Chapter 18

Lightning Protection

18.1 Ground Flash Density 18-1

18.2 Mitigation Methods 18-3

18.3 Stroke Incidence to Power Lines 18-3

18.4 Stroke Current Parameters 18-4

18.5 Calculation of Lightning Overvoltage on Grounded Object 18-5

18.6 Calculation of Resistive Voltage Rise VR 18-5

18.7 Calculation of Inductive Voltage Rise VL 18-6

18.8 Calculation of Voltage Rise on Phase Conductor 18-6

18.9 Joint Distribution of Peak Voltage on Insulators 18-7

18.10 Insulation Strength 18-8

18.11 Calculation of Transmission Line Outage Rate 18-9

18.12 Improving the Transmission Line Lightning Outage Rate 18-11

Increasing the Insulator Dry Arc Distance • Modifying the Distribution of Footing Resistance • Increasing the Effective Number of Groundwires Using UBGW • Increasing the Effective Number of Groundwires Using Line Surge Arresters

18.13 Conclusion 18-13

References 18-13

William A. Chisholm

Kinectrics/Université du Québec à Chicoutimi

The study of lightning predates electric power systems by many centuries. Observations of thunder were maintained in some areas for more than a millennium. Franklin and others established the electrical nature of lightning, and introduced the concepts of shielding and grounding to protect structures. Early power transmission lines used as many as six overhead shield wires, strung above the phase conductors and grounded at the towers for effective lightning protection. Later in the twentieth century, repeated strikes to tall towers, buildings, and power lines, contradicting the adage that “it never strikes twice,” allowed systematic study of stroke current parameters. Improvements in electronics, computers, telecommunications, rocketry, and satellite technologies have all extended our knowledge about lightning, while at the same time exposing us to ever-increasing risks of economic damage from its consequences.

18.1 Ground Flash Density

The first return stroke from the direct termination of a negative, downward cloud-to-ground lightning flash is the dominant risk to power system components. Positive first strokes, negative subsequent strokes, and continuing currents can also cause specific problems. A traditional indicator of cloud-to-ground lightning activity is given by thunder observations, collected to World Meteorological Organization standards and converted to Ground Flash Density (Anderson et al., 1984; MacGorman et al., 1984):

GFD=0.04TD1.25 (18.1)

GFD=0.054TH1.1 (18.2)

where

TD is the number of days with thunder per year

TH is the number of hours with thunder per year

GFD is the number of first cloud-to-ground strokes per square kilometer per year

Long-term thunder data suggest that GFD has a relative standard deviation of 30%.

Observations of optical transient density have been performed using satellites starting in 1995. These data have some of the same defects as thunder observations: cloud flash and ground flash activity is equally weighted and the observations are sporadic. However, statistical considerations as well as richly detailed observations of orographic terrain features now favor the use of optical transient density, reported by (Christian et al., 2003; NASA, 2006) over thunder observations to estimate ground flash density.

A good estimate of ground flash density can be obtained by dividing the optical transient density values in Figure 18.1 by a factor of 3.0. This average factor is valid in four different continents but may vary across regions, calling for a lower factor in some limited areas where storms have a higher ratio of positive to negative flashes.

Figure 18.1

Image of >Observed optical transient density per km2 per year from NASA (2006)

Observed optical transient density per km2 per year from NASA (2006). The optical transient density (OTD) can be used to estimate lightning ground flash density N g (flashes per km2 per year) by dividing the observed values by 3.0.

Electromagnetic signals from individual lightning strokes are unique and have high signal-to-noise ratio at large distances. Many single-station lightning flash counters have been developed and calibrated, each with good discrimination between cloud flash and ground flash activity using simple electronic circuits (Heydt, 1982). It has also been feasible for more than 30 years (Krider et al., 1976) to observe these signals with two or more stations, and to triangulate lightning stroke locations on a continent-wide basis. Lightning location networks have improved continuously to the point where multiple ground strikes from a single flash can be resolved with high spatial and temporal accuracy and high probability of detection (CIGRE, 2009). A GFD value from these data should be based on approximately 400 counts in each cell to reduce relative standard deviation of the observation process below 5%. In areas with moderate flash density, a minimum cell size of 20 × 20 km is appropriate.

