylene

166

Benzene

48

n-Butane

45

Carbon disulfide

58

Carbon monoxide

46

n-Decane

43

Diethyl ether

47

Ethane

47

Ethylene

80

Gasoline (100 octane)

40

n-Hexane

46

Hydrogen

312

Isopropyl alcohol

41

Methane

40

Methyl alcohol

56

n-Pentane

46

Propane

46

Toluene

41

Selected from NFPA 68, Guide for Venting of Deflagrations (Quincy, MA: National Fire Protection Association, 2018).

Britton proposed the following correlation for estimating the burning parameter, Su:11

11Britton, L. G. “Using Heats of Oxidation to Evaluate Flammability Hazards.” Process Safety Progress 21, no. 1 (2000): 1–24.

Su=166634.23(ΔHcz)0.180(ΔHcz)2(10-26)

where

Su is the burning parameter (m/s),

ΔHcis the heat of combustion of the fuel (kcal/mol),and

z is the stoichiometric ratio of oxygen to fuel.

For a fuel with a composition of CcHhOmNnXx, the stoichiometric ratio of oxygen to fuel is calculated from

z=c+hx2m4(10-27)

Example 10-7

A room is used for dispensing flammable liquids. The liquids are expected to have a burning parameter of 50 cm/s. The room is 9 m long by 6 m wide by 6 m in height. Three of the walls are shared with an adjoining structure. The fourth and larger wall of the room is on the outer surface of the structure. The three inside walls are capable of withstanding a pressure of 0.05 barg. Estimate the vent area required for this operation.

Solution

The vent must be installed on the larger outer wall to vent the combustion away from the adjoining structure. The venting constant for this flammable vapor is calculated using Equation 10-25. Assume no turbulent augmentation, so λ = 1. Then,

C=0.0223λSu=0.0223(1)(0.050 m/s)=1.12×103 bar1/2

Equation 10-23 is used to estimate the required vent area. The total surface area of the room (including floor and ceiling) is

As=(2)(9m)(6m)+(2)(6m)(6m)+(2)(6m)(9m)=288m2

The required vent area is then

Av=AsCPred=(288m2)(1.12×103 bar1/2)0.05bar=1.4m2

The area of the large outer wall has more than adequate space to accommodate this vent.

Vents for Dusts and Hybrid Mixtures

The vent design for dusts and hybrid mixtures is based on the definition of a deflagration index for gases or dusts:

KSt=(dPdt)maxV1/3(10-28)

where

KSt is the deflagration index for the dust (bar m/s),

(dP/dt)max is the maximum pressure increase, determined experimentally (bar/s), and

V is the volume of the vessel (m3).

Chapter 6 discusses how to measure the deflagration index for dusts and provides a table of typical values.

When the structure initial pressure is between –0.2 barg and 0.2 barg, and the vent opening pressure, Pstat, is less than 0.75 barg, then the following equation is used to estimate the vent area required:

Av=1×104KStV3/4(1+1.54P4/3stat)PmaxPred1(10-29)

where

Av is the required vent area (m2),

KSt is the deflagration index for the dust, given by Equation 10-28 (bar m/s),

V is the internal volume of the enclosure (m3),

Pstat is the opening pressure for the vent (barg),

Pmax is the maximum pressure of an unvented deflagration initially at atmospheric pressure (barg),

Pred is the maximum internal pressure developed in the structure during the venting process (barg). This is based on the pressure rating of the weakest element of the structure.

Equation 10-29 applies only for the following conditions:

0.1 m3  V  10,000 m310 bar m/s  KSt  800 bar m/s(10-30)5 barg  Pmax  12 barg

NFPA 68 provides equations for other conditions.

Example 10-8

Consider again the room of Example 10-7, but now assume it is handling a dust. In this case, the walls have been reinforced to withstand a pressure of 0.4 barg (Pred). The vent will open at 0.2 barg (Pstat), the maximum pressure of the exploding dust is 10 barg (Pmax), and KSt of the dust is 200 bar-m/s. Estimate the vent area required to protect this enclosure.

