Chapter 26
26.1 Modeling 26-1
Line Impedance • Shunt Admittance • Line Segment Models • Step-Voltage Regulators • Transformer Bank Connections • Load Models • Shunt Capacitor Models
26.2 Analysis 26-49
Power-Flow Analysis
References 26-57
William H. Kersting
New Mexico State University
Radial distribution feeders are characterized by having only one path for power to flow from the source (distribution substation) to each customer. A typical distribution system will consist of one or more distribution substations consisting of one or more “feeders.” Components of the feeder may consist of the following:
The loading of a distribution feeder is inherently unbalanced because of the large number of unequal single-phase loads that must be served. An additional unbalance is introduced by the nonequilateral conductor spacings of the three-phase overhead and underground line segments.
Because of the nature of the distribution system, conventional power-flow and short-circuit programs used for transmission system studies are not adequate. Such programs display poor convergence characteristics for radial systems. The programs also assume a perfectly balanced system so that a single-phase equivalent system is used.
If a distribution engineer is to be able to perform accurate power-flow and short-circuit studies, it is imperative that the distribution feeder be modeled as accurately as possible. This means that three-phase models of the major components must be utilized. Three-phase models for the major components will be developed in the following sections. The models will be developed in the “phase frame” rather than applying the method of symmetrical components.
Figure 26.1 shows a simple one-line diagram of a three-phase feeder; it illustrates the major components of a distribution system. The connecting points of the components will be referred to as “nodes.” Note in the figure that the phasing of the line segments is shown. This is important if the most accurate models are to be developed.
The following sections will present generalized three-phase models for the “series” components of a feeder (line segments, voltage regulators, transformer banks). Additionally, models are presented for the “shunt” components (loads, capacitor banks). Finally, the “ladder iterative technique” for power-flow studies using the models is presented along with a method for computing short-circuit currents for all types of faults.
The determination of the impedances for overhead and underground lines is a critical step before analysis of the distribution feeder can begin. Depending upon the degree of accuracy required, impedances can be calculated using Carson’s equations where no assumptions are made, or the impedances can be determined from tables where a wide variety of assumptions are made. Between these two limits are other techniques, each with their own set of assumptions.
Since a distribution feeder is inherently unbalanced, the most accurate analysis should not make any assumptions regarding the spacing between conductors, conductor sizes, or transposition. In a classic paper, John Carson developed a technique in 1926 whereby the self and mutual impedances for ncond overhead conductors can be determined. The equations can also be applied to underground cables. In 1926, this technique was not met with a lot of enthusiasm because of the tedious calculations that had to be done on the slide rule and by hand. With the advent of the digital computer, Carson’s equations have now become widely used.
In his paper, Carson assumes the earth is an infinite, uniform solid, with a flat uniform upper surface and a constant resistivity. Any “end effects” introduced at the neutral grounding points are not large at power frequencies, and therefore are neglected. The original Carson equations are given in Equations 26.1 and 26.2.
Self-impedance:
ˆzii=ri+4ω PiiG+j(Xi+2ωG. lnSiiRDi+4 ωQiiG) Ω/mile
Mutual impedance:
ˆzij=4ω PijG+j(2ωG . lnSijDij+4ωQijG) Ω/mile
Xi=2ωG⋅lnRDiGMRi Ω/mile
Pij=π8−13√2kijcos(θij)+k2ij16cos(2θij)⋅(0.6728+ln2kij)
Qij=−0.0386+12 ⋅ln2kij+13√2kijcos(θij)
kij=8.565×10−4⋅Sij⋅√fρ
where
ˆzii
ˆzij
ri is the resistance of conductor i in Ω/mile
ω = 2πf is the system angular frequency in radians per second
G is the 0.1609347 × 10–3 Ω/mile
RDi is the radius of conductor i in feet
GMRi is the Geometric mean radius of conductor i in feet
f is the system frequency in Hertz
ρ is the resistivity of earth in Ω-meters
Dij is the distance between conductors i and j in ft. (see Figure 4.4)
Sij is the distance between conductor i and image j in ft. (see Figure 4.4)
θij is the angle between a pair of lines drawn from conductor i to its own image and to the image of conductor j (see Figure 4.4)
As indicated above, Carson made use of conductor images; that is, every conductor at a given distance above ground has an image conductor the same distance below ground. This is illustrated in Figure 26.2.
Only two approximations are made in deriving the “modified Carson equations.” These approximations involve the terms associated with Pij and Qij. The approximations are shown below:
Pij=π8
Qij=−0.03860+12ln2kij
It is also assumed
f is the frequency = 60 Hz
r is the resistivity = 100 Ω m
Using these approximations and assumptions, Carson’s equations reduce to:
ˆzii =ri+0.0953+j0.12134(ln1GMRi+7.93402) Ω/mile
ˆzij =0.0953+j0.12134(ln1Dij+7.93402) Ω/mile
Equations 26.9 and 26.10 can be used to compute an ncond × ncond “primitive impedance” matrix. For an overhead four wire, grounded wye distribution line segment, this will result in a 4 × 4 matrix. For an underground grounded wye line segment consisting of three concentric neutral cables, the resulting matrix will be 6 × 6. The primitive impedance matrix for a three-phase line consisting of m neutrals will be of the form
[zprimitive]=[ˆzaaˆzabˆzacˆzanl⋅ˆzanmˆzbaˆzbbˆzbcˆzbnl⋅ˆzbnmˆzcaˆzcbˆzccˆzcnl⋅ˆzcnmˆznlaˆznlbˆznlcˆznlnl⋅ˆznlnm⋅⋅⋅⋅⋅⋅ˆznmaˆznmbˆznmcˆznmnl⋅ˆznmnm]
In partitioned form Equation 20.11 becomes
[zprimitive]=[[ˆzij][ˆzin][ˆznj][ˆznn]]s
For most applications, the primitive impedance matrix needs to be reduced to a 3 × 3 phase frame matrix consisting of the self and mutual equivalent impedances for the three phases. One standard method of reduction is the “Kron” reduction (1952) where the assumption is made that the line has a multigrounded neutral. The Kron reduction results in the “phase impedances matrix” determined by using Equation 26.13 below:
[zabc]=[ˆzij]−[ˆzin][ˆznn]−1[ˆznj]
It should be noted that the phase impedance matrix will always be of rotation a–b–c no matter how the phases appear on the pole. That means that always row and column 1 in the matrix will represent phase a, row and column 2 will represent phase b, row and column 3 will represent phase c.
For two-phase (V-phase) and single-phase lines in grounded wye systems, the modified Carson equations can be applied, which will lead to initial 3 × 3 and 2 × 2 primitive impedance matrices. Kron reduction will reduce the matrices to 2 × 2 and a single element. These matrices can be expanded to 3 × 3 phase frame matrices by the addition of rows and columns consisting of zero elements for the missing phases. The phase frame matrix for a three-wire delta line is determined by the application of Carson’s equations without the Kron reduction step.
The phase frame matrix can be used to accurately determine the voltage drops on the feeder line segments once the currents flowing have been determined. Since no approximations (transposition, for example) have been made regarding the spacing between conductors, the effect of the mutual coupling between phases is accurately taken into account. The application of Carson’s equations and the phase frame matrix leads to the most accurate model of a line segment. Figure 26.3 shows the equivalent circuit of a line segment.
The voltage equation in matrix form for the line segment is given by the following equation:
[VagVbgVcg]n=[VagVbgVcg]m+[ZaaZabZacZbaZbbZbcZcaZcbZcc] [IaIbIc]
where
Zij=zij×length
The phase impedance matrix is defined in Equation 26.15. The phase impedance matrix for single-phase and V-phase lines will have a row and column of zeros for each missing phase
[Zabc]=[ZaaZabZacZbaZbbZbcZcaZcbZcc]
Equation 26.14 can be written in condensed form as
[VLGabc]n=[VLGabc]m+[Zabc][Iabc]
This condensed notation will be used throughout the document.
Many times the analysis of a feeder will use the positive and zero sequence impedances for the line segments. There are basically two methods for obtaining these impedances. The first method incorporates the application of Carson’s equations and the Kron reduction to obtain the phase frame impedance matrix. The 3 × 3 “sequence impedance matrix” can be obtained by
[z012]=[As]−1[zabc][As] Ω/mile
where
[As]=[1111a2sas1asa2s]
as=1.0∠120 a2s=1.0∠240
The resulting sequence impedance matrix is of the form:
[z012]=[z00z01z02z10z11z12z20z21z22] Ω/mile
where
z00 is the zero sequence impedance
z11 is the positive sequence impedance
z22 is the negative sequence impedance
In the idealized state, the off-diagonal terms of Equation 26.19 would be zero. When the off-diagonal terms of the phase impedance matrix are all equal, the off-diagonal terms of the sequence impedance matrix will be zero. For high-voltage transmission lines, this will generally be the case because these lines are transposed, which causes the mutual coupling between phases (off-diagonal terms) to be equal. Distribution lines are rarely if ever transposed. This causes unequal mutual coupling between phases, which causes the off-diagonal terms of the phase impedance matrix to be unequal. For the nontransposed line, the diagonal terms of the phase impedance matrix will also be unequal. In most cases, the off-diagonal terms of the sequence impedance matrix are very small compared to the diagonal terms and errors made by ignoring the off-diagonal terms are small.