18.2 Mitigation Methods

Lightning mitigation methods for transmission lines need to be appropriate for the expected long-term ground flash density and power system reliability requirements. Table 18.1 summarizes typical practices at five different levels of lightning activity to achieve a reliability of 1 outage per 100 km of line per year on an HV line.

Table 18.1

Typical Design Approaches for Overhead Transmission Lines

Optical Transient Density from Figure 18.1 (Transients per km2 per Year)

Ground Flash Density Range (Flashes per km2 per Year)

Typical Design Approaches

0.3–1

0.1–0.3

Unshielded, one or three-pole reclosing

1–3

0.3–1

Single overhead shield wire or unshielded with line arresters, upper phases, all towers

3–10

1–3

Two overhead shield wires

10–30

3–10

Two overhead shield wires with good grounding or line surge arresters

30–100

10–30

Three or more overhead and underbuilt shield wires with good grounding; line surge arresters; underground transmission cables

Power system insulation is designed to withstand overvoltages that are generated within the power system, under steady state and also when components are switched. Unfortunately, even the weakest direct lightning stroke from a shielding failure to a phase conductor will cause an overvoltage that will flash over across an insulator that is not protected by a surge arrester nearby. Once an arc appears across an insulator, the power system fault current keeps this arc alive until voltage is removed by protective relay action. If the flash incidence is low, Table 18.1 shows that some utilities can simply accept a high tripout rate, up to 6 interruptions per 100 km per year, and can protect against the consequences using automatic reclosing and redundant paths.

Effective overhead shielding, with wires placed above the phase conductors to intercept flashes and divert them to ground, is the most common form of lightning protection on transmission lines in areas with moderate to high ground flash density.

When the overhead shield wire is struck, the potential difference on insulators is the sum of the resistive and inductive voltage rises on the tower, minus the coupled voltage on the phase conductors. The potential difference can lead to a “backflashover” from the tower to the phase conductor.

Backflashover is probable when peak stroke current is large, when footing resistance is high and when insulation strength is low. Simplified models (CIGRE, 1991; IEEE, 1997; EPRI, 2005) are available to carry out the lightning overvoltage calculations and coordinate the results with insulator strength, giving lightning outage rates. A schematic of this process is given as follows.

18.3 Stroke Incidence to Power Lines

The lightning leader, a thin column of electrically-charged plasma, develops from cloud down to the ground in a series of step breakdowns (Rakov and Uman, 2007). Near the ground, electric fields are high enough to satisfy the conditions for continuous positive leader inception upward from tall objects or conductors. Analysis of a single overhead conductor with this approach (Rizk, 1990) leads to

NS=3.8GFDh0.45 (18.3)

where

NS is the number of strikes to the conductor per 100 km of line length per year

h is the average height of the conductor above ground in meters

In areas of moderate to high ground flash density, one or more overhead shield wires are usually installed above the phase conductors. This shielding usually has a success rate of greater than 95%, but adds nearly 10% to the cost of line construction and also wastes energy from induced currents. The leader inspection model (Rizk, 1990) has been developed to analyze shielding failures more accurately. The goal was to reduce the failure rate below the IEEE set reliability target of 0.05 per 100 km per year (IEEE, 1997).

18.4 Stroke Current Parameters

Once the downward leader contacts a power system component through an upward-connecting leader, the stored charge will be swept from the channel into a grounded object through a plasma channel with high internal impedance of 600–4000 Ω. With this high source impedance relative to the impedance of grounded structures, an impulse current source model is suitable.

Berger (1977) made the most reliable direct measurements of current and charge flow from negative downward cloud-to-ground lightning parameters on an instrumented tower from 1947 to 1977. Additional observations have been provided by many researchers and then summarized (Anderson and Eriksson, 1980; CIGRE, 1991; Takami and Okabe, 2007). The overall stroke current distribution can be approximated as lognormal with a mean of 31 kA and a log standard deviation of σln(I) = 0.48. The probability of exceeding a first return stroke peak current magnitude I can also be estimated from (CIGRE, 1991; IEEE, 1997; EPRI, 2005; IEEE, 2010):

P(I)=11+(I31kA)2.6 (18.4)

The peak stroke current associated with a given probability level P can be obtained by inverting Equation 18.4 to obtain

I=(31kA)(1PP)(1/2.6) (18.5)

This leads to the following probability table.