Solution

The volume of the structure is

(9 m)(6 m)(6 m)=324 m3

All of the conditions of Equations 10-30 apply, and Equation 10-29 is used to solve this problem. Substituting the numbers into the fixed units equation,

Av=1×104KStV3/4(1+1.54P4/3stat)PmaxPred1 =(1×104)(200 bar m/s)(324 m3)3/4[1+1.54(0.2 barg)4/3]10 barg0.4 barg1=8.83 m2

10-6 Venting for Fires External to the Process

Fires external to process vessels can result in heating and boiling of process liquids, as shown in Figure 10-9. Venting is required to prevent explosion of these vessels.

A figure displays the heating of process vessels by means of external fire.
Figure 10-9 Heating of a process vessel as a result of an external fire. Venting is required to prevent vessel rupture. For most fires, only a fraction of the external vessel is exposed to fire.

Two-phase flow during these reliefs is possible, but not likely. For runaway reactor reliefs, the energy is generated by reaction throughout the entire reactor liquid contents. For heating caused by external fire, the heating occurs only at the surface of the vessel. Thus, for vessels exposed to fire, the liquid boiling will occur only next to the wall; the resulting two-phase foam or froth at the liquid surface will not have a substantial thickness. Two-phase flow during fire relief can be prevented by providing a suitable vapor space above the liquid within the vessel.

Two-phase fire relief equations are available to support conservative designs. Leung provides an equation for the maximum temperature based on an energy balance around the heated vessel.12 This equation assumes a constant heat input rate Q:

12J. C. Leung. “Simplified Vent Sizing Equations for Emergency Relief Requirements in Reactors and Storage Vessels.” AICHE Journal 32, no. 10 (1986): 1622.

TmTs=QGTACV[ln(moVQGTAvfgΔHV)1]+VΔHVmoCVvfg(10-31)

where

Tm is the maximum temperature in the vessel (degrees),

Ts is the set temperature corresponding to the set pressure (degrees),

Q is the constant heat input rate (energy/time),

GT is the mass flux through the relief (mass/volume-time),

A is the area of the relief (area),

CV is the heat capacity at constant volume (energy/mass-degrees),

mo is the liquid mass in the vessel (mass),

V is the volume of the vessel (volume),

vfg is the specific volume difference between the vapor and liquid phases (volume/mass), and

ΔHv is the heat of vaporization of the liquid (energy/mass).

The solution to Equation 10-31 for GTA is obtained by an iterative or trial-and-error technique. Equation 10-31 is likely to produce multiple roots, in which case the correct solution is the minimum mass flux GT. For the special case of no overpressure, Tm = Ts, and Equation 10-31 reduces to

A=QmovfgGTVΔHv(10-32)

Various relationships have been recommended for estimating the heat added to a vessel that is engulfed in fire. For regulated materials, the OSHA 1910.106 criterion is mandatory.13 Other standards are also available.14,15 Crozier, after analysis of the various standards, recommended the following equations for determining the total heat input Q:16

13OSHA 1910.106, Flammable and Combustible Liquids (Washington, DC: U.S. Department of Labor, 1996).

14API Standard 2000, Venting Atmospheric and Low-Pressure Storage Tanks (Nonrefrigerated and Refrigerated), 5th ed. (Washington, DC: American Petroleum Institute, 1998).

15NFPA 30, Flammable and Combustible Liquids Code (Quincy, MA: National Fire Protection Association, 2000).

16R. A. Crozier. “Sizing Relief Valves for Fire Emergencies.” Chemical Engineering (October 28, 1985), pp. 49-54

Q=20,000Afor20<A<200       Q=199,300A0.566for200<A<1000Q=936,400A0.338for1000<A<2800Q=21,000A0.82forA>2800(10-33)

where

A is the area absorbing heat (in ft2) for the following geometries:

  • For spheres, 55% of total exposed area;

  • For horizontal tanks, 75% of total exposed area;

  • For vertical tanks, 100% of total exposed area for first 30 ft; and

Q is the total heat input to the vessel (in Btu/hr).

The mass flux GT is determined using Equation 10-16 or 10-19.

API 520 suggests a slightly different approach to estimate the heat flux to process equipment as a result of a fire.17 If prompt firefighting is available and if the flammable material is drained away from the vessel, then the heat flux is estimated using the following equation:

17API RP 520, Sizing, Selection, and Installation of Pressure-Relieving Devices in Refineries, 6th ed. (Washington, DC: American Petroleum Institute, 1993).

