Chapter 28
28.1 Overcurrent Protection 28-1
Introduction • Fault Levels • Surface Current Levels • Reclosing and Inrush • Cold Load Pickup • Calculation of Fault Current • Current Limiting Fuses • Rules for Application of Fuses • More Overcurrent Rules • Capacitor Fusing • Conductor Burndown • Protective Device Numbers • Protection Abbreviations • Simple Coordination Rules • Lightning Characteristics • Arc Impedance
28.2 Transformers 28-15
Saturation Curve • Insulation Levels • Δ-Y Transformer Banks
28.3 Instrument Transformers 28-17
Two Types • Accuracy • Potential Transformers • Current Transformer • H-Class • Current Transformer Facts • Glossary of Transducer Terms
28.4 Loading 28-20
Transformer Loading Basics • Examples of Substation Transformer Loading Limits • Distribution Transformers • Ampacity of Overhead Conductors • Emergency Ratings of Equipment
28.5 Miscellaneous Loading Information 28-23
Jim Burke
Quanta Technology
The distribution system shown in Figure 28.1 illustrates many of the features of a distribution system making it unique. The voltage level of a distribution system can be anywhere from about 5 kV to as high as 35 kV with the most common voltages in the 15 kV class. Areas served by a given voltage are proportional to the voltage itself, indicating that, for the same load density, a 35 kV system can serve considerably longer lines. Lines can be as short as a mile or two and as long as 20 or 30 miles. Typically, however, lines are generally 10 miles or less. Short-circuit levels at the substation are dependent on voltage level and substation size. The average short-circuit level at a distribution substation has been shown, by survey, to be about 10,000 A. Feeder load current levels can be as high as 600 A but rarely exceed about 400 A with many never exceeding a couple of hundred amperes.
There are two types of faults: low impedance and high impedance. A high-impedance fault is considered to be a fault that has a high Z due to the contact of the conductor to the earth, i.e., Zf is high. By this definition, a bolted fault at the end of a feeder is still classified as a low-impedance fault. A summary of findings on faults and their effects is as follows.
Low-impedance faults or bolted faults can be either very high in current magnitude (10,000 A or above) or fairly low, for example, 300 A at the end of a long feeder. Faults that can be detected by normal protective devices are all low-impedance faults. These faults are such that the calculated value of fault current assuming a “bolted fault” and the actual are very similar. Most detectable faults, per study data, do indeed show that fault impedance is close to 0 Ω. This implies that the phase conductor either contacts the neutral wire or that the arc to the neutral conductor has a very low impedance. An EPRI study performed by the author over 10 years ago indicated that the maximum fault impedance for a detectable fault was 2 Ω or less. Figure 28.2 indicates that 2 Ω of fault impedance influences the level of fault current depending on location of the fault. As can be seen, 2 Ω of fault impedance considerably decreases the level of fault current for close-in faults but has little effect for faults some distance away. What can be concluded is that fault impedance does not significantly affect faulted circuit indicator performance since low level faults are not greatly altered.
High-impedance faults are faults that are low in value, i.e., generally less than 100 A due to the impedance between the phase conductor and the surface on which the conductor falls. Figure 28.3 illustrates that most surface areas, whether wet or dry, do not conduct well. If one considers the fact that an 8 ft ground rod sunk into the earth more often than not results in an impedance of 100 Ω or greater, then it is not hard to visualize the fact that a conductor simply lying on a surface cannot be expected to have a low impedance. These faults, called high-impedance faults, do not contact the neutral and do not arc to the neutral. They are not detectable by any conventional means and are not to be considered at all in the evaluation of fault current indicators (FCIs) and most other protective devices.
See Figure 28.3.
On most systems where most faults are temporary, the concept of reclosing and the resulting inrush currents are a fact of life. Typical reclosing cycles for breakers and reclosers are different and are shown in Figure 28.4.
These reclosing sequences produce inrush primarily resulting from the connected transformer kVA. This inrush current is high and can approach the actual fault current level in many instances. Figure 28.5 shows the relative magnitude of these currents. What keeps most protective devices from operating is that the duration of the inrush is generally short and as a consequence will not melt a fuse or operate a time delay relay.
Cold load pickup, occurring as the result of a permanent fault and long outage, is often maligned as the cause of many protective device misoperations. Figure 28.6 illustrates several cold load pickup curves developed by various sources. These curves are normally considered to be composed of the following three components:
When a lateral fuse misoperates, it is probably not the result of this loss of diversity, i.e., the fuse is overloaded. This condition is rare on most laterals. Relay operation during cold load pickup is generally the result of a trip of the instantaneous unit and probably results from high inrush. Likewise, an FCI operation would not appear to be the result of loss of diversity but rather the high inrush currents. Since inrush occurs during all energization and not just as a result of cold load pickup, it can be concluded that cold load pickup is not a major factor in the application of FCIs.