Table 18.2 suggests that there will be a 15% chance that the first negative return stroke peak current will exceed 60 kA, and an 85% chance that it will exceed 16 kA.

Table 18.2

Probability of Exceeding First Return Stroke Current in Lightning Flash

Probability

0.05

0.15

0.25

0.35

0.45

0.55

0.65

0.75

0.85

0.95

Peak current (kA)

96.2

60.4

47.3

39.3

33.5

28.7

24.4

20.3

15.9

10.0

The waveshape of the first return stroke current rises with a concave front, giving the maximum steepness near the crest of the wave, then decays with a time to half value of 50 μs or more. The median value of maximum steepness (CIGRE, 1991) is 24 kA/μs, with a log standard deviation of 0.60. Steepness has a strong correlation to the peak amplitude (CIGRE, 1991; Takami and Okabe, 2007) that allows simplified modeling using a single equivalent front time (peak current divided by peak rate of rise). The mean equivalent front is 1.4 μs for the median 31 kA current, and increases to 2.7 μs as peak stroke current increases to the 5% level of 100 kA (Takami and Okabe, 2007). An equivalent front time of 2 μs is recommended for simplified analysis of lightning performance (CIGRE, 1991; IEEE, 1997) with peak currents in the range of 50–150 kA.

18.5 Calculation of Lightning Overvoltage on Grounded Object

The peak voltage resulting from a lightning flash can be estimated from the sum of two components, the resistive voltage rise of the nearest ground electrode VR and the inductive voltage rise VL. The voltage rise VL associated with conductor and tower series inductance L and the equivalent front time (Δt = 2 μs) is VL = LI/Δt. The VL term will add to, and sometimes dominate, VR.

18.6 Calculation of Resistive Voltage Rise VR

The voltage rise VR of the ground resistance Rf at each tower will be proportional to peak stroke current: VR = RfI. The resistance Rf of a tower base consisting of foundations, buried wires and anchor systems in close proximity, can be estimated closely using

Rf=ρ2π[1gln(11.8g2ATotal)+1lln(ATotal2AWire)] (18.6)

where

ρ is the soil resistivity (Ω-m)

g is the geometric radius, given by the square root of the sum of the squares of the electrode extent in each direction (m)

ATotal is the surface area (sides + base) of the hole needed to excavate the electrode (m2)

l is the total length (m) of wire and foundations in the wire frame approximation to the electrode (infinite for solid electrodes)

AWire is the surface area (2πrl) of the wire and concrete in the wire frame, with wire radius r, requiring ATotal ≥ 2AWire

ln is the natural logarithm function

For large surge currents, local ionization will reduce the second contact resistance term (varying as 1/l) but not the first geometric resistance term varying as 1/g inside the square braces of Equation 18.6.

The soil resistivity ρ along a transmission line has a rather wide statistical distribution, typically with log standard deviation σln(ρ) of 0.9. The variation of resistivity from tower to tower can be expressed as a probability function of the form

P(ρ)=11+(ρρMedian)1.85 (18.7)

The local soil resistivity associated with a given probability level P can be obtained by inverting Equation 18.7 to obtain

ρ=ρMedian(1PP)(1/1.85) (18.8)

This leads to the following probability table.

Table 18.3 suggests that there will be a 5% chance that the soil resistivity at any randomly selected tower will be 4.9 times higher than the median value over the entire line length.