Sometimes the phase impedance matrix is modified such that the three diagonal terms are equal and all of the off-diagonal terms are equal. The usual procedure is to set the three diagonal terms of the phase impedance matrix equal to the average of the diagonal terms of Equation 26.15 and the off-diagonal terms equal to the average of the off-diagonal terms of Equation 26.15. When this is done, the self and mutual impedances are defined as
zs=13(zaa+zbb+zcc)
zm=13(zab+zbc+zca)
The phase impedance matrix is now defined as
[zabc]=[zszmzmzmzszmzmzmzs]
When Equation 26.17 is used with this phase impedance matrix, the resulting sequence matrix is diagonal (off-diagonal terms are zero). The sequence impedances can be determined directly as
z00=zs+2zmz11=zn=zs−zm
A second method that is commonly used to determine the sequence impedances directly is to employ the concept of geometric mean distances (GMDs). The GMD between phases is defined as
Dij=GMDij=3√DabDbcDca
The GMD between phases and neutral is defined as
Din=GMDin=3√DanDbnDcn
The GMDs as defined above are used in Equations 26.9 and 26.10 to determine the various self and mutual impedances of the line resulting in
ˆzii=ri+0.0953+j0.12134[ln(1GMRi)+7.93402]
ˆznn=rn+0.0953+j0.12134[ln(1GMRn)+7.93402] (26.27)
ˆzij =0.0953+j0.12134[ln(1Dij)+7.93402] (26.28)
ˆzin =0.0953+j0.12134[ln(1Din)+7.93402] (26.29)
Equations 26.26 through 26.29 will define a matrix of order ncond × ncond, where ncond is the number of conductors (phases plus neutrals) in the line segment. Application of the Kron reduction (Equation 26.13) and the sequence impedance transformation (Equation 26.23) lead to the following expressions for the zero, positive, and negative sequence impedances:
z00=ˆzii+ 2ˆzij− 3(ˆz2inˆznn) Ω/mile (26.30)
z11=z22=ˆzii−ˆzijz11=z22=ri+j0.12134×ln(DijGMRi) Ω/mile (26.31)
Equation 26.31 is recognized as the standard equation for the calculation of the line impedances when a balanced three-phase system and transposition are assumed.
The spacings for an overhead three-phase distribution line are constructed as shown in Figure 26.4. The phase conductors are 336,400 26/7 ACSR (Linnet) and the neutral conductor is 4/0 6/1 ACSR.
Solution
From the table of standard conductor data, it is found that
33,400 26/7ACSR: GMR=0.0244 ftResistance=0.306 Ω/mile4/0 6/1ACSR: GMR=0.00814 ftResistance=0.5920 Ω/mile
From Figure 26.4 the following distances between conductors can be determined:
Dab=2.5 ft Dbc=4.5 ft Dca=7.0 ftDan=5.6569 ft Dbn=4.272 ft Dcn=5.0 ft
Applying Carson’s modified equations (Equations 26.9 and 26.10) results in the primitive impedance matrix.
[ˆzˆ]=[0.4013+j1.41330.0953+j0.85150.0953+j0.72660.0953+j0.75240.0953+j0.85150.4013+j1.41330.0953+j0.78020.0953+j0.78650.0953+j072660.0953+j0.78020.4013+j1.41330.0953+j0.76740.0953+j0.75240.0953+j0.78650.0953+j0.76740.6873+j1.5465] (26.32)
The Kron reduction of Equation 26.13 results in the phase impedance matrix
[zabc]=[0.4576+j1.07800.1560+j0.50170.1535+j0.38490.1560+j0.50170.4666+j1.04820.1580+j0.42360.1535+j0.38490.1580+j0.42360.4615+j1.0651] Ω/mile (26.33)
The phase impedance matrix of Equation 26.33 can be transformed into the sequence impedance matrix with the application of Equation 26.17
[z012]=[0.7735+j1.93730.0256+j0.0115−0.0321+j0.0159−0.0321+j0.01590.3061+j0.6270−0.0723−j0.00600.0256+j0.01150.0723+j0.00590.3061+j0.6270] Ω/mile (26.34)
In Equation 26.34, the 1,1 term is the zero sequence impedance, the 2,2 term is the positive sequence impedance, and the 3,3 term is the negative sequence impedance. Note that the off-diagonal terms are not zero, which implies that there is mutual coupling between sequences. This is a result of the nonsymmetrical spacing between phases. With the off-diagonal terms nonzero, the three sequence networks representing the line will not be independent. However, it is noted that the off-diagonal terms are small relative to the diagonal terms.
In high-voltage transmission lines, it is usually assumed that the lines are transposed and that the phase currents represent a balanced three-phase set. The transposition can be simulated in this example by replacing the diagonal terms of Equation 26.33 with the average value of the diagonal terms (0.4619 + j1.0638) and replacing each off-diagonal term with the average of the off-diagonal terms (0.1558 + j0.4368). This modified phase impedance matrix becomes
[zlabc]=[0.3619+j1.06380.1558+j0.43680.1558+j0.43680.1558+j0.43680.3619+j1.06380.1558+j0.43680.1558+j0.43680.1558+j0.43680.3619+j1.0638] Ω/mile (26.35)
Using this modified phase impedance matrix in the symmetrical component transformation, Equation 26.17 results in the modified sequence impedance matrix
[zl012]=[0.7735+j1.93730000.3061+j0.62700000.3061+j0.6270] Ω/mile (26.36)
Note now that the off-diagonal terms are all equal to zero, meaning that there is no mutual coupling between sequence networks. It should also be noted that the zero, positive, and negative sequence impedances of Equation 26.36 are exactly equal to the same sequence impedances of Equation 26.34.
The results of this example should not be interpreted to mean that a three-phase distribution line can be assumed to have been transposed. The original phase impedance matrix of Equation 26.33 must be used if the correct effect of the mutual coupling between phases is to be modeled.
Figure 26.5 shows the general configuration of three underground cables (concentric neutral, or tape shielded) with an additional neutral conductor.
Carson’s equations can be applied to underground cables in much the same manner as for overhead lines. The circuit of Figure 26.5 will result in a 7 × 7 primitive impedance matrix. For underground circuits that do not have the additional neutral conductor, the primitive impedance matrix will be 6 × 6.
Two popular types of underground cables in use today are the “concentric neutral cable” and the “tape shield cable.” To apply Carson’s equations, the resistance and GMR of the phase conductor and the equivalent neutral must be known.
Figure 26.6 shows a simple detail of a concentric neutral cable. The cable consists of a central phase conductor covered by a thin layer of nonmetallic semiconducting screen to which is bonded the insulating material. The insulation is then covered by a semiconducting insulation screen. The solid strands of concentric neutral are spiraled around the semiconducting screen with a uniform spacing between strands. Some cables will also have an insulating “jacket” encircling the neutral strands.
In order to apply Carson’s equations to this cable, the following data needs to be extracted from a table of underground cables:
dc is the phase conductor diameter (in.)
dod is the nominal outside diameter of the cable (in.)
ds is the diameter of a concentric neutral strand (in.)
GMRc is the geometric mean radius of the phase conductor (ft)
GMRs is the geometric mean radius of a neutral strand (ft)
rc is the resistance of the phase conductor (Ω/mile)
rs is the resistance of a solid neutral strand (Ω/mile)
k is the number of concentric neutral strands
The geometric mean radii of the phase conductor and a neutral strand are obtained from a standard table of conductor data. The equivalent geometric mean radius of the concentric neutral is given by
GMRcn=k√GMRs×kRk−1 ft (26.37)
where R is the radius of a circle passing through the center of the concentric neutral strands
R=dod−ds24 ft (26.38)
The equivalent resistance of the concentric neutral is
rcn=rsk Ω/mile (26.39)
The various spacings between a concentric neutral and the phase conductors and other concentric neutrals are as follows:
Concentric neutral to its own phase conductor
Dij=R (Equation 21.38 above)
Concentric neutral to an adjacent concentric neutral
Dij=center-to-center distance of the phase conductors
Concentric neutral to an adjacent phase conductor
Figure 26.7 shows the relationship between the distance between centers of concentric neutral cables and the radius of a circle passing through the centers of the neutral strands.
The GMD between a concentric neutral and an adjacent phase conductor is given by the following equation:
Dij=k√Dknm−Rk ft (26.40)
where Dnm is the center-to-center distance between phase conductors.
For cables buried in a trench, the distance between cables will be much greater than the radius R and therefore very little error is made if Dij in Equation 26.40 is set equal to Dnm. For cables in conduit, that assumption is not valid.
Three concentric neutral cables are buried in a trench with spacings as shown in Figure 26.8. The cables are 15 kV, 250,000 CM stranded all aluminum with 13 strands of #14 annealed coated copper wires (1/3 neutral). The data for the phase conductor and neutral strands from a conductor data table are
250,000 AA phase conductor: GMRp = 0.0171 ft, resistance = 0.4100 Ω/mile
#14 copper neutral strands GMRs = 0.00208 ft, resistance = 14.87 Ω/mile
Diameter (ds) = 0.0641 in.
The equivalent GMR of the concentric neutral (Equation 26.37) = 0.04864 ft
The radius of the circle passing through strands (Equation 26.38) = 0.0511 ft
The equivalent resistance of the concentric neutral (Equation 26.39) = 1.1440 Ω/mile
Since R (0.0511 ft) is much less than D12 (0.5 ft) and D13 (1.0 ft), then the distances between concentric neutrals and adjacent phase conductors are the center-to-center distances of the cables.