Line Faults
where
Zℓ is the line impedance
2Zℓ is the loop impedance assuming the impedance of the phase conductor and the neutral conductor are equal (some people use a 1.5 factor)
Line-to-line fault =
Transformer Faults
where
Current limiting fuses (CLFs) use a fusible element (usually silver) surrounded by sand (Figure 28.7). When the element melts, it causes the sand to turn into fulgurite (glass). Since glass is a good insulator, this results in a high resistance in series with the faults. This limits not only the magnitude of the fault but also the energy. All this can happen in less than a half cycle.
CLFs are very good at interrupting high currents (e.g., 50,000 A). They historically have had trouble (general purpose and backup) with low level fault currents and overloads, where the fuse tube melts before the element (i.e., these two fuses are not considered to be “full range,” since they do not necessarily interrupt low currents that melt the element). There are now “full range” CLFs in the market (see Figure 28.7).
The three types of CLFs are defined as follows:
After 15 min outage | 200% for 0.5 s |
140% for 5 s | |
After 4 h, all electric | 300% for 5 min |
Fault Type | Multiplying Factor |
Three phase | N |
Phase to phase | 87 (N) |
Phase to ground | 1.73 (N) |
where N is the ratio of Vprimary/Vsecondary. |
Zpositive | Z0 | |
Cable UG | 0.31 + j0.265 | 1.18 + j0.35 |
Spacer | 0.3 + j0.41 | 1.25 + j2.87 |
Tree wire | 0.3 + j0.41 | 1.25 + j2.87 |
Armless | 0.3 + j0.61 | 0.98 + j2.5 |
Open | 0.29 + j0.66 | 0.98 + j2.37 |
Conductor burndown is a function of (1) conductor size, (2) whether the wire is bare or covered, (3) the magnitude of the fault current, (4) climatic conditions such as wind, and (5) the duration of the fault current.
If burndown is less of a problem today than in years past, it must be attributed to the trend of using heavier conductors and a lesser use of covered conductors. However, extensive outages and hazards to life and property still occur as the result of primary lines being burned down by flashover, tree branches falling on lines, etc. Insulated conductors, which are used less and less, anchor the arc at one point and thus are the most susceptible to being burned down. With bare conductors, except on multigrounded neutral circuits, the motoring action of the current flux of an arc always tends to propel the arc along the line away from the power source until the arc elongates sufficiently to automatically extinguish itself. However, if the arc encounters some insulated object, the arc will stop traveling and may cause line burndown.
With tree branches falling on bare conductors, the arc may travel away and clear itself; however, the arc will generally reestablish itself at the original point and continue this procedure until the line burns down or the branch falls off the line. Limbs of soft spongy wood are more likely to burn clear than hard wood. However ½ in. diameter branches of any wood, which cause a flashover, are apt to burn the lines down unless the fault is cleared quickly enough.
Figure 28.9 shows the burndown characteristics of several weatherproof conductors. Arc damage curves are given as arc is extended by traveling along the phase wire; it is extinguished but may be reestablished across the original path. Generally, the neutral wire is burned down.
The devices in the switching equipment are referred to by numbers, with appropriate suffix letters (when necessary), according to the functions they perform. These numbers are based on a system that has been adopted as standard for automatic switchgear by the American Standards Association (Table 28.1).