Q=21,000FA0.82(10-34)

If adequate firefighting and drainage do not exist, then the following equation is recommended:

Q=34,500FA0.82(10-35)

where

Q is the total heat input through the surface of the vessel (BTU/hr),

F is an environment factor (unitless), and

A is the total wetted surface of the vessel (ft2).

The environment factor F is used to account for vessel protection from insulation. A number of values for various insulation thicknesses are shown in Table 10-3.

Table 10-3 Environment Factors F for Equations 10-34 and 10-35

Insulation thickness (in)

Environment factor F

0

1.0

1

0.30

2

0.15

4

0.075

The surface area A is the area of the vessel wetted by its internal liquid with a height less than 25 ft above the flame source. Wong provided considerably more detail on how to determine this as well as a number of equations for various vessel geometries.18

18W. Y. Wong. “Fires, Vessels, and the Pressure Relief Valve.” Chemical Engineering (May 2000) 107: 84.

Example 10-9

Leung reported on the computation of the required relief area for a spherical propane vessel exposed to fire19. The vessel has a volume of 100 m3 and contains 50,700 kg of propane. A set pressure of 4.5 bars absolute is required. This corresponds to a set temperature, based on the saturation pressure, of 271.5 K. At these conditions, the following physical property data are reported:

19J. C. Leung. “Simplified Vent Sizing Equations for Emergency Relief Requirements in Reactors and Storage Vessels.” AICHE Journal 32, no. 10 (1986): 1622.

CP=CV=2.41×103 J/kgKΔHv=3.74×105 J/kgvfg=0.1015 m3/kg

The molecular weight of propane is 44.

Solution

The problem is solved by assuming no overpressure during the relief. The relief vent area calculated is larger than the actual area required for a real relief device with overpressure.

The diameter of the sphere is

d=(6Vπ)1/3=[(6)(100m3)(3.14)]1/3=5.76m

The surface area of the sphere is

πd2=(3.14)(5.76m)2=104.2m2=1121ft2

The area exposed to heat is given by the geometry factors provided with Equation 10-33:

A=(0.55)(1121ft2)=616ft2

The total heat input is found using Equation 10-33:

Q=199,300A0.566=(199,300)(616ft2)0.566=7.56×106Btu/hr=2100  Btu/sec=2.22×106 J/s

If we use Equation 10-34 and assume that the vessel is full of liquid, then the entire vessel surface area is exposed to the fire. If we also assume that no insulation is present, then F = 1.0. Then,

Q=21,000FA0.82=(21,000)(1.0)(1121ft2)0.82=6.65×106Btu/hr

which is close to the value estimated using Equation 10-33. From Equation 10-16 and assuming ψ = 1.0, we obtain

GT=QmA=0.9ψΔHVvfggcTsCP=(0.9)(1.0)(3.74×105 J/kg0.1015 m3/kg)(1NmJ)×1(kg m/s2)/N(271.5K)(2.41×103 J/kgK)(1 Nm/J)=4.10×103kg/m2s

The required vent area is determined from Equation 10-32:

A=QmoνfgGTVΔHv=(2.22×106J/s)(50,700kg)(0.1015m3/kg)(4.10×103kg/m2s)(100m3)(3.74×105J/kg)=0.0745m2

The required relief diameter is

d=4Aπ=(4)(0.0745m2)3.14=0.308m=12.1in

An alternative way to look at the problem might be to ask the question: What initial fill fraction should be specified in the tank to avoid two-phase flow during a fire exposure incident? No tested correlations are presently available to compute the height of a foam layer above the boiling liquid.

For fire reliefs with single-phase vapor flow, the equations provided in Section 10-3 are used to determine the size of the relief.

As mentioned previously, two-phase flow discharges for fire scenarios are possible, but not likely. To size the relief for fire and a single-vapor phase, use the heat input determined from Equations 10-33 through 10-35, and determine the vapor mass flow rate through the relief by dividing the heat input by the heat of vaporization of the liquid. This assumes that all the heat input from the fire is used to vaporize the liquid. The relief area is then determined using Equations 10-12 through 10-14.