Applying Carson’s equations results in a 6 × 6 primitive impedance matrix. This matrix in partitioned form (Equation 26.12) is:
[zij]=[0.5053+j1.45640.0953+j1.04680.0953+j0.96270.0953+j1.04680.5053+j1.45640.0953+j1.04680.0953+j0.96270.0953+j1.04680.5053+j1.4564][zin]=[0.0953+j1.32360.0953+j1.04680.0953+j0.96270.0953+j1.04680.0953+j1.32360.0953+j1.04680.0953+j0.96270.0953+j1.04680.0953+j1.3236][znj]=[zin][znn]=[1.2393+j1.32960.0953+j1.04680.0953+j0.96270.0953+j1.04681.2393+j1.32960.0953+j1.04680.0953+j0.96270.0953+j1.04681.2393+j1.3296]
Using the Kron reduction (Equation 26.13) results in the phase impedance matrix
[zabc]=[0.7982+j0.44630.3192+j0.03280.2849−j0.01430.3192+j0.03280.7891+j0.40410.3192+j0.03280.2849−j0.01430.3192+j0.03280.7982+j0.4463] Ω/mile
The sequence impedance matrix for the concentric neutral three-phase line is determined using Equation 26.3. The resulting sequence impedance matrix is
[z012]=[1.4106+j0.4665−0.0028−j0.0081−0.0056+j0.0065−0.0056+j0.00650.4874+j0.4151−0.0264+j0.0451−0.0028−j0.00810.0523+j0.00030.4867+j0.4151] Ω/mile
Figure 26.9 shows a simple detail of a tape shielded cable.
Parameters of Figure 26.9 are
dc is the diameter of phase conductor (in.)
ds is the inside diameter of tape shield (in.)
dod is the outside diameter over jacket (in.)
T is the thickness of copper tape shield in mils
= 5 mils (standard)
Once again, Carson’s equations will be applied to calculate the self-impedances of the phase conductor and the tape shield as well as the mutual impedance between the phase conductor and the tape shield.
The resistance and GMR of the phase conductor are found in a standard table of conductor data.
The resistance of the tape shield is given by
rshield=18.826dsT Ω/mile (26.41)
The resistance of the tape shield given in Equation 26.41 assumes a resistivity of 100 Ω m and a temperature of 50°C. The diameter of the tape shield ds is given in inches and the thickness of the tape shield T is in mils.
The GMR of the tape shield is given by
GMRshield=(ds/2)−(T/2000)12 ft (26.42)
The various spacings between a tape shield and the conductors and other tape shields are as follows:
Tape shield to its own phase conductor
Dij=GMRtape=radius to midpoint of the shield (26.43)
Tape shield to an adjacent tape shield
Dij=center-to-center distance of the phase conductors (26.44)
Tape shield to an adjacent phase or neutral conductor
Dij=Dnm (26.45)
where Dnm is the center-to-center distance between phase conductors.
In applying Carson’s equations for both concentric neutral and tape shielded cables, the numbering of conductors and neutrals is important. For example, a three-phase underground circuit with an additional neutral conductor must be numbered as
1 is the phase conductor #1
2 is the phase conductor #2
3 is the phase conductor #3
4 is the neutral of conductor #1
5 is the neutral of conductor #2
6 is the neutral of conductor #3
7 is the additional neutral conductor (if present).
A single-phase circuit consists of a 1/0 AA tape shielded cable and a 1/0 CU neutral conductor as shown in Figure 26.10.
Cable Data: 1/0 AA
Inside diameter of tape shield = ds = 1.084 in.
Resistance = 0.97 Ω/mile
GMRp = 0.0111 ft
Tape shield thickness = T = 8 mils
Neutral Data: 1/0 Copper, 7 strand
Resistance = 0.607 Ω/mile
GMRn = 0.01113 ft
Distance between cable and neutral = Dnm = 3 in.
The resistance of the tape shield is computed according to Equation 26.41:
rshield=18.826dsT=18.8261.084×8=2.1705 Ω/mile
The GMR of the tape shield is computed according to Equation 26.42:
GMRshield=(ds/2)−(T/2000)12=(1.084/2)−(8/2000)12=0.0455 ft
Using the relations defined in Equations 26.43 through 26.45 and Carson’s equations results in a 3 × 3 primitive impedance matrix:
zprimitive=[1.0653+j1.50880.0953+j1.33770.0953+j1.13090.0953+j1.33772.2658+j1.33770.0953+j1.13090.0953+j1.13090.0953+j1.13090.7023+j1.5085] Ω/mile
Applying Kron’s reduction method will result in a single impedance that represents the equivalent single-phase impedance of the tape shield cable and the neutral conductor.
zlp=1.3368+j0.6028 Ω/mile
When a high-voltage transmission line is less than 50 miles in length, the shunt capacitance of the line is typically ignored. For lightly loaded distribution lines, particularly underground lines, the shunt capacitance should be modeled.
The basic equation for the relationship between the charge on a conductor to the voltage drop between the conductor and ground is given by
Qn=CngVng (26.46)
where
Qn is the charge on the conductor
Cng is the capacitance between the conductor and ground
Vng is the voltage between the conductor and ground
For a line consisting of ncond (number of phase plus number of neutral) conductors, Equation 26.46 can be written in condensed matrix form as
[Q]=[C][V] (26.47)
where
[Q] is the column vector of order ncond
[C] is the ncond × ncond matrix
[V] is the column vector of order ncond
Equation 26.47 can be solved for the voltages
[V]=[C]−1[Q]=[P][Q] (26.48)
where
[P]=[C]−1 (26.49)
The determination of the shunt admittance of overhead lines starts with the calculation of the “potential coefficient matrix” (Glover and Sarma, 1994). The elements of the matrix are determined by
Pii=11.17689×lnSiiRDi (26.50)
Pij=11.17689×lnSijDij (26.51)
See Figure 26.2 for the following definitions.
Sii is the distance between a conductor and its image below ground (ft)
Sij is the distance between conductor i and the image of conductor j below ground (ft)
Dij is the overhead spacing between two conductors (ft)
RDi is the radius of conductor i (ft)
The potential coefficient matrix will be an ncond × ncond matrix. If one or more of the conductors is a grounded neutral, then the matrix must be reduced using the Kron method to an nphase × nphase matrix [Pabc].
The inverse of the potential coefficient matrix will give the nphase × nphase capacitance matrix [Cabc]. The shunt admittance matrix is given by
[yabc]=jω [Cabc] μS/mile (26.52)
where ω = 2πf = 376.9911.
Determine the shunt admittance matrix for the overhead line of Example 26.1. Assume that the neutral conductor is 25 ft above ground.
Solution
For this configuration, the image spacing matrix is computed to be
[S]=[5858.053958.420954.147958.05395858.174354.020858.420958.17435854.083354.147954.020854.083550] ft
The primitive potential coefficient matrix is computed to be
[Pprimitive]=[84.5635.152223.714725.246935.452284.5628.605828.35923.714728.605884.5626.613125.246928.35926.613185.6659]
Kron reduce to a 3 × 3 matrix
[P]=[77.119426.794415.871426.794475.17219.795715.871419.795776.2923]
Invert [P] to determine the shunt capacitance matrix
[Yabc]=j376.9911[Cabc]=[j5.6711−j1.8362−j0.7033−j1.8362j5.9774−j1.169−j0.7033−j1.169j5.391] μS/mile
Multiply [Cabc] by the radian frequency to determine the final three-phase shunt admittance matrix.
Because the electric fields of underground cables are confined to the space between the phase conductor and its concentric neutral to tape shield, the calculation of the shunt admittance matrix requires only the determination of the “self” admittance terms.
The self-admittance in μS/mile for a concentric neutral cable is given by
Ycn=j77.582ln(Rb/Ra)−(1/k)ln(kRn/Rb) (26.53)
where
Rb is the radius of a circle to center of concentric neutral strands (ft)
Ra is the radius of phase conductor (ft)
Rn is the radius of concentric neutral strand (ft)
k is the number of concentric neutral strands
Determine the three-phase shunt admittance matrix for the concentric neutral line of Example 26.2.
Solution
Rb=R=0.0511 ft
Diameter of the 250,000 AA phase conductor = 0.567 in.
Rb=0.56724=0.0236 ft
Diameter of the #14 CU concentric neutral strand = 0.0641 in.
Rn=0.064124=0.0027 ft
Substitute into Equation 26.53:
Ycn=j77.582ln(Rb/Ra)−(1/k)ln(kRn/Rb)=j77.582ln(0.0511/0.0236)−113ln((13×0.0027)/0.0511)=j96.8847
The three-phase shunt admittance matrix is:
[Yabc]=[j96.8847000j96.8847000j96.8847] μS/mile
The shunt admittance in μS/mile for tape shielded cables is given by
Yts=j77.586ln(Rb/Ra) μS/mile (26.54)
where
Rb is the inside radius of the tape shield
Ra is the radius of phase conductor
Determine the shunt admittance of the single-phase tape shielded cable of Example 26.3 in Section 26.1.1.
Solution
Rb=ds24=1.08424=0.0452
The diameter of the 1/0 AA phase conductor = 0.368 in.
Ra=dp24=0.36824=0.0153
Substitute into Equation 26.54:
Yts=j77.586ln(Rb/Ra)=j77.586ln(0.0452/0.0153)=j71.8169 μS/mile
The exact model of a three-phase line segment is shown in Figure 26.11. For the line segment in Figure 26.11, the equations relating the input (node n) voltages and currents to the output (node m) voltages and currents are
[VLGabc]n=[a][VLGabc]m+[b][Iabc]m (26.55)
[Iabc]n=[c][VLGabc]m+[d][Iabc]m (26.56)
where
[a]=[U]−12[Zabc][Yabc] (26.57)
[b]=[Zabc] (26.58)
[c]=[Yabc]−14[Zabc][Yabc]2 (26.59)
[d]=[U]−12[Zabc][Yabc] (26.60)
In Equations 26.57 through 26.60, the impedance matrix [Zabc] and the admittance matrix [Yabc] are defined earlier in this document.