Table 18.3

Probability of Exceeding Soil Resistivity ρ

Probability

0.05

0.15

0.25

0.35

0.45

0.55

0.65

0.75

0.85

0.95

ρ /ρ Median

4.9

2.6

1.8

1.4

1.1

0.9

0.7

0.6

0.4

0.2

18.7 Calculation of Inductive Voltage Rise VL

Lumped inductance of a structure can be approximated from the expression

L=Zτ=60ln(2hr)lc (18.9)

where

L is the inductance in Henries

Z is the element antenna impedance in ohms

h is the wire height above conducting ground (m)

r is the wire or overall structure radius (m)

l is the length of the wire or structure (m)

c is the speed of light (3 × 108 m/s)

In numerical analyses, series and shunt impedance elements can be populated using the same procedure. Tall transmission towers have longer travel times τ and thus higher inductance, which further exacerbates the increase of stroke incidence with line height. Thin steel pole structures, and wooden poles with bond wires of small radius r, will also have higher inductance than lattice towers with multiple paths to ground, giving a larger overall radius. The inductance of structures with guy wires is given by the parallel combination of the inductance of the central structure and the inductances of the individual guy wires, ignoring mutual coupling (CIGRE, 1991).

18.8 Calculation of Voltage Rise on Phase Conductor

The high electromagnetic fields surrounding any lighting flash illuminate nearby conductors and cause the flow of current, leading to induced voltages across insulators.

Fields from vertical lightning strokes to ground near overhead lines can induce overvoltages with 100–300 kV peak magnitude in nearby overhead lines without a direct flash termination. This is a particular concern only for MV and LV systems (IEEE, 2010).

In the case of a lightning flash directly to an overhead groundwire (OHGW), a small fraction of the overall current flows in horizontal directions, away from the flash location into every interconnected groundwire, shield wire beneath the phases and any phase conductor protected by a parallel line surge arrester. The voltage rise on each participant in this current flow increases common-mode voltage and reduces differential voltage across insulators through transverse electromagnetic (TEM) or surge-impedance coupling to insulated phases. Bundle configurations and corona can improve this desirable surge-impedance coupling to mitigate half of the total tower potential rise (VR + VL), but increasing separation between the phases and groundwires will reduce the effect.

Calculation of the coupling coefficients Cn on the undriven, unprotected phase conductors calls for registering the self and mutual surge impedances of each phase and groundwire, setting the voltage on the stricken conductors to unity and calculating the potential rise on undriven phases from the inverse of the resulting surge impedance matrix. Simplified methods for systems with one or two overhead groundwires (CIGRE, 1991; IEEE, 1997) consider voltage dependent corona effects as well as bundle conductor impedance.

The combined peak stress on an insulator under lightning surge conditions, VPk (kV), with a linear front time Δt of 2 μs, can be approximated by

VPkIPk(1Cn)1Rf+L2μs+2nZGW (18.10)

where

IPk is the peak first return stroke current (kA)

Cn is the surge impedance coupling coefficient from n groundwires, modified for corona effects

n is the number of groundwires, including OHGWs, underbuilt OPGW, and neutral wires and phases protected with line surge arresters

ZGW is an average value of surge impedance of the groundwires (Ω)

Rf is the resistance of the stricken tower to ground from Equation 18.6 (Ω)

L is the inductance of the stricken tower from insulator location to ground (H) from Equation 18.7

18.9 Joint Distribution of Peak Voltage on Insulators

Since the peak stroke current and the resistivity at the base of a tower are statistically independent, the joint distribution of their voltage stress levels can be obtained by summing over the probability of all possible events.

Table 18.4 shows that the voltage stress on a transmission line insulator varies by a 50:1 range as a result of statistical variations in lightning peak current magnitude and tower-to-tower changes in soil resistivity.

Table 18.4

Probability Table for Insulator Voltage Rise on Untreated Line Median R f of 15 Ω , L of 15 μ H, Z GW 500 Ω , n = 2, C n = 0.3

V pk (I pk , R f ) (kV)

P (I pk )

0.05

0.15

0.25

0.35

0.45

0.55

0.65

0.75

0.85

0.95

P (R f )

R f (Ω )

I pk (kA)