Protective Device Numbers
Device No. |
Function and Definition |
11 |
Control power transformer is a transformer that serves as the source of AC control power for operating AC devices |
24 |
Bus-tie circuit breaker serves to connect buses or bus sections together |
27 |
AC undervoltage relay is one which functions on a given value of single-phase AC under voltage |
43 |
Transfer device is a manually operated device that transfers the control circuit to modify the plan of operation of the switching equipment or of some of the devices |
50 |
Short-circuit selective relay is one which functions instantaneously on an excessive value of current |
51 |
AC overcurrent relay (inverse time) is one which functions when the current in an AC circuit exceeds a given value |
52 |
AC circuit breaker is one whose principal function is usually to interrupt short-circuit or fault currents |
64 |
Ground protective relay is one which functions on failure of the insulation of a machine, transformer, or other apparatus to ground; this function is, however, not applied to devices 51N and 67N connected in the residual or secondary neutral circuit of current transformers |
67 |
AC power directional or AC power directional overcurrent relay is one which functions on a desired value of power flow in a given direction or on a desired value of overcurrent with AC power flow in a given direction |
78 |
Phase–angle measuring relay is one which functions at a predetermined phase angle between voltage and current |
87 |
Differential current relay is a fault-detecting relay that functions on a differential current of a given percentage or amount |
CS—Control switch
X—Auxiliary relay
Y—Auxiliary relay
YY—Auxiliary relay
Z—Auxiliary relay
N—Neutral
SI—Seal-in
H—High set unit of relay
L—Low set unit of relay
OC—Operating coil
RC—Restraining coil
TC—Trip coil
“a”—closed when main device is in energized or operated position
“b”—closed when main device is in de-energized or nonoperated position
A—Automatic
ER—Electrically reset
HR—Hand rest
M—Manual
TDC—Time-delay closing
TDDO—Time-delay dropping out
TDO—Time-delay opening
To prevent any possible conflict, one letter or combination of letters has only one meaning on individual equipment. Any other words beginning with the same letter are written out in full each time, or some other distinctive abbreviation is used.
There are few things more confusing in distribution engineering than trying to find out rules of overcurrent coordination, i.e., what size fuse to pick or where to set a relay, etc. The patented (just kidding) Burke 2× rule states that when in doubt, pick a device of twice the rating of what it is you are trying to protect, as shown in Figure 28.10. This rule picks the minimum value you should normally consider and is generally as good as any of the much more complicated approaches you might see. For various reasons, you might want to go higher than this, which is usually okay. To go lower, you will generally get into trouble. One exception to this rule is the fusing of capacitors where minimum size fusing is important to prevent case rupture.
Although arcs are quite variable, a commonly accepted value for currents between 70 and 20,000 A has been an arc drop of 440 V/ft, essentially independent of current magnitude:
Lightning Discharge Current vs. Location
Col. 1 |
Col. 2 |
Col. 3 |
Col. 4 |
Urban Circuits (%) |
Semiurban Circuits (%) |
Rural Circuits (%) |
Discharge Currents (A) |
20 |
35 |
45 |
1,000 |
1.6 |
7 |
12 |
5,000 |
0.55 |
3.5 |
6 |
10,000 |
0.12 |
0.9 |
2.4 |
20,000 |
0.4 |
40,000 |
Zarc = 440l/I l = length of arc (in feet) I = current
Assume
IF = 5000 A = I
Arc length = 2 ft
Zarc = 440 × (2/5000) = 0.176 Ω i.e., Arc impedance is pretty small.
Let us say you have a 120 V secondary fault and the distance between the phase and neutral is 1 ft. If the current level was 500 A, then the arc resistance would be (440 × 1)/500 = 0.88 Ω, which is significant in its effect on fault levels.
See Figure 28.11.
Table 28.3 gives the American standard test levels for insulation of distribution transformers.
Insulation Levels for Transformer Windings and Bushings
Windings |
Bushings |
||||||
Impulse Tests (1.2 × 50 Wave) |
Bushing Withstand Voltages |
||||||
Insulation Class and Nominal Bushing Rating |
Chopped Wave |
||||||
Low-Frequency Dielectric Tests |
Minimum Time to Flashover |
Full Wave |
60-Cycle 1 min Dry |
60-Cycle 10 s Wet |
Impulse 1.2 × 50 Wave |
||
kV |
kV |
kV |
μ s |
kV |
kV (rms) |
kV (rms) |
kV (Crest) |
1.2 |
10 |
36 |
1.0 |
10 |
10 |
6 |
30 |
5.0 |
19 |
69 |
1.5 |
60 |
21 |
20 |
60 |
8.66 |
26 |
88 |
1.6 |
75 |
27 |
24 |
75 |
15.0 |
34 |
110 |
1.8 |
95 |
35 |
30 |
95 |
25.0 |
40 |
145 |
1.9 |
125 |
70 |
60 |
150 |
34.5 |
70 |
175 |
3.0 |
150 |
95 |
95 |
200 |
46.0 |
95 |
290 |
3.0 |
250 |
120 |
120 |
250 |
69.0 |
140 |
400 |
3.0 |
350 |
175 |
175 |
350 |
Figure 28.12 is a review of fault current magnitudes for various secondary faults on a Δ-Y transformer bank connection.
When the transformer is overloaded, the high temperature decreases the mechanical strength and increases the brittleness of the fibrous insulation. Even though the insulation strength of the unit may not be seriously decreased, transformer failure rate increases due to this mechanical brittleness.