Sometimes it is necessary to determine the voltages at node m as a function of the voltages at node n and the output currents at node m. The necessary equation is
[VLGabc]m=[A][VLGabc]n−[B][Iabc]m (26.61)
where
[A]=([U]+12[Zabc][Yabc])−1 (26.62)
[B]=([U]+12[Zabc][Yabc])−1[Zabc] (26.63)
[U]=[100010001] (26.64)
In many cases the shunt admittance is so small that it can be neglected. However, for all underground cables and for overhead lines longer than 15 miles, it is recommended that the shunt admittance be included. When the shunt admittance is neglected, the [a], [b], [c], [d], [A], and [B] matrices become
[a]=[U] (26.65)
[b]=[Zabc] (26.66)
[c]=[0] (26.67)
[d]=[U] (26.68)
[A]=[U] (26.69)
[B]=[Zabc] (26.70)
When the shunt admittance is neglected, Equations 26.55, 26.56, and 26.61 become
[VLGabc]n=[VLGabc]m+[Zabc][Iabc]m (26.71)
[Iabc]n=[Iabc]m (26.72)
[VLGabc]m=[VLGabc]n−[Zabc][Iabc]m (26.73)
If an accurate determination of the voltage drops down a line segment is to be made, it is essential that the phase impedance matrix [Zabc] be computed based upon the actual configuration and phasing of the overhead or underground lines. No assumptions should be made, such as transposition. The reason for this is best demonstrated by an example.
The phase impedance matrix for the line configuration in Example 26.1 was computed to be
[zabc]=[0.4576+j1.07800.1560+j0.50170.1535+j0.38490.1560+j0.50170.4666+j1.04820.1580+j0.42360.1535+j0.38490.1580+j0.42360.4615+j1.0651] Ω/mile
Assume that a 12.47 kV substation serves a load 1.5 miles from the substation. The metered output at the substation is balanced 10,000 kVA at 12.47 kV and 0.9 lagging power factor. Compute the three-phase line-to-ground voltages at the load end of the line and the voltage unbalance at the load.
Solution
The line-to-ground voltages and line currents at the substation are
[VLGabc]=[7200∠07200∠−1207200∠120] [Iabc]n=[463∠−25.84463∠−145.84463∠94.16]
Solve Equation 26.71 for the load voltages:
[VLGabc]m=[VLGabc]n−1.5 [Zabc][Iabc]n=[6761.10∠2.326877.7∠−122.436836.33∠117.21]
The voltage unbalance at the load using the NEMA definition is
Vunbalance=max (Vdeviation)Vavg100=0.937%
The point of Example 26.7 is to demonstrate that even though the system is perfectly balanced at the substation, the unequal mutual coupling between the phases results in a significant voltage unbalance at the load; significant because NEMA requires that induction motors be derated when the voltage unbalance is 1% or greater.
Many times the only data available for a line segment will be the positive and zero sequence impedances. An approximate three-phase line segment model can be developed by applying the “reverse impedance transformation” from symmetrical component theory.
Using the known positive and zero sequence impedances, the “sequence impedance matrix” is given by
[Zseq]=[Z0000Z+000Z+] (26.74)
The reverse impedance transformation results in the following “approximate phase impedance matrix:”
[Zapprox]=[As][Zseq][As]−1=13[(2Z+−Z0)(Z0−Z+)(Z0−Z+)(Z0−Z+)(2Z+−Z0)(Z0−Z+)(Z0−Z+)(Z0−Z+)(2Z+−Z0)] (26.75)
Notice that the approximate phase impedance matrix is characterized by the three diagonal terms being equal and all mutual terms being equal. This is the same result that is achieved if the line is assumed to be transposed. Substituting the approximate phase impedance matrix into Equation 26.71 results in
[VanVbnVcn]n=[VanVbnVcn]m+13[(2Z+−Z0)(Z0−Z+)(Z0−Z+)(Z0−Z+)(2Z+−Z0)(Z0−Z+)(Z0−Z+)(Z0−Z+)(2Z+−Z0)] [IaIbIc]n (26.76)
Equation 26.76 can be expanded and an equivalent circuit for the approximate line segment model can be developed. This approximate model is shown in Figure 26.12.
The errors made by using this approximate line segment model are demonstrated in the following example.
For the line of Example 26.7, the positive and zero sequence impedances were determined to be
Z+=0.3061+j0.6270 Ω/mileZ0=0.7735+j1.9373 Ω/mile
Solution
The sequence impedance matrix is
[zseq]=[0.7735+j1.93730000.3061+j0.62700000.3061+j0.6270]
Performing the reverse impedance transformation results in the approximate phase impedance matrix.
[zapprox]=[As][zseq][As]−1=[0.4619+j1.06380.1558+j0.43680.1558+j0.43680.1558+j0.43680.4619+j1.06380.1558+j0.43680.1558+j0.43680.1558+j0.43680.4619+j1.0638]
Note in the approximate phase impedance matrix that the three diagonal terms are equal and all of the mutual terms are equal.
Use the approximate impedance matrix to compute the load voltage and voltage unbalance as specified in Example 26.1.
Note that the voltages are computed to be balanced. In the previous example it was shown that when the line is modeled accurately, there is a voltage unbalance of almost 1%.
A step-voltage regulator consists of an autotransformer and a LTC mechanism. The voltage change is obtained by changing the taps of the series winding of the autotransformer. The position of the tap is determined by a control circuit (line drop compensator). Standard step regulators contain a reversing switch enabling a ±10% regulator range, usually in 32 steps. This amounts to a 5/8% change per step or 0.75 V change per step on a 120 V base.
A type B step-voltage regulator is shown in Figure 26.13. There is also a type A step-voltage regulator where the load and source sides of the regulator are reversed from that shown in Figure 26.13. Since the type B regulator is more common, the remainder of this section will address the type B step-voltage regulator.
The tap changing is controlled by a control circuit shown in the block diagram of Figure 26.14. The control circuit requires the following settings:
The rating of a regulator is based on the kVA transformed, not the kVA rating of the line. In general this will be 10% of the line rating since rated current flows through the series winding that represents the ±10% voltage change.
Figure 26.15 shows a detailed and abbreviated drawing of a type B regulator in the raise position. The defining voltage and current equations for the type B regulator in the raise position are as follows:
Voltage equations Current equations
V1N1=V2N2 N1II=N2I2 (26.77)
VS=V1−V2 IL=IS−I1 (26.78)
VL=V1 I2=−IS (26.79)
V2=N2N1V1=N2N1VL I1=N2N1I2=N2N1IS (26.80)
VS=(1−N2N1)Vl IL=(1−N2N1)IS (26.81)
VS=aRVL IL=aRIS (26.82)
aR=1−N2N1 (26.83)
Equations 26.82 and 26.83 are the necessary defining equations for modeling a regulator in the raise position.
Figure 26.16 shows the detailed and abbreviated drawings of a regulator in the lower position. Note in the figure that the only difference between the lower and the raise models is that the polarity of the series winding and how it is connected to the shunt winding is reversed.
The defining voltage and current equations for a regulator in the lower position are as follows:
Voltage equations Current equations
V1N1=V2N2 N1II=N2I2 (26.84)
VS=V1+V2 IL=IS−I1 (26.85)
VL=V1 I2=−IS (26.86)
V2=N2N1V1=N2N1VL I1=N2N1I2=N2N1(−IS) (26.87)
VS=(1+N2N1)V1 IL=(1−N2N1)IS (26.88)
VS=aRVL IL=aRIS (26.89)
aR=1+N2N1 (26.90)
Equations 26.83 and 26.90 give the value of the effective regulator ratio as a function of the ratio of the number of turns on the series winding (N2) to the number of turns on the shunt winding (N1). The actual turns ratio of the windings is not known. However, the particular position will be known. Equations 26.83 and 26.90 can be modified to give the effective regulator ratio as a function of the tap position. Each tap changes the voltage by 5/8% or 0.00625 per unit. On a 120 V base, each step change results in a change of voltage of 0.75 V. The effective regulator ratio can be given by
aR=1∓0.00625 ⋅ Tap (26.91)
In Equation 26.91, the minus sign applies to the “raise” position and the positive sign for the “lower” position.
The changing of taps on a regulator is controlled by the “line drop compensator.” Figure 26.17 shows a simplified sketch of the compensator circuit and how it is connected to the circuit through a potential transformer and a current transformer.
The purpose of the line drop compensator is to model the voltage drop of the distribution line from the regulator to the load center. Typically, the compensator circuit is modeled on a 120 V base. This requires the potential transformer to transform rated voltage (line-to-neutral or line-to-line) down to 120 V. The current transformer turns ratio (CTp : CTs) where the primary rating (CTp) will typically be the rated current of the feeder. The setting that is most critical is that of R′ and X′. These values must represent the equivalent impedance from the regulator to the load center. Knowing the equivalent impedance in Ohms from the regulator to the load center (Rline_ohms and Xline_ohms), the required value for the compensator settings are calibrated in volts and determined by
R′volts+jX′volts=(Rline_ohms+jXline_ohms)⋅CtpNpt V (26.92)
The value of the compensator settings in ohms is determined by
R′ohms+jX′ohms=R′volts+jX′voltsCts Ω (26.93)
It is important to understand that the value of Rline_ohms + jXline_ohms is not the impedance of the line between the regulator and the load center. Typically the load center is located down the primary main feeder after several laterals have been tapped. As a result, the current measured by the CT of the regulator is not the current that flows all the way from the regulator to the load center. The proper way to determine the line impedance values is to run a power-flow program of the feeder without the regulator operating. From the output of the program, the voltages at the regulator output and the load center are known. Now the “equivalent” line impedance can be computed as
Rline+jXline=Vregulator_output−Vload_centerIline Ω (26.94)
In Equation 26.94, the voltages must be specified in system volts and the current in system amps.
Three single-phase regulators connected in wye are shown in Figure 26.18. In Figure 26.18 the polarities of the windings are shown in the raise position. When the regulator is in the lower position, a reversing switch will have reconnected the series winding so that the polarity on the series winding is now at the output terminal.
Regardless of whether the regulator is raising or lowering the voltage, the following equations apply.