96.2

60.4

47.3

39.3

33.5

28.7

24.4

20.3

15.9

10.0

0.05

73.7

3314

2081

1630

1355

1154

989

842

700

548

344

0.15

38.3

2258

1418

1110

923

786

673

573

477

373

234

0.25

27.2

1828

1148

899

747

636

545

464

386

302

190

0.35

21.0

1561

980

768

638

543

466

396

330

258

162

0.45

16.7

1366

858

672

559

476

408

347

289

226

142

0.55

13.5

1209

759

594

494

421

361

307

255

200

126

0.65

10.7

1072

673

527

438

373

320

272

226

177

111

0.75

8.3

944

593

464

386

328

282

240

199

156

98

0.85

5.9

814

511

400

333

283

243

207

172

135

84

0.95

3.1

655

412

322

268

228

196

166

138

108

68

Electrical utilities will often install additional buried grounding electrodes, such as vertical rods or radial counterpoise wires a meter below grade, at towers that have high soil resistivity. Construction specifications may call for achieving “20 Ω resistance where practical.” Thus, the distribution of footing resistance Rf in Table 18.4 is modified by a “treatment rule” that follows this general model:

  • If Rf < 20 Ω, do nothing.
  • If 20 Ω < Rf < 40 Ω, install enough grounding to reduce to 20 Ω.
  • If Rf > 40 Ω, install enough grounding to reduce Rf by factor of 2.

This treatment strategy will improve the line outage rate as shown hereafter.

18.10 Insulation Strength

The lightning impulse flashover gradient (kV CFO per meter of dry arc distance) of typical transmission line insulator strings is linear over a wide range from 1 to 6 m. The critical flashover level (CFO) is the median voltage at which flashover occurs when tested with a standard lightning impulse voltage wave with 1.2 μs rise time and 50 μs time to half value, and is normally distributed with a relative standard deviation of about 5%. The CFO for full lightning impulse voltage waves scales linearly with insulator string dry arc distance as shown in Table 18.6.

Table 18.6

Peak Flashover Voltage (kV) versus Probability of Flashover for Insulator Strings Based on Critical Impulse Flashover Gradient of 540 kV/m and 5% Relative Standard Deviation

Dry Arc Distance (m)

Critical Impulse Flashover Level (kV)

Standard Deviation of CFO (kV)

Probability Level (Normal Distribution)

0.05

0.15

0.25

0.35

0.45

0.55

0.65

0.75

0.85

0.95

1

540

27

496

512

522

530

537

543

550

558

568

584

2

1080

54

991

1024

1044

1059

1073

1087

1101

1116

1136

1169

3

1620

81

1487

1536

1565

1589

1610

1630

1651

1675

1704

1753

4

2160

108

1982

2048

2087

2118

2146

2174

2202

2233

2272

2338

The probability of flashover with 5% relative standard deviation can be approximated conveniently by Equation 18.11. For example, with VPk = 1136 kV applied to insulation having CFO = 1080 kV, the probability of flashover is 85%. However, accurate normal distribution functions are readily accessible in spreadsheets such as Excel and should be used where available:

P(flashover)111+(VPkCFO(t))35 (18.11)

The lightning impulse flashover voltage has a pronounced nonlinear volt–time characteristic, giving an increasing ability to withstand short-duration impulses at times t less than 10 μs compared to the full-wave CFO strength of 540 kV/m. The lightning surge itself peaks in an equivalent front time of about 2 μs. A simplified method may evaluate the possibility of flashover at this time t, resulting in a fixed strength of 822 kV per meter of dry arc distance DDry Arc based on a volt–time characteristic as follows (Darveniza et al., 1975):

CFO=DDryArc(400+710t0.75) (18.12)

where

DDry Arc is the dry arc distance of the insulator (m), in the range of 1–6 m

t is the time of flashover (μs), in the range of 0.3–14 μs

CFO is the peak of the applied standard lightning impulse voltage wave (kV) that causes a flashover 50% of the time

A volt–time curve approach such as Equation 18.12 remains valid up to the point in time when the applied voltage wave deviates significantly from the standard test wave. In the case of transmission lines, this point is well defined as the time at which cancelling reflections from the ground electrodes of nearby towers arrive, after a propagation time tSpan associated with 90% of the speed of light, c. Table 18.7 shows that the span length can thus change the critical flashover voltage by ±10%, leading to about ±30% changes in the predicted line outage rate.