10-7 Reliefs for Thermal Expansion of Process Fluids

Liquids contained within process vessels and piping will normally expand when heated. The expansion will damage pipes and vessels if the pipe or vessel is filled completely with fluid and the liquid is blocked in.

A typical situation is thermal expansion of water in cooling coils in a reactor, shown in Figure 10-10. If the coils are filled with water and are accidentally blocked in, the water will expand when heated by the reactor contents, leading to damage to the cooling coils.

A figure illustrates the damage of cooling coils due to external heating of blockage in cooling fluid.
Figure 10-10 Damage to cooling coils as a result of external heating of blocked-in cooling fluid.

Relief vents are installed in these systems to prevent damage resulting from liquid expansion. Although this may appear to be a minor problem, damage to heat exchange systems can result in (1) contamination of product or intermediate substances, (2) subsequent corrosion problems, (3) substantial plant outages, and (4) large repair expenses. Failure in heat exchange equipment is also difficult to identify, and repairs are time-consuming.

A thermal expansion coefficient for liquids, β, is defined as

β=1V(dVdT)(10-36)

where

V is the volume of the fluid (volume), and

T is the temperature (degrees).

Table 10-4 lists thermal expansion coefficients for a number of substances. Water behaves in an unusual fashion. Its thermal expansion coefficient decreases with increasing temperature up to about 4°C, after which the thermal expansion coefficient increases with temperature. Coefficients for water are readily determined from the steam tables.

Table 10-4 Thermal Expansion Coefficients for a Variety of Liquids

Liquid

Density at 20°C (kg/m3)

Thermal expansion coefficient (°C–1)

Alcohol, ethyl

791

112 × 10–5

Alcohol, methyl

792

120 × 10–5

Benzene

877

124 × 10–5

Carbon tetrachloride

1595

124 × 10–5

Ether, ethyl

714

166 × 10–5

Glycerin

1261

51 × 10–5

Mercury

13,546

18.2 × 10–5

Turpentine

873

97 × 10–5

Source: G. Shortley and D. Williams. Elements of Physics, 4th ed. (Englewood Cliffs, NJ: Prentice Hall, 1965), p. 302.

The volumetric expansion rate Qv through the relief resulting from thermal expansion is

Qv=dVdt=dVdTdTdt(10-37)

By applying the definition of the thermal expansion coefficient, given by Equation 10-36, we obtain

Qv=βVdTdt(10-38)

For a pipe or process vessel heated externally by a hot fluid, the energy balance of the fluid is given by

mCPdTdt=UA(TTa)(10-39)

where

T is the temperature of the fluid (degrees),

CP is the heat capacity of the liquid (energy/mass-degrees),

UA is an overall heat transfer coefficient (energy/time-degrees), and

Ta is the ambient temperature (degrees).

It follows that

dTdt=UAmCP(TTa)(10-40)

Substituting into Equation 10-41, we obtain

Qv=βVmCPUA(TTa)(10-41)

and, with the definition of the liquid density ρ,

Qv=βρCPUA(TTa)(10-42)

Equation 10-42 describes the fluid expansion only at the beginning of heat transfer, when the fluid is initially exposed to the external temperature Ta. The heat transfer will increase the temperature of the liquid, changing the value of T. However, it is apparent that Equation 10-42 provides the maximum thermal expansion rate, sufficient for sizing a relief device.

The volumetric expansion rate Qv is subsequently used in an appropriate equation to determine the relief vent size.

Example 10-10

The cooling coil in a reactor has a surface area of 10,000 ft2. Under the most severe conditions, such coils can contain water at 32°F and can be exposed to superheated steam at 400°F. Given a heat transfer coefficient of 50 BTU/hr-ft2-°F, estimate the volumetric expansion rate of the water in the cooling coils in gpm.

Solution

The expansion coefficient β for water at 32°F should be used. This is estimated using liquid volumetric data from the steam tables over a short range of temperatures around 32°F. However, the steam tables do not provide liquid-water–specific volume data at temperatures below 32°F. A value between 32°F and some appropriate higher temperature will suffice. From the steam tables:

Temperature (°F)

Specific volume (ft3/lbm)

32

0.01602

50

0.01603

The expansion coefficient is computed using Equation 10-36:

β=1vdvdT=10.016025ft3/1bm(0.016030.016025032)(ft3/1bm°F)=3.47×105 oF1

The volumetric expansion rate is given by Equation 10-42:

Qv=βρCPUA(TTa)=(3.47×105/°F)(50 BTU/hr-ft2 oF)(10,000ft2)(40032)°F(62.4 1bm/ft3)(1Btu/1bm°F)=102 ft3/hr=12.7gpm

The relief device vent area must be designed to accommodate this volumetric flow.