Three factors will influence accuracy:
Distribution Transformer Overload with Normal Loss of Life
Duration of Peak Load (h) |
Self-Cooled with % Load before Peak of |
||
50 |
70 |
90 |
|
0.5 |
189 |
178 |
164 |
1 |
158 |
149 |
139 |
2 |
137 |
132 |
124 |
4 |
119 |
117 |
113 |
8 |
108 |
107 |
106 |
Burden is measured in VA,
Assume
Voltage at secondary is low and must be compensated by 11% to get the actual primary voltage using the marked ratio.
True ratio = marked ratio × RCF
Burdens are in series,
for example, 10H200 ⇒ 10% error at 200 V
or
If Zb = 4 Ω
200 V/4 Ω = 50 A (10 times normal)
H-class—constant magnitude error (variable %)
L-class—constant % error (variable magnitude)
Example
True ratio = marked ratio × RCF
Assume marked is 600/5 or 120:1 at rated amps and 2 Ω
At 100% A true = 120 × 1.002 × 5 secondary
Primary = 600 × 1.002 = 601.2
At 20% A true = 600 × 0.2 × 1.003 = 120.36 (marked was 120)
Voltage transformers—They are used whenever the line voltage exceeds 480 V or whatever lower voltage may be established by the user as a safe voltage limit. They are usually rated on a basis of 120 V secondary voltage and used to reduce primary voltage to usable levels for transformer-rated meters.
Current transformers—Current transformers are usually rated on a basis of 5 A secondary current and used to reduce primary current to usable levels for transformer-rated meters and to insulate and isolate meters from high-voltage circuits.
Current transformer ratio—Current transformer ratio is the ratio of primary to secondary current. For current transformer rated 200:5, the ratio is 200:5 or 40:1.
Voltage transformer ratio—Voltage transformer ratio is the ratio of primary to secondary voltage. For voltage transformer rated 480:120, the ratio is 4:1, 7200:120, or 60:1.
Transformer ratio (TR)—TR is the total ratio of current and voltage transformers. For 200:5 CT and 480:120 PT, TR = 40 × 4 = 160.
Weatherability—Transformers are rated as indoor or outdoor, depending on construction (including hardware).
Accuracy classification—Accuracy classification is the accuracy of an instrument transformer at specified burdens. The number used to indicate accuracy is the maximum allowable error of the transformer for specified burdens. For example, 0.3 accuracy class means the maximum error will not exceed 0.3% at stated burdens.
Rated burden—Rated burden is the load that may be imposed on the transformer secondaries by associated meter coils, leads, and other connected devices without causing an error greater than the stated accuracy classification.
Current transformer burdens—Current transformer burdens are normally expressed in ohms impedance such as B-0.1, B-0.2, B-0.5, B-0.9, or B-1.8. Corresponding volt–ampere values are 2.5, 5.0, 12.5, 22.5, and 45.
Voltage transformer burdens—Voltage transformer burdens are normally expressed as volt–amperes at a designated power factor (pf). It may be W, X, M, Y, or Z, where W is 12.5 VA at 0.10 pf, X is 25 VA at 0.70 pf, M is 35 VA at 0.20 pf, Y is 75 VA at 0.85 pf, and Z is 200 VA at 0.85 pf. The complete expression for a current transformer accuracy classification might be 0.3 at B-0.1, B-0.2, and B-0.5, while the potential transformer might be 0.3 at W, X, M, and Y.
Continuous thermal rating factor (TRF)—Continuous TRF is normally designated for current transformers and is the factor by which the rated primary current is multiplied to obtain the maximum allowable primary current without exceeding temperature rise standards and accuracy requirements. For example, if a 400:5 CT has a TRF of 4.0, the CT will continuously accept 400 × 4 or 1600 primary amperes with 5 × 4 or 20 A from the secondary. The thermal burden rating of a voltage transformer shall be specified in terms of the maximum burden in volt–amperes that the transformer can carry at rated secondary voltage without exceeding a given temperature rise.
Rated insulation class—Rated insulation class denotes the nominal (line-to-line) voltage of the circuit on which it should be used. Associated Engineering Company has transformers rated for 600 V through 138 kV.
Polarity—The relative polarity of the primary and secondary windings of a current transformer is indicated by polarity marks (usually white circles), associated with one end of each winding. When current enters at the polarity end of the primary winding, a current in phase with it leaves the polarity end of the secondary winding. Representation of primary marks on wiring diagrams is shown as black squares.