Table 18.7

Peak Flashover Voltage (kV) for 1-m (7 Standard Disk) Insulator String as Function of Span Length

Span (m)

Travel Time (μ s)

CFO at t Span (kV)

Standard Deviation of CFO (kV)

Probability Level (Normal Distribution)

0.05

0.15

0.25

0.35

0.45

0.55

0.65

0.75

0.85

0.95

200

1.5

929

46

852

881

897

911

923

935

947

960

977

1005

250

1.9

847

42

778

803

819

831

842

853

864

876

891

917

300

2.2

790

40

725

749

763

775

785

795

805

817

831

855

350

2.6

748

37

686

709

722

733

743

752

762

773

786

809

18.11 Calculation of Transmission Line Outage Rate

The lightning outage rate of a transmission line is given by the number of flashes to the line, Equation 18.3, multiplied by the probability of flashover of each flash. Table 18.4 and Table 18.5 have shown how the distribution of peak backflashover voltage stress across insulation varies for the probability distribution of peak first return stroke current Ipk and footing resistance Rf, considering that other factors such as tower inductance Ltwr, number of OHGWs n, and the related coupling coefficient Cn in Equation 18.10 are all fixed. Table 18.6 and Table 18.7 give the insulation characteristics as a function of insulator dry arc distance DDry Arc and span length, which can also be calculated with Equation 18.12 for a particular line design or section. Thus, the calculation of a line outage rate simplifies into a calculation of the probability of flashover for each element in Table 18.4 or Table 18.5, summed over the entire range of probability as illustrated in Figure 18.2.

Table 18.5

Probability Table for Insulator Voltage Rise on Treated Line Median R f of 15 Ω , Treatment to 20 Ω , L of 15 μ H, Z GW 500 Ω , n = 2, C n = 0.3

V pk (I pk , R f ) (kV)

P (I pk )

0.05

0.15

0.25

0.35

0.45

0.55

0.65

0.75

0.85

0.95

P (R f )

R f (Ω )

I pk (kA)

96.2

60.4

47.3

39.3

33.5

28.7

24.4

20.3

15.9

10.0

0.05

36.8

2204

1384

1084

901

767

657

560

465

364

229

0.15

20.0

1518

953

746

621

528

453

386

321

251

158

0.25

20.0

1518

953

746

621

528

453

386

321

251

158

0.35

20.0

1518

953

746

621

528

453

386

321

251

158

0.45

16.7

1366

858

672

559

476

408

347

289

226

142

0.55

13.5

1209

759

594

494

421

361

307

255

200

126

0.65

10.7

1072

673

527

438

373

320

272

226

177

111

0.75

8.3

944

593

464

386

328

282

240

199

156

98

0.85

5.9

814

511

400

333

283

243

207

172

135

84

0.95

3.1

655

412

322

268

228

196

166

138

108

68

Figure 18.2

Image of Simplified spreadsheet calculation of backflashover protection efficiency based on Table 18.5

Simplified spreadsheet calculation of backflashover protection efficiency based on Table 18.5 and Equation 18.11.

Computer programs and methods for calculating lightning outage rates (CIGRE, 1991; IEEE, 1997; Hileman, 1999) make use of the simplified concepts illustrated in Figure 18.2, but adding in calculation details related to

  • Automatic calculation of individual conductor surge impedances ZGW and coupling coefficients Cn at each phase conductor, incorporating nonlinear increase in Cn with increasing tower top voltage
  • Automated analysis of the risk of a shielding failure and consequent flashover from a direct lightning flash to a phase conductor
  • Integration of line voltage bias for every degree of phase (0°–360°) to establish the proportion of backflashover failures among phases

Advanced computer models are available to compute the possibility of multiple-phase or multi-circuit backflashover, and also to investigate the effects of applying transmission line surge arresters across selected insulators to limit their overvoltage stress and increase coupling coefficients on unprotected phases as suggested in (CIGRE, 2010).

18.12 Improving the Transmission Line Lightning Outage Rate

There are a number of options that affect the transmission line outage rate. A design with adequate shielding performance will use OHGWs to provide an estimated 0.05 shielding failures per 100 km year on new designs. It is difficult to reposition existing OHGWs on existing lines. If a study shows that time-correlated lightning outages on a line are the result of surges with low peak amplitudes (<20 kA), estimated from a lightning location system, then the application of transmission line surge arresters of suitable energy rating should be considered.