Suggested Reading

Deflagration Vents

W. Bartknecht. “Pressure Venting of Dust Explosions in Large Vessels.” Plant/Operations Progress 5, no. 4 (1986): 196.

Frank T. Bodurtha. Industrial Explosion Prevention and Protection (New York, NY: McGraw-Hill, 1980).

Ian Swift and Mike Epstein. “Performance of Low Pressure Explosion Vents.” Plant/Operations Progress 6, no. 2 (1987): 98–107.

Relief Codes and Standards

API RP 520, Recommended Practice for the Sizing, Selection, and Installation of Pressure-Relieving Systems in Refineries, 9th ed. (Washington, DC: American Petroleum Institute, 2014).

API RP 521, Guide for Pressure-Relieving and Depressurizing Systems, 3rd ed. (Washington, DC: American Petroleum Institute, 2015).

API Standard 2000, Venting Atmospheric and Low-Pressure Storage Tanks (Nonrefrigerated and Refrigerated), 7th ed. (Washington, DC: American Petroleum Institute, 2014).

ASME Boiler and Pressure Vessel Code (New York, NY: American Society of Mechanical Engineers, 2017).

NFPA 68, Guide for Venting of Deflagrations (Quincy, MA: National Fire Protection Association, 1998).

Two-Phase Flow

AICHE Center for Chemical Process Safety. Guidelines for Pressure Relief and Effluent Handling Systems, 2nd ed. (Hoboken, NJ: John Wiley, 2017).

G. W. Boicourt. “Emergency Relief System (ERS) Design: An Integrated Approach Using DIERS Methodology.” Process Safety Progress 14, no. 2 (1995): 68–74.

R. D’Alessandro. “Thrust Force Calculations for Pressure Safety Valves.” Process Safety Progress 25, no. 3 (2006): 203.

R. Darby. “Relief Sizing for Deflagrations.” Process Safety Progress 25, no. 2 (2006): 130.

H. K. Fauske. “Determine Two-Phase Flows during Release.” Chemical Engineering Progress (February 1999): 55–58.

H. K. Fauske. “Emergency Relief System (ERS) Design.” Chemical Engineering Progress (August 1985): 53–56.

H. K. Fauske. “Flashing Flows or Some Practical Guidelines for Emergency Releases.” Plant/Operations Progress (July 1985): 132.

H. K. Fauske. “Generalized Vent Sizing Nomogram for Runaway Chemical Reactions.” Plant/Operations Progress 3, no. 4 (1984): 213.

H. Fauske. “Managing Chemical Reactivity: Minimum Best Practice.” Process Safety Progress 25, no. 2 (2006): 120.

H. K. Fauske. “Properly Sized Vents for Nonreactive and Reactive Chemicals.” Chemical Engineering Progress (February 2000): 17.

H. Fauske. “Revisiting DIERS’ Two-Phase Methodology for Reactive Systems Twenty Years Later.” Process Safety Progress 25, no. 3 (2006): 180.

H. K. Fauske and J. C. Leung. “New Experimental Technique for Characterizing Runaway Chemical Reactions.” Chemical Engineering Progress (August 1985): 39–46.

K. E. First and J. E. Huff. “Design Charts for Two-Phase Flashing Flow in Emergency Pressure Relief Systems.” Paper presented at 1988 AICHE Spring National Meeting.

Harold G. Fisher. “DIERS Research Program on Emergency Relief Systems.” Chemical Engineering Progress (August 1985): 33.

H. G. Fisher, H. S. Forrest, S. S. Grossel, J. E. Huff, A. R. Muller, J. A. Noronha, D. A. Shaw, and R. J. Tilley. Emergency Relief System Design Using DIERS Technology (New York, NY: American Institute of Chemical Engineers, 1992).