Hazardous open circulating—The operation of CTs with the secondary winding open can result in a high voltage across the secondary terminals, which may be dangerous to personnel or equipment. Therefore, the secondary terminals should always be short circuited before a meter is removed from service. This may be done automatically with a bypass in the socket or by a test switch for A-base meters.
Probably no area of distribution engineering causes more confusion than does loading. Reading the standards does not seem to help much since everyone appears to have their own interpretation. Manufacturers of equipment are very conservative since they really never know how the user will actually put the product to use so they must expect the worst. On the other hand, many users seem to take the approach that since it did not fail last year with traditional overloading values, it will not fail this year either. In fact, it will not fail until after retirement. Heck! “Save a buck and get a promotion.” The author of this document is not a psychology major and frankly has no idea of what the thinking was when much of the following was produced. The material that follows, however, was taken from sources with excellent reputation. Use it with caution.
The following is an example of maximum temperature limits via the IEEE for a 65°C rise transformer:
IEEE Normal Life Expectancy |
|
Top-oil temperature |
105°C |
Hotspot temperature |
120°C |
This next example shows the loading practice of various utilities for substation transformers:
Utility A |
Utility B |
Utility C |
Utility D |
Utility E |
Utility F |
Utility G |
|
Normal conditions |
|||||||
Top oil |
95 |
110 |
95 |
95 |
95 |
110 |
110 |
Hotspot |
125 |
130 |
120 |
110 |
120 |
140 |
120 |
Emergency conditions |
|||||||
Top oil |
110 |
110 |
110 |
110 |
110 |
110 |
110 |
Hotspot |
140 |
140 |
140 |
130 |
140 |
140 |
140 |
What happens when the hotspot is raised from 125°C to 130°C? This is shown as follows:
Maximum Hotspot (°C) |
% Loss of Life, Annual |
125 |
0.3366 |
130 |
0.5372 |
An example of the effect of load cycle (3 h peak with 70% preload for 13 h and 45% load for 8 h) and ambient on transformer capability via the ANSI guide is shown as follows:
Peak Load for Normal Life Expectancy |
Emergency Peak Load with 24 h Loss of Life |
|||
Transformer Type |
10°C Ambient |
30°C Ambient |
0.25% |
1.0% |
20,000—OA |
30,000 |
24,200 |
28,400 |
32,000 |
15,000/2,000—OA/FA |
28,700 |
23,800 |
27,500 |
30,700 |
12,000/16,000/ 20,000—OA/FA/FOA |
27,500 |
23,200 |
26,800 |
29,700 |
20,000—FOA |
27,500 |
23,200 |
26,800 |
29,700 |
The following is the effect on transformer ratings for various limits of top-oil temperature:
MVA |
Top-Oil Temperature (°C) |
|
Normal rating |
50 |
95 |
New rating |
55 |
105 |
Emergency rating |
59 |
110 |
The loading of distribution transformers varies more widely than substation units. Some utilities try to never exceed the loading of the transformer nameplate. Others, particularly those using TLM, greatly overload smaller distribution transformers with no apparent increase in failure rates. An example of one utilities practice is as follows:
Padmounted |
Submersible |
|||
kVA |
Install Range |
Removal Point |
Install Range |
Removal Point |
25 |
0–40 |
55 |
0–34 |
42 |
50 |
41–69 |
88 |
35–64 |
79 |
75 |
70–105 |
122 |
65–112 |
112 |
100 |
106–139 |
139 |
113–141 |
141 |
The following table shows the rating of conductors via a typical utility:
Conductor Size |
ACSR |
All Aluminum |
||
Normal |
Emergency |
Normal |
Emergency |
|
1/0 |
319 |
331 |
318 |
334 |
2/0 |
365 |
379 |
369 |
388 |
3/0 |
420 |
435 |
528 |
450 |
4/0 |
479 |
496 |
497 |
523 |
267 |
612 |
641 |
576 |
606 |
336 |
711 |
745 |
671 |
705 |
397 |
791 |
830 |
747 |
786 |
The following are some typical 2 h overload ratings of various substation equipment. Use at your own risk:
Station transformer |
140% |
Current transformer |
125% |
Breakers |
110% |
Reactors |
140% |
Disconnects |
110% |
Regulators |
150% |
The following are some miscellaneous loading information and thoughts from a number of actual utilities:
Load Factor (%) | Transformer Load Limit (%) |
0–64 | 130 |
65–74 | 125 |
75–100 | 120 |