18.12.1 Increasing the Insulator Dry Arc Distance

Insulator dry arc distance, or the number of disks selected for insulator strings, has a remarkable effect on the lightning performance of transmission lines. At the 115 and 138 kV levels, it is common to use 7 or 8 standard (146 × 254 mm) disks or the equivalent polymer insulator length, giving DDry Arc = 1–1.2 m. At 230 kV, 14 disks are common and EHV lines may use 23–26 disks at the 500 kV level for DDry Arc = 3.4–3.8 m. This range of dry arc dimensions can change the lightning performance of a typical transmission line by a factor of 10 or more, as shown in Table 18.8, Table 18.9, and Table 18.10.

Table 18.10

Effect of Insulator Dry Arc Distance on Efficiency of Lightning Protection for Line with Median Footing Resistance R f = 30 Ω , Treated to Reduce below 20 Ω Where Feasiblea

Dry Arc Distance D Dry Arc (m)

Typical System Voltage (kV)

n = 2 (OHGW), C n = 0.3

n = 3 (2 OHGW, UBGW), C n = 0.4

n = 4 (2 OHGW + 2 Phases with Arresters), C n = 0.5

Efficiency (%)

Line Fault Ratea

Efficiency (%)

Line Fault Ratea

Efficiency (%)

Line Fault Ratea

1

115

67.7

1.52

78.7

1.00

87.7

0.58

1.5

161

83.5

0.78

90.3

0.45

95.0

0.24

2

230

90.5

0.44

94.9

0.24

97.5

0.12

2.5

275

94.1

0.28

96.9

0.14

98.6

0.07

3

345

96.1

0.18

98.1

0.09

99.0

0.05

3.5

500

97.3

0.13

98.6

0.06

99.6

0.02

a Normalized to reference case with DDry Ar c = 1 m, Median R f = 15 Ω, treated to 20 Ω or factor of 2 reduction (whichever is greater), n = 2, C n = 0.3, 300 m span, Ltw r = 15 μH.

Table 18.9

Effect of Insulator Dry Arc Distance on Efficiency of Lightning Protection for Line with Median Footing Resistance R f = 15 Ω , Untreateda

Dry Arc Distance D Dry Arc (m)

Typical System Voltage (kV)

n = 2 (OHGW), C n = 0.3

n = 3 (2 OHGW, UBGW), C n = 0.4

n = 4 (2 OHGW + 2 Phases with Arresters), C n = 0.5

Efficiency (%)

Line Fault Ratea

Efficiency (%)

Line Fault Ratea

Efficiency (%)

Line Fault Ratea

1

115

73.0

1.27

82.0

0.84

89.5

0.49

1.5

161

85.9

0.66

91.7

0.39

95.7

0.20

2

230

91.8

0.39

95.5

0.21

97.8

0.10

2.5

275

94.8

0.24

97.4

0.12

98.8

0.06

3

345

96.5

0.16

98.3

0.08

99.3

0.03

3.5

500

97.6

0.11

98.9

0.05

99.6

0.02

a Normalized to reference case with DDry Ar c = 1 m, Median R f = 15 Ω, treated to 20 Ω or factor of 2 reduction (whichever is greater), n = 2, C n = 0.3, 300 m span, Ltw r = 15 μH.

Table 18.8

Effect of Insulator Dry Arc Distance on Efficiency of Lightning Protection for Line with Median Footing Resistance R f = 15 Ω , Treated to Reduce below 20 Ω Where Feasiblea

Dry Arc Distance D Dry Arc (m)

Typical System Voltage (kV)

n = 2 (OHGW), C n = 0.3

n = 3 (2 OHGW, UBGW), C n = 0.4

n = 4 (2 OHGW + 2 Phases with Arresters), C n = 0.5

Efficiency (%)

Line Fault Ratea

Efficiency (%)

Line Fault Ratea

Efficiency (%)

Line Fault Ratea

1

115

78.7

1.00

86.5

0.63

92.3

0.36

1.5

161

90.3

0.46

94.4

0.26

97.1

0.14

2

230

94.8

0.24

97.2

0.13

98.6

0.07

2.5

275

96.9

0.15

98.4

0.08

99.2

0.04

3

345

98.0

0.09

99.0

0.05

99.5

0.02

3.5

500

98.7

0.06

99.3

0.03

99.8

0.01

a Normalized to reference case with DDry Ar c = 1 m, Median R f = 15 Ω, treated to 20 Ω or factor of 2 reduction (whichever is greater), n = 2, C n = 0.3, 300 m span, Ltw r = 15 μH. Note : The value of 1.00 is the reference case described in superscript a.