[VAnVBnVCn]=[aR_a000aR_b000aR_c] [VanVbnVcn] (26.95)
Equation 26.95 can be written in condensed form as
[VLNABC]=[aRVabc][VLNabc] (26.96)
also
[VLNabc]=[aRVABC][VLNABC] (26.97)
where
[aRVABC]=[aRVabc]−1 (26.98)
[IAIBIC]=[1aR_a0001aR_b0001aR_c] [IaIbIc] (26.99)
or
[IABC]=[aRIabc] [Iabc] (26.100)
also
[Iabc]=[aRIABC] [IABC] (26.101)
where
[aRIABC]=[aRIabc]−1 (26.102)
where 0.9 ≤ aR_abc ≤ 1.1 in 32 steps of 0.625% per step (0.75 V/step on 120 V base).
Note: The effective turn ratios (aR_a, aR_b, and aR_c ) can take on different values when three single-phase regulators are connected in wye. It is also possible to have a three-phase regulator connected in wye where the voltage and current are sampled on only one phase and then all three phases are changed by the same value of aR (number of taps).
Three single-phase regulators can be connected in a closed delta as shown in Figure 26.19. In the figure, the regulators are shown in the raise position. The closed delta connection is typically used in three-wire delta feeders. Note that the potential transformers for this connection are monitoring the load side line-to-line voltages and the current transformers are monitoring the load side line currents.
Applying the basic voltage and current Equations 26.77 through 26.83 of the regulator in the raise position, the following voltage and current relations are derived for the closed delta connection.
[VABVBCVCA]=[aR_ab1−aR_bc00aR_bc1−aR_ca1−aR_ab0aR_ca] [VabVbcVca] (26.103)
Equation 26.101 in abbreviated form can be written as
[VLLABC]=[aRVDabc][VLLabc] (26.104)
When the load side voltages are known, the source side voltages can be determined by
[VLLabc]=[aRVDABC][VLLABC] (26.105)
where
[aRVDABC]=[aRVDabc]−1 (26.106)
In a similar manner, the relationships between the load side and source side line currents are given by
[IaIbIc]=[aR_ab01−aR_ca1−aR_abaR_bc001−aR_bcaR_ca] [IAIBIC] (26.107)
or
[Iabc]=[AIDABC][IABC] (26.108)
also
[IABC]=[AIDabc][Iabc] (26.109)
where
[IADabc]=[IADABC]−1 (26.110)
The closed delta connection can be difficult to apply. Note in both the voltage and current equations that a change of the tap position in one regulator will affect voltages and currents in two phases. As a result, increasing the tap in one regulator will affect the tap position of the second regulator. In most cases the bandwidth setting for the closed delta connection will have to be wider than that for wye connected regulators.
Two single-phase regulators can be connected in the “open” delta connection. Shown in Figure 26.20 is an open delta connection where two single-phase regulators have been connected between phases AB and CB.
Two other open connections can also be made where the single-phase regulators are connected between phases BC and AC and also between phases CA and BA.
The open delta connection is typically applied to three-wire delta feeders. Note that the potential transformers monitor the line-to-line voltages and the current transformers monitor the line currents. Once again, the basic voltage and current relations of the individual regulators are used to determine the relationships between the source side and load side voltages and currents.
For all three open connections, the following general equations will apply:
[VLLABC]=[aRVabc][VLLabc] (26.111)
[VLLabc]=[aRVABC][VLLABC] (26.112)
[IABC]=[aRIabc] [Iabc] (26.113)
[Iabc]=[aRIABC] [IABC] (26.114)
The matrices for the three open connections are defined as follows:
Phases AB and CB
[aRVabc]=[aR_A000aR_C0−aR_A−aR_C0] (26.115)
[aRVABC]=[1aR_A0001aR_C0−1aR_A−1aR_C0] (26.116)
[aRIabc]=[1aR_A00−1aR_A0−1aR_C001aR_C] (26.117)
[aRIABC]=[aR_A00−aR_A0aR_C00aR_C] (26.118)
Phases BC and AC
[aRVabc]=[0−aR_B−aR_A0aR_B000aR_A] (26.119)
[aRVABC]=[0−1aR_B−1aR_A01aR_B0001aR_A] (26.120)
[aRIabc]=[1aR_A0001aR_B0−1aR_A−1aR_B0] (26.121)
[aRIABC]=[aR_A000aR_B0−aR_A−aR_B0] (26.122)
Phases CA and BA
[aRVabc]=[aR_B00−aR_B0−aR_C00aR_C] (26.123)
[aRVABC]=[1aR_B00−1aR_B0−1aR_C001aR_C] (26.124)
[aRIabc]=[0−1aR_B−1aR_C01aR_B0001aR_C] (26.125)
[aRIABC]=[0−aR_B−aR_C0aR_B000aR_C] (26.126)
The voltage regulator models used in power-flow studies are generalized for the various connections in a form similar to the ABCD parameters that are used in transmission line analysis. The general form of the power-flow models in matrix form is
[VABC]=[a][Vabc]+[b][Iabc] (26.127)
[IABC]=[c][Vabc]+[d][Iabc] (26.128)
[Vabc]=[A][VABC]+[B][Iabc] (26.129)
Depending upon the connection, the matrices [VABC] and [Vabc] can be either line-to-line or line-to-ground. The current matrices represent the line currents regardless of the regulator connection. For all voltage regulator connections, the generalized constants are defined as
[a]=[aRVabc] (26.130)
[b]=[0] (26.131)
[c]=[0] (26.132)
[d]=[aRIabc] (26.133)
[A]=[aRVABC] (26.134)
[B]=[0] (26.135)
Unique models of three-phase transformer banks applicable to radial distribution feeders have been developed (Kersting, 1999). Models for the following three-phase connections are included in this document:
Figure 26.21 defines the various voltages and currents for the transformer bank models. The models can represent a step-down (source side to load side) or a step-up (source side to load side) transformer bank. The notation is such that the capital letters A, B, C, N will always refer to the source side of the bank and the lower case letters a, b, c, n will always refer to the load side of the bank. It is assumed that all variations of the wye–delta connections are connected in the “American Standard Thirty Degree” connection. The standard is such that:
Step-down connection
VAB leads Vab by 30°
IA leads Ia by 30°
Step-up connection
Vab leads VAB by 30°
Ia leads IA by 30°
The models to be used in power-flow studies are generalized for the connections in a form similar to the ABCD parameters that are used in transmission line analysis. The general form of the power-flow models in matrix form are
[VLNABC]=[at][VLNabc]+[bt][Iabc] (26.136)
[IABC]=[ct][Vabc]+[dt][Iabc] (26.137)
[VLNabc]=[At][VLNABC]−[Bt][Iabc] (26.138)
In Equations 26.136 through 26.138, the matrices [VLNABC] and [VLNabc] will be the equivalent line-to-neutral voltages on delta and ungrounded wye connections and the line-to-ground voltages for grounded wye connections.
When the “ladder technique” or “sweep” iterative method is used, the “forward” sweep is assumed to be from the source working toward the remote nodes. The “backward” sweep will be working from the remote nodes toward the source node.
All transformer models will use the following common variable and matrices:
nt=Vrated_sourceVrated_load (26.139)
where
Vrated_source is the transformer winding rating on the source side. Line-to-line voltage for delta connections and line-to-neutral for wye connections
Vrated_load is the transformer winding rating on the load side. Line-to-line voltage for delta connections and line-to-neutral for wye connections
Note that the transformer “winding” ratings may be either line-to-line or line-to-neutral, depending upon the connection. The winding ratings can be specified in actual volts or per-unit volts using the appropriate base line-to-neutral voltages.
[VABC]=[AV][Vabc] (26.140)
The voltage matrices may be line-to-line or line-to-neutral voltages depending upon the connection.
[Iabc]=[AI][IABC] (26.141)
The current matrices may be line currents or delta currents depending upon the connection.
[Ztabc]=[Zta000Ztb000Ztc] (26.142)
The impedance elements in the matrix will be the per-unit impedance of the transformer windings on the load side of the transformer whether it is connected in wye or delta.
[As]=[1111a2sas1asa2s] (26.143)
where as = 1 ∠120
[Ts]=[1000t*000ts] (26.144)
where ts=(1/√3)∠30
[W]=[As][Ts][As]−1=13[210021102] (26.145)
Example: [VLN] = [W][VLL]
[DI]=[10−1−1100−11] (26.146)
Example: [Iabc] = [DI][IDabc]
[D]=[1−1001−1−101] (26.147)
Example: [VLLabc] = [D][VLNabc]
All transformer models were developed so that they can be applied using either “actual” or “per-unit” values of voltages, currents, and impedances. When the per-unit system is used, all per-unit voltages (line-to-line and line-to-neutral) use the line-to-neutral base as the base voltage. In other words, for a balanced set of three-phase voltages, the per-unit line-to-neutral voltage magnitude will be 1.0 at rated voltage and the per-unit line-to-line voltage magnitude will be the √3 . In a similar fashion, all currents (line currents and delta currents) are based on the base line current. Again, √3 relationship will exist between the line and delta currents under balanced conditions. The base line impedance will be used for all line impedances and for wye and delta connected transformer impedances. There will be different base values on the two sides of the transformer bank.