J. C. Leung. “A Generalized Correlation for One-Component Homogeneous Equilibrium Flashing Choked Flow.” AICHE Journal 32, no. 10 (1986): 1743.

J. C. Leung. “Simplified Vent Sizing Equations for Emergency Relief Requirements in Reactors and Storage Vessels.” AICHE Journal 32, no. 10 (1986): 1622.

J. C. Leung and H. G. Fisher. “Two-Phase Flow Venting from Reactor Vessels.” Journal of Loss Prevention 2, no. 2 (1989): 78.

J. C. Leung and M. A. Grolmes. “The Discharge of Two-Phase Flashing Flows in a Horizontal Duct.” AICHE Journal 33, no. 3 (1987): 524.

J. C. Leung and M. A. Grolmes. “A Generalized Correlation for Flashing Choked Flow of Initially Subcooled Liquid.” AICHE Journal 34, no. 4 (1988): 688.

S. Waldram, R. McIntosh, and J. Etchells. “Thrust Force Calculations for Pressure Safety Valves.” Process Safety Progress 25, no. 3 (2006): 214.

Problems

10-1. Fill in the blanks in the table.

Relief configuration

MAWP

Set pressure

Maximum set pressure

Maximum accumulated pressure

Allowable overpressure

a. Single relief, nonfire

100 psig

100 psig

 

 

 

b. Single relief, nonfire

100 psig

90 psig

 

 

 

c. Primary relief, nonfire, with secondary relief

100 psig

100 psig

 

 

 

d. Secondary relief, nonfire

100 psig

100 psig

 

 

 

e. Primary relief, fire

100 psig

90 psig

 

 

 

f. Secondary relief, fire

100 psig

100 psig

 

 

 

g. Supplemental relief

100 psig

90 psig

 

 

 

h. Single relief, nonfire

10 barg

barg

 

 

 

i. Single relief, nonfire

10 barg

9 barg

 

 

 

j. Primary relief, nonfire with secondary relief

10 barg

10 barg

 

 

 

k. Secondary relief, nonfire

10 barg

10 barg

 

 

 

l. Primary relief, fire

10 barg

9 barg

 

 

m. Secondary relief, fire

10 barg

10 barg

 

 

 

n. Supplemental relief

10 barg

9 barg

 

 

 

10-2. Calculate the diameter of a certified capacity spring-type liquid relief for the following conditions:

Pump capacity at Δp

Set pressure

Overpressure

Backpressure

Valve type

(ρ /ρref)

a. 100 gpm

50 psig

5 psig

5 psig

Conventional

1.0

b. 200 gpm

100 psig

10 psig

10 psig

Balanced-bellows

1.3

c. 5 m3/s

5 barg

0.5 barg

0.5 barg

Balanced-bellows

1.2

d. 7 m3/s

10 barg

1 barg

1 barg

Conventional

1.0

10-3. Calculate the diameter of a spring-type vapor relief for the following conditions. Assume for each case a heat capacity ratio γ = 1.3 and a compressibility z = 1.0.

Set pressure

Temperature

Molecular weight

Mass flow

Overpressure

Backpressure

a. 100 psig

100°F

28

50 lbm/hr

10 psig

10 psig

b. 150 psig

200°F

44

100 lbm/hr

30 psig

15 psig

c. 200 psig

100°F

28

150 lbm/hr

10 psig

20 psig

d. 8 barg

300 K

44

10 kg/s

1 barg

1 barg

e. 10 barg

400 K

28

20 kg/s

2 barg

2 barg

f. 20 barg

400 K

28

30 kg/s

2 barg

1 barg

10-4. Calculate the required diameter for certified-capacity liquid rupture discs for the following conditions. Assume a liquid specific gravity of 1.2 for all cases.

Liquid flow

Set pressure

Overpressure

Backpressure

a. 500 gpm

100 psig

10 psig

5 psig

b. 100 gpm

50 psig

5 psig

2 psig

c. 5 m3/s

10 barg

1 barg

0.5 barg

d. 10 m3/s

20 barg

2 barg

1 barg

10-5. Calculate the diameter for rupture discs in vapor service for the following conditions. Assume that nitrogen is the vent gas.