Base values are computed following the steps listed below:
ax=kVLLsourcekVLLload (26.148)
kVLNS=kVLLS√3 (26.149)
IS=kVAbase√3kVLLsource (26.150)
ZS=kVLL2source1000kVAB (26.151)
kVLNL=kVLNSax (26.152)
IL=axIS (26.153)
ZL=ZSa2x (26.154)
The matrices [at], [bt], [ct], [dt], [At], and [Bt] (see Equations 26.136 through 26.138) for each connection are defined as follows:
Backward sweep:
[VLNABC]=[at][VLGabc]+[bt][Iabc][IABC]=[ct][VLGabc]+[dt][Iabc]
Forward sweep:
[VLGabc]=[At][VLNABC]−[Bt][Iabc]
The matrices used for the step-down connection are
[at]=−nt3[021102210][bt]=−nt3[02ZtbZtcZta02Ztc2ZtaZtb0][ct]=[000000000][dt]=1nt[1−1001−1−101]
[At]=1nt[10−1−1100−11][Bt]=[Zta000Ztb000Ztc]
Power-flow equations:
Backward sweep:
[VLNABC]=[at][VLNabc]+[bt][Iabc][IABC]=[ct][VLNabc]+[dt][Iabc]
Forward sweep:
[VLNabc]=[At][VLNABC]−[Bt][Iabc]
Matrices used for the step-down connection are
[at]=nt[1−1001−1−101][bt]=nt3[Ztab−Ztab0Ztbc2Ztbc0−2Ztca−Ztca0][ct]=[000000000][dt]=13nt[1−10120−2−10]
[At]=13nt[210021102][Bt]=19[2Ztab+Ztbc2Ztbc−2Ztab02Ztbc−2Ztca4Ztbc−Ztca0Ztab−4Ztca−Ztab+2Ztca0]
where Ztab, Ztbc, and Ztca are the transformer impedances inside the delta secondary connection.
Power-flow equations:
Backward sweep:
[VLGABC]=[at][VLNabc]+[bt][Iabc][IABC]=[ct][VLNabc]+[dt][Iabc]
Forward sweep:
[VLGabc]=[At][VLNABC]−[Bt][Iabc]
The matrices used for the step-down connection are
[at]=nt[1−1001−1−101][bt]=ntZtab+Ztbc+Ztca[ZtabZtca−ZtabZtbc0ZtbcZtcaZtbc(Ztca+Ztab)0Ztca(−Ztab−Ztbc)−ZtbcZtca0][ct]=[000000000][dt]=1nt(Ztab+Ztbc+Ztca)[Ztca−Ztbc0ZtcaZtab+Ztca0−Ztab−Ztbc−Ztca0][At]=13nt[210021102][Bt]=13∑Zt[2ZtabZtca+ZtbcZtca−2ZtabZtbc+Ztbc(Ztab+Ztca)02ZtbcZtca−Ztbc(Ztab+Ztbc)2Ztbc(Ztab+Ztca)−ZtbcZtca0ZtabZtca−2Ztca(Ztab+Ztbc)−ZtabZtbc−2ZtbcZtca0]
where
∑Zt=Ztab+Ztbc+Ztca
Power-flow equations:
Backward sweep:
[VLGABC]=[at][VLGabc]+[bt][Iabc][IABC]=[ct][VLGabc]+[dt][Iabc]
Forward sweep:
[VLGabc]=[At][VLGABC]−[Bt][Iabc]
The matrices used are
[at]=nt[100010001][bt]=nt[Zta000Ztb000Ztc][ct]=[000000000][dt]=1nt[100010001][At]=1nt[100010001][Bt]=[Zta000Ztb000Ztc]
Power-flow equations:
Backward sweep:
[VLNABC]=[at][VLNabc]+[bt][Iabc][IABC]=[ct][VLNabc]+[dt][Iabc]
Forward sweep:
[VLNabc]=[At][VLNABC]−[Bt][Iabc]
The matrices used are
[at]=nt3[2−1−1−12−1−1−12][bt]=nt3∑Zt[2ZtabZtca+ZtbcZtca−2ZtabZtbc+Ztbc(Ztab+Ztca)02ZtbcZtca−Ztbc(Ztab+Ztbc)2Ztbc(Ztab+Ztca)−ZtbcZtca0ZtabZtca−2Ztca(Ztab+Ztbc)−ZtabZtbc−2ZtbcZtca0]
where
∑Zt=Ztab+Ztbc+Ztca[ct]=[000000000][dt]=1nt[100010001][At]=13nt[2−1−1−12−1−1−12][Bt]=13∑Zt[2ZtabZtca+ZtbcZtca−2ZtabZtbc+Ztbc(Ztab+Ztca)02ZtbcZtca−Ztbc(Ztab+Ztbc)2Ztbc(Ztab+Ztca)−ZtbcZtca0ZtabZtca−2Ztca(Ztab+Ztbc)−ZtabZtbc−2ZtbcZtca0]
where
∑Zt=Ztab+Ztbc+Ztca
The study of short-circuit studies that occur on the load side of a transformer bank requires the three-phase Thevenin equivalent circuit referenced to the load side terminals of the transformer. In order to determine this equivalent circuit, the Thevenin equivalent circuit up to the primary terminals of the “feeder” transformer must be determined. It is assumed that the transformer matrices as defined above are known for the transformer connection in question. A one-line diagram of the total system is shown in Figure 26.22.
The desired Thevenin equivalent circuit on the secondary side of the transformer is shown in Figure 26.23.
In Figure 26.22 the system voltage source [ELNABC] will typically be a balanced set of per-unit voltages. The Thevenin equivalent voltage on the secondary side of the transformer will be:
[Ethabc]=[At]⋅[ELNABC] (26.155)
The Thevenin equivalent impedance in Figure 26.23 from the source to the primary terminals of the feeder transformer is given by
[Zthabc]=[At][ZsysABC][dt]+[Bt] (26.156)
The values of the source side Thevenin equivalent circuit will be the same regardless of the type of connection of the feeder transformer. For each three-phase transformer connection, unique values of the matrices [Ethabc] and [Zthabc] are defined as functions of the source side Thevenin equivalent circuit. These definitions are shown for each transformer connection below.
The typical single-phase service to a customer is 120/240 V. This is provided from a center tapped single-phase transformer through the three-wire secondary and service drop to the customer’s meter. The center tapped single-phase transformer with the three-wire secondary and 120/240 V loads can be modeled as shown in Figure 26.24.
Notice in Figure 26.24 that three impedance values are required for the center tapped transformer. These three impedances typically will not be known. In fact, usually only the magnitude of the transformer impedance will be known as found on the nameplate. In order to perform a reasonable analysis, some assumptions have to be made regarding the impedances. It is necessary to know both the per-unit RA and the XA components of the transformer impedance. References Gonen (1986) and Hopkinson (1977) are two sources for typical values. From Hopkinson (1977) the center tapped transformer impedances as a function of the transformer impedance are given. For interlaced transformers the three impedances are given by
Z0=0.5RA+j0.8XAZ1=RA+j0.4XAZ2=RA+j0.4XA (26.157)
The equations for the noninterlaced design are
Z0=0.25RA+j0.6XAZ1=1.5RA+j3.3XAZ2=1.5RA+j3.1XA (26.158)
The transformer turns ratio is defined as
nt=high side rated voltagelow side half winding rated voltage (26.159)
Example :nt=7200120=60
With reference to Figure 26.24, note that the secondary current I1 flows out of the dot of the secondary half winding whereas the current I2 flows out of the undotted terminal. This is done in order to simplify the voltage drop calculations down the secondary. The basic transformer equations that must apply at all times are
E0=ntVt1=ntVt2I0=1nt(I1−I2) (26.160)
General matrix equations similar to those of the three-phase transformer connections are used in the analysis. For the backward sweep (working from the load toward the source), the equations are
[Vss]=[act][V12]+[bct][I12][I00]=[dct][I12] (26.161)
where
[Vss]=[VsVs]00[I00]=[I0I0][I12]=[I1I2]
[act]=[nt00nt][bct]=[nt(Z1+Z0n2t)−Z0ntZ0nt−nt(Z2+Z0n2t)][dct]=1nt[1−11−1] (26.162)
For the forward sweep (working from the source toward the loads) the equations are
[V12]=[Act][Vss]−[Bct][I12] (26.163)
where
[Act]=1nt[1001][Bct]=[Z1+Z0n2t−Z0n2tZ0n2t−(Z2+Z0n2t)] (26.164)
The three-wire secondary is modeled by first applying the Carson’s equations and Kron reduction method to determine the 2 × 2 phase impedance matrix:
[Zs]=[Zs11Zs12Zs21Zs22] (26.165)
The backward sweep equation becomes
[V12]=[as][VL12]+[bs][I12]
where
[as]=[1001][bs]=[Zs] (26.166)
The forward sweep equation is:
[VL12]=[As][V12]−[Bs][I12] (26.167)
where
[As]=[as]−1[Bs]=[Zs] (26.168)
Loads can be represented as being connected phase-to-phase or phase-to-neutral in a four-wire wye systems or phase-to-phase in a three-wire delta system. The loads can be three-phase, two-phase, or single-phase with any degree of unbalance and can be modeled as
The load models developed in this document are used in the iterative process of a power-flow program. All models are initially defined by a complex power per phase and either a line-to-neutral (wye load) or a line-to-line voltage (delta load). The units of the complex power can be in volt-amperes and volts or per-unit volt-amperes and per-unit volts.
For both the wye and delta connected loads, the basic requirement is to determine the load component of the line currents coming into the loads. It is assumed that all loads are initially specified by their complex power (S = P + jQ) per phase and a line-to-neutral or line-to-line voltage.
Figure 26.25 shows the model of a wye connected load.
The notation for the specified complex powers and voltages is as follows:
Phase a:|Sa|∠θa=Pa+jQa and |Van|∠δa (26.169)
Phase b:|Sb|∠θb=Pb+jQb and |Vbn|∠δb (26.170)
Phase c:|Sc|∠θc=Pc+jQc and |Vcn|∠δc (26.171)
ILa=(SaVan)*=|Sa||Van|∠δa−θa= |ILa|∠αaILb=(SbVbn)*=|Sb||Vbn|∠δb−θb= |ILb|∠αbILc=(ScVcn)*=|Sc||Vcn|∠δc−θc= |ILc|∠αc (26.172)
In this model the line-to-neutral voltages will change during each iteration until convergence is achieved.