Gas flow

Temperature

Set pressure

Overpressure

Backpressure

a. 100 lbm/hr

100oF

100 psig

10 psig

5 psi

b. 200 lbm/hr

150oF

150 psig

15 psig

10 psi

c. 10 kg/s

400 K

10 barg

1 barg

0.5 barg

d. 20 kg/s

500 K

20 barg

1 barg

0.5 barg

10-6. Determine the relief diameter for the following two-phase flow conditions. Assume in all cases that L/D = 0.0.

 

a

b

c

d

Reaction mass

10,000 lbm

10,000 lbm

4000 kg

4000 kg

Volume

200 ft3

500 ft3

15 m3

500 m3

Set pressure

100 psia

100 psia

7 bara

7 bara

Set temperature

500°F

500°F

500 K

500 K

(dT/dt)s

0.5°F/s

0.5°F/s

2.0 K/s

2.0 K/s

Maximum pressure

120 psia

120 psia

8 bara

9 bara

Maximum temperature

520°F

520°F

540 K

540 K

(dT/dt)m

0.66°F/s

0.66°F/s

2.4 K/s

2.6 K/s

Liquid-specific volume

0.02

0.2

0.02

0.02

Vapor-specific volume

1.4

1.4

1.4

1.4

Heat capacity

1.1 Btu/lbm°F

1.1 Btu/lbm°F

5.0 kJ/kg K

5.0 kJ/kg K

Heat of vaporization

130 Btu/lbm

130 Btu/lbm

300 kJ/kg

130 kJ/kg

10-7. Determine the deflagration vent size for the following structures:

Vapors

a

b

c

d

Internal area of structure

1000 ft3

1000 ft3

300 m3

300 m3

Turbulent augmentation factor, λ

1.0

1.5

1.0

1.5

Max. internal pressure, Pred

0.05 bar

0.10 bar

0.05 bar

0.10 bar

Gas

Methane

Hydrogen

Methane

Hydrogen

Dusts

e

f

g

h

Volume of structure

1000 ft3

1000 ft3

30 m3

30 m3

Deflagration index, KSt, bar m/s

200

300

200

300

Opening pressure of vent, Pstat

3 psig

6 psig

0.2 barg

0.4 barg

Max. pressure of unvented, Pmax

150 psig

200 psig

10 barg

15 barg

Max. internal pressure, Pred

6 psig

8 psig

0.4 barg

0.6 barg

10-8. A cooling coil contains ethyl alcohol. The heat capacity of the alcohol is 0.58 kcal/kg°C, and its density is 791 kg/m3. Determine the relief volumetric flow required. Assume a cooling coil area of 300 m2 and a heat transfer coefficient of 1000 J/s m2 K. The ambient temperature is 300 K and the maximum temperature to which the alcohol is exposed is 550 K.

10-9. Home hot-water heaters contain relief devices to provide protection in the event that the heater controls fail and the water is heated to a high temperature. A typical water heater contains 40 gal of water and has a heat input of 42,000 Btu/hr. If the heater is equipped with a 150-psia capacity-certified spring relief device, compute the area required for the relief. Single-phase flow is expected. Assume no overpressure.

Also compute the relief vent size assuming all vapor relief. Assume 20% backpressure.

10-10. A cylindrical tank, 4 ft in diameter and 10 ft long, is completely filled with water and blocked in. Estimate the thermal expansion rate of the water if the water is at 50°F and the steel shell of the tank is suddenly heated to 100°F by the sun. Assume a heat transfer coefficient of 50 Btu/hr ft2 °F and that only the top half of the tank is heated.

If the tank is exposed to fire, what is the required relief area? Assume no overpressure.

The tank MAWP is 200 psig.

10-11. A 10-ft-wide by 10-ft-long by 10-ft-high shed is used to store tanks of methane. What deflagration vent area is required? Assume a maximum internal overpressure of 0.1 psig.

10-12. A horizontal vessel, 3 m long and 1 m in diameter, contains water. What relief size is required to protect the vessel from fire exposure? Assume the following: vapor relief only, MAWP of 14 barg, conventional capacity-certified spring-operated relief.

Additional homework problems are available in the Pearson Instructor Resource Center.

..................Content has been hidden....................

You can't read the all page of ebook, please click here login for view all page.
Reset