The “constant load impedance” is first determined from the specified complex power and line-to-neutral voltages according to the following equation:
Za=|Van|2S*a=|Van|2|Sa|∠θa= |Za|∠θaZb=|Vbn|2S*b=|Vbn|2|Sb|∠θb= |Zb|∠θbZc=|Vcn|2S*c=|Vcn|2|Sc|∠θc= |Zc|∠θc (26.173)
The load currents as a function of the constant load impedances are given by the following equation:
ILa=VanZa=|Van||Za|∠δa−θa= |ILa|∠αaILb=VbnZb=|Vbn||Zb|∠δb−θb= |ILb|∠αbILc=VcnZc=|Vcn||Zc|∠δc−θc= |ILc|∠αc (26.174)
In this model the line-to-neutral voltages will change during each iteration until convergence is achieved.
In this model the magnitudes of the currents are computed according to Equation 26.172 and then held constant while the angle of the voltage (δ) changes during each iteration. In order to keep the power factor constant, the angles of the load currents are given by
ILa= |ILa|∠δa−θaILb= |ILb|∠δb−θbILc= |ILc|∠δc−θc (26.175)
Combination loads can be modeled by assigning a percentage of the total load to each of the above three load models. The total line current entering the load is the sum of the three components.
Figure 26.26 shows the model of a delta connected load.
The notation for the specified complex powers and voltages is as follows:
Phase ab : |Sab|∠θab=Pab+jQab and |Vab|∠δab (26.176)
Phase bc: |Sbc|∠θbc=Pbc+jQbc and |Vbc|∠δbc (26.177)
Phase ca:|Sca|∠θca=Pca+jQca and |Vca|∠δca (26.178)
ILab=(SabVab)*=|Sab||Vab|∠δab−θab= |ILab|∠αabILbc=(SbcVbc)*=|Sbc||Vbc|∠δbc−θbc= |ILbc|∠αbcILca=(ScaVca)*=|Sca||Vca|∠δca−θca= |ILca|∠αca (26.179)
In this model the line-to-line voltages will change during each iteration until convergence is achieved.
The constant load impedance is first determined from the specified complex power and line-to-neutral voltages according to the following equation:
Zab=|Vab|2S*ab=|Vab|2|Sab|∠θab= |Zab|∠θabZbc=|VLbc|2S*bc=|Vbc|2|Sbc|∠θbc= |Zbc|∠θbcZca=|Vca|2S*ca=|Vca|2|Sca|∠θca= |Zca|∠θca (26.180)
The load currents as a function of the constant load impedances are given by the following equation:
ILab=VabZab=|Vanb||Zab|∠δab−θab= |ILab|∠αabILbc=VbcZbc=|Vbc||Zbc|∠δbc−θbc= |ILbc|∠αbcILca=VcaZca=|Vca||Zca|∠δca−θca= |ILca|∠αca (26.181)
In this model the line-to-line voltages in Equation 26.181 will change during each iteration until convergence is achieved.
In this model the magnitudes of the currents are computed according to Equation 26.179 and then held constant while the angle of the voltage (δ) changes during each iteration. This keeps the power factor of the load constant.
ILab= |ILab|∠δab−θabILbc= |ILbc|∠δbc−θbcILca= |ILca|∠δca−θca (26.182)
Combination loads can be modeled by assigning a percentage of the total load to each of the above three load models. The total delta current for each load is the sum of the three components.
The line currents entering the delta connected load for all models are determined by
[ILaILbILc]=[10−1−1100−11] [ILabILbcILca] (26.183)
In both the wye and delta connected loads, single-phase and two-phase loads are modeled by setting the complex powers of the missing phases to zero. In other words, all loads are modeled as three-phase loads and by setting the complex power of the missing phases to zero, the only load currents computed using the above equations will be for the nonzero loads.
Shunt capacitor banks are commonly used in a distribution system to help in voltage regulation and to provide reactive power support. The capacitor banks are modeled as constant susceptances connected in either wye or delta. Similar to the load model, all capacitor banks are modeled as three-phase banks with the kVAr of missing phases set to zero for single-phase and two-phase banks.
A wye connected capacitor bank is shown in Figure 26.27. The individual phase capacitor units are specified in kVAr and kV. The constant susceptance for each unit can be computed in either Siemans or per unit. When per unit is desired, the specified kVAr of the capacitor must be divided by the base single-phase kVAr and the kV must be divided by the base line-to-neutral kV.
The susceptance of a capacitor unit is computed by
Bactual=kVArkV21000 Siemans (26.184)
Bpu=kVArpuV2pu per unit (26.185)
where
kVArpu=kVAractualkVAsingle_phase_base (26.186)
Vpu=kVactualkVline_to_neutral_base (26.187)
The per-unit value of the susceptance can also be determined by first computing the actual value (Equation 26.184) and then dividing by the base admittance of the system.
With the susceptance computed, the line currents serving the capacitor bank are given by
ICa=jBaVanICb=jBbVbnICc=jBcVcn (26.188)
A delta connected capacitor bank is shown in Figure 26.28.
Equations 26.184 through 26.187 can be used to determine the value of the susceptance in actual Siemans or per unit. It should be pointed out that in this case, the kV will be a line-to-line value of the voltage. Also, it should be noted that in Equation 26.187, the base line-to-neutral voltage is used to compute the per-unit line-to-line voltage. This is a variation from the usual application of the per-unit system where the actual line-to-line voltage would be divided by a base line-to-line voltage in order to get the per-unit line-to-line voltage. That is not done here so that under normal conditions, the per-unit line-to-line voltage will have a magnitude of √3 rather than 1.0. This is done so that Kirchhoff’s current law (KCL) at each node of the delta connection will apply for either the actual or per-unit delta currents.
The currents flowing in the delta connected capacitors are given by
ICab=jBabVabICbc=jBbcVbcICca=jBcaVca (26.189)
The line currents feeding the delta connected capacitor bank are given by
[ICaICbICc]=[10−1−1100−11] [ICabICbcICca] (26.190)
The power-flow analysis of a distribution feeder is similar to that of an interconnected transmission system. Typically what will be known prior to the analysis will be the three-phase voltages at the substation and the complex power of all the loads and the load model (constant complex power, constant impedance, constant current, or a combination). Sometimes, the input complex power supplied to the feeder from the substation is also known.
In Sections 26.1.3 through 26.1.5, phase frame models were presented for the series components of a distribution feeder. In Sections 26.1.6 and 26.1.7, models were presented for the shunt components (loads and capacitor banks). These models are used in the “power-flow” analysis of a distribution feeder.
A power-flow analysis of a feeder can determine the following by phase and total three-phase:
Because the feeder is radial, iterative techniques commonly used in transmission network power-flow studies are not used because of poor convergence characteristics (Trevino, 1970). Instead, an iterative technique specifically designed for a radial system is used. The ladder iterative technique (Kersting and Mendive, 1976) will be presented here.
A modification of the ladder network theory of linear systems provides a robust iterative technique for power-flow analysis. A distribution feeder is nonlinear because most loads are assumed to be constant kW and kVAr. However, the approach taken for the linear system can be modified to take into account the nonlinear characteristics of the distribution feeder.
For the ladder network in Figure 26.29, it is assumed that all of the line impedances and load impedances are known along with the voltage at the source (Vs).
The solution for this network is to assume a voltage at the most remote load (V5). The load current I5 is then determined as
I5=V5ZL5 (26.191)
For this “end-node” case, the line current I45 is equal to the load current I5. The voltage at node 4 (V4) can be determined using Kirchhoff’s voltage law (KVL):
V4=V5+Z45I45 (26.192)
The load current I4 can be determined and then KCL applied to determine the line current I34.
I34=I45+I4 (26.193)
KVL is applied to determine the node voltage V3. This procedure is continued until a voltage (V1) has been computed at the source. The computed voltage V1 is compared to the specified voltage Vs. There will be a difference between these two voltages. The ratio of the specified voltage to the compute voltage can be determined as
Ratio=VsV1 (26.194)
Since the network is linear, all of the line and load currents and node voltages in the network can be multiplied by the Ratio for the final solution to the network.
The linear network of Figure 26.29 is modified to a nonlinear network by replacing all of the constant load impedances by constant complex power loads as shown in Figure 26.30.
The procedure outlined for the linear network is applied initially to the nonlinear network. The only difference being that the load current (assuming constant P and Q) at each node is computed by
In=(SnVn)* (26.195)
The backward sweep will determine a computed source voltage V1. As in the linear case, this first iteration will produce a voltage that is not equal to the specified source voltage Vs. Because the network is nonlinear, multiplying currents and voltages by the ratio of the specified voltage to the computed voltage will not give the solution. The most direct modification to the ladder network theory is to perform a forward sweep. The forward d sweep commences by using the specified source voltage and the line currents from the backward sweep. KVL is used to compute the voltage at node 2 by
V2=Vs−Z12I12 (26.196)
This procedure is repeated for each line segment until a “new” voltage is determined at node 5. Using the new voltage at node 5, a second backward sweep is started that will lead to a new computed voltage at the source. The backward and forward sweep process is continued until the difference between the computed and specified voltage at the source is within a given tolerance.
A typical distribution feeder will consist of the “primary main” with laterals tapped off the primary main, and sublaterals tapped off the laterals, etc., Figure 26.30 shows an example of a typical feeder.
The ladder iterative technique for the feeder of Figure 26.31 would proceed as follows:
The previous section outlined the general procedure for performing the ladder iterative technique. This section will address how that procedure can be used for an unbalanced three-phase feeder.
Figure 26.32 is the one-line diagram of an unbalanced three-phase feeder. The topology of the feeder in Figure 26.32 is the same as the feeder in Figure 26.31. Figure 26.32 shows more detail of the feeder however. The feeder in Figure 26.32 can be broken into the series components and the shunt components.
The series components of a distribution feeder are
Models for each of the series components have been developed in prior areas of this section. In all cases, models (three-phase, two-phase, and single-phase) were developed in such a manner that they can be generalized. Figure 26.33 shows the “general model” for each of the series components.
The general equations defining the “input” (node n) and “output” (node m) voltages and currents are given by
[Vabc]n=[a][Vabc]m+[b][Iabc]m (26.197)
[Iabc]n=[c][Vabc]m+[d][Iabc]m (26.198)
The general equation relating the output (node m) and input (node n) voltages is given by
[Vabc]m=[A][Vabc]n+[B][Iabc]m (26.199)
In Equations 26.197 through 26.199, the voltages are line-to-neutral for a four-wire wye feeder and equivalent line-to-neutral for a three-wire delta system. For transformers and voltage regulators, the voltages are line-to-neutral for terminals that are connected to a four-wire wye and line-to-line when connected to a three-wire delta.
The shunt components of a distribution feeder are
Spot loads are located at a node and can be three-phase, two-phase, or single-phase and connected in either a wye or a delta connection. The loads can be modeled as constant complex power, constant current, constant impedance, or a combination of the three.
Distributed loads are located at the midsection of a line segment. A distributed load is modeled when the loads on a line segment are uniformly distributed along the length of the segment. As in the spot load, the distributed load can be three-phase, two-phase, or single-phase and connected in either a wye or a delta connection. The loads can be modeled as constant complex power, constant current, constant impedance, or a combination of the three. To model the distributed load, a “dummy” node is created in the center of a line segment with the distributed load of the line section modeled at this dummy node.
Capacitor banks are located at a node and can be three-phase, two-phase, or single-phase and can be connected in a wye or delta. Capacitor banks are modeled as constant admittances.
In Figure 26.32 the solid line segments represent overhead lines while the dashed lines represent underground lines. Note that the phasing is shown for all of the line segments. In the area of the Section 26.1.1, the application of Carson’s equations for computing the line impedances for overhead and underground lines was presented. There it was pointed out that two-phase and single-phase lines are represented by a 3 × 3 matrix with zeros set in the rows and columns of the missing phases.
In the area of the Section 26.1.2, the method for the computation of the shunt capacitive susceptance for overhead and underground lines was presented. Most of the time the shunt capacitance of the line segment can be ignored; however, for long underground segments, the shunt capacitance should be included.
The “node” currents may be three-phase, two-phase, or single-phase and consist of the sum of the load current at the node plus the capacitor current (if any) at the node.
The previous section outlined the steps required for the application of the ladder iterative technique. For the general feeder of Figure 26.32 the same outline applies. The only difference is that Equations 26.197 and 26.198 are used for computing the node voltages on the backward sweep and Equation 26.199 is used for computing the downstream voltages on the forward sweep. The [a], [b], [c], [d], [A], and [B] matrices for the various series components are defined in the following areas of this section:
The node currents are defined in the following area:
It is extremely important that the impedances and admittances of the line segments be computed using the exact spacings and phasing. Because of the unbalanced loading and resulting unbalanced line currents, the voltage drops due to the mutual coupling of the lines become very important. It is not unusual to observe a voltage rise on a lightly loaded phase of a line segment that has an extreme current unbalance.
The real power losses of a line segment must be computed as the difference (by phase) of the input power to a line segment minus the output power of the line segment. It is possible to observe a negative power loss on a phase that is lightly loaded compared to the other two phases. Computing power loss as the phase current squared times the phase resistance does not give the actual real power loss in the phases.
Many times the input complex power (kW and kVAr) to a feeder is known because of the metering at the substation. This information can be either total three-phase or for each individual phase. In some cases the metered data may be the current and power factor in each phase.
It is desirable to have the computed input to the feeder match the metered input. This can be accomplished (following a converged iterative solution) by computing the ratio of the metered input to the computed input. The phase loads can now be modified by multiplying the loads by this ratio. Because the losses of the feeder will change when the loads are changed, it is necessary to go through the ladder iterative process to determine a new computed input to the feeder. This new computed input will be closer to the metered input, but most likely not within a specified tolerance. Again, a ratio can be determined and the loads modified. This process is repeated until the computed input is within a specified tolerance of the metered input.
The computation of short-circuit currents for unbalanced faults in a normally balanced three-phase system has traditionally been accomplished by the application of symmetrical components. However, this method is not well-suited to a distribution feeder that is inherently unbalanced. The unequal mutual coupling between phases leads to mutual coupling between sequence networks. When this happens, there is no advantage to using symmetrical components. Another reason for not using symmetrical components is that the phases between which faults occur is limited. For example, using symmetrical components, line-to-ground faults are limited to phase a to ground. What happens if a single-phase lateral is connected to phase b or c? This section will present a method for short-circuit analysis of an unbalanced three-phase distribution feeder using the phase frame (Kersting, 1980).
Figure 26.34 shows the unbalanced feeder as modeled for short-circuit calculations. In Figure 26.34, the voltage sources Ea, Eb, and Ec represent the Thevenin equivalent line-to-ground voltages at the faulted bus. The matrix [ZTOT] represents the Thevenin equivalent impedance matrix at the faulted bus. The fault impedance is represented by Zf in Figure 26.34.
Kirchhoff’s voltage law in matrix form can be applied to the circuit of Figure 26.33.
[EaEbEc]=[ZaaZabZacZbaZbbZbcZcaZcbZcc] [IfaIfbIfc]+[Zf000Zf000Zf] [IfaIfbIfc]+[VaxVbxVcx]+[VxgVxgVxg] (26.200)
Equation 26.188 can be written in compressed form as
[Eabc]=[ZTOT][Ifabc]+[ZF][Ifabc]+[Vabcx]+[Vxg] (26.201)
Combine terms in Equation 26.201.
[Eabc]=[ZEQ][Ifabc]+[Vabcx]+[Vxg] (26.202)
where
[ZEQ]=[ZTOT]+[ZF] (26.203)
Solve Equation 26.202 for the fault currents:
[Ifabc]=[YEQ][Eabc]−[YEQ][Vabcx]−[YEQ][Vxg] (26.204)
where
[YEQ]=[ZEQ]−1 (26.205)
Since the matrices [YEQ] and [Eabc] are known, define
[IPabc]=[YEQ][Eabc] (26.206)
Substituting Equation 26.206 into Equation 26.204 results in the following expanded equation:
[IfaIfbIfc]=[IPaIPbIPc]−[YaaYabYacYbaYbbYbcYcaYcbYcc] [VaxVbxVcx]−[YaaYabYacYbaYbbYbcYcaYcbYcc] [VxgVxgVxg] (26.207)
Performing the matrix operations in Equation 26.195:
Ifa=IPa−(YaaVax+YabVbx+YacVcx)−YaVxgIfb=IPb−(YbaVax+YbbVbx+YbcVcx)−YbVxgIfc=IPc−(YcaVax+YcbVbx+YccVcx)−YcVxg (26.208)
where
Ya=Yaa+Yab+YacYb=Yba+Ybb+YbcYc=Yca+Ycb+Ycc (26.209)
Equation 26.208 become the general equations that are used to simulate all types of short circuits. Basically there are three equations and seven unknowns (Ifa, Ifb, Ifc, Vax, Vbx, Vcx, and Vxg). The other three variables in the equations (IPa, IPb, and IPc) are functions of the total impedance and the Thevenin voltages and are therefore known. In order to solve Equation 26.208, it will be necessary to specify four of the seven unknowns. These specifications are functions of the type of fault being simulated. The additional required four knowns for various types of faults are given below:
Three-phase faults
Vax=Vbx=Vcx=0Ia+Ib+Ic=0 (26.210)
Three-phase-to-ground faults
Vax=Vbx=Vcx=Vxg=0 (26.211)
Line-to-line faults (assume i–j fault with phase k unfaulted)
Vix=Vjx=0Ifk=0Ifi=Ifj=0 (26.212)
Line-to-line-to-ground faults (assume i–j to ground fault with k unfaulted)
Vix=Vjx=Vxg=0Vkx=IPkYkk (26.213)
Line-to-ground faults (assume phase k fault with phases i and j unfaulted)
Vkx=Vxg=0Ifi=Ifj=0 (26.214)
Notice that Equations 26.212 through 26.214 will allow the simulation of line-to-line, line-to-line-to-ground, and line-to-ground faults for all phases. There is no limitation to b–c faults for line-to-line and a–g for line-to-ground as is the case when the method of symmetrical components is employed.
Carson, J.R., Wave propagation in overhead wires with ground return, Bell Syst. Tech. J., 5, 539–554, 1926.
Glover, J.D. and Sarma, M., Power System Analysis and Design, 2nd edn., PWS Publishing Company, Boston, MA, Chapter 5, 1994.
Gonen, T., Electric Power Distribution System Engineering, McGraw-Hill Book Company, New York, 1986.
Hopkinson, R.H., Approximate distribution transformer impedances, from an internal GE Memo dated August 30, 1977.
Kersting, W.H., Distribution system short circuit analysis, 25th Intersociety Energy Conversion Conference, Reno, NV, August 1980.
Kersting, W.H., Milsoft transformer models—Theory, research Report, Milsoft Integrated Solutions, Inc., Abilene, TX, 1999.
Kersting, W.H. and Mendive, D.L., An application of ladder network theory to the solution of three-phase radial load-flow problems, IEEE Conference Paper presented at the IEEE Winter Power Meeting, New York, January 1976.
Kron, G., Tensorial analysis of integrated transmission systems, Part I: The six basic reference frames, AIEE Trans., 71, 505–512, 1952.
Trevino, C., Cases of difficult convergence in load-flow problems, IEEE Paper no. 71-62-PWR, presented at the IEEE Summer Power Meeting, July 12–17, 1970, Los Angeles, CA, 1970.