18.12.2 Modifying the Distribution of Footing Resistance

The simplified spreadsheet example of Figure 18.2 shows the relative outage rate in Table 18.8 and Table 18.9 obtained when a utility makes an effort during construction to reduce most footing resistance values to less than 20 Ω “where feasible” using the modification schedule in Table 18.5. If no effort is made to improve grounding, leading to the untreated resistance and voltage stress values in Table 18.4, the efficiency of double OHGW protection decreases from 78.7% to 73.0%, meaning that the lightning fault rate would be 27% higher without treatment for a dry arc distance of 1 m with other line characteristics fixed. As dry arc distance increases, improved grounding makes a larger fractional reduction in a decreasing outage rate.

18.12.3 Increasing the Effective Number of Groundwires Using UBGW

The number of shield wires in parallel, n, has a direct role in Equation 18.10 as well as an indirect influence on the value of Cn, the electromagnetic coupling coefficient from all n driven shield wires (those carrying a small fraction of lightning current) and the insulated phase. The groundwires consist of the traditional overhead groundwires (OHGWs) as well as underbuilt groundwires (UBGWs) and any phases protected with line surge arresters, including circuits at lower distribution voltages. UBGWs have been used on transmission lines to provide convenient access to optical fibers, giving a protected location of the metal-sheathed OPGW that is not exposed to direct flashes, as well as to manage ac fault currents and to reduce electric and magnetic fields in urban areas. UBGWs are preferred to buried continuous counterpoise for the safety and lightning protection functions as they have reduced installation cost, less environmental impact, easier inspection, and greater physical security. The improved coupling coefficient Cn associated with a single UBGW is seen in Table 18.8 and Table 18.9 to be roughly as effective as grounding improvements to maintain 20 Ω resistance “where feasible.”

18.12.4 Increasing the Effective Number of Groundwires Using Line Surge Arresters

When selected properly, line surge arresters clip the transient overvoltages across insulators in lightning surge conditions to prevent flashovers across nearby insulators. The limit distance related to lightning equivalent front time typically means that arresters on one transmission tower are typically too far away to provide protection of insulators on the same phase of adjacent towers. Table 18.8, Table 18.9, and Table 18.10 suggest that, in addition to eliminating flashovers on the protected phases, the flow of current through the arresters and the resulting rise in potential on the protected phases make important improvements in the lightning performance of unprotected phases on the same tower. More detailed examples, including the use of arresters on a lower voltage circuit to protect a higher voltage circuit, are found in (CIGRE, 2010).

18.13 Conclusion

Direct lightning strokes to any overhead transmission line are likely to cause impulse flashover of supporting insulation, leading to a circuit interruption. The use of overhead shield wires, located above the phase conductors and grounded adequately at each tower, can reduce the risk of flashover by 70%–99.8% depending on insulation dry arc distance and soil conditions. Underbuilt groundwires and phases protected with line surge arresters both improve electromagnetic coupling and can further reduce the risk of backflashover to achieve protection efficiency that exceeds 90%, even for systems with 1 m dry arc distance.

References

Anderson, R. B. and Eriksson, A. J., Lightning parameters for engineering applications, Electra 69, 65–102, 1980.

Anderson, R. B., Eriksson, A. J., Kroninger, H., and Meal, D. V., Lightning and thunderstorm parameters, in Lightning and Power Systems, IEE Conference Publication 236, London, U.K., June 1984.

Berger, K., The earth flash, in Lightning, ed. Golde, R., Academic Press, London, U.K., 1977, pp. 119–190.

Christian, H. J., Blakeslee, R. J., Boccippio, D., Boeck, W., Buechler, D., Driscoll, K., Goodman, S., Hall. J., Koshak, W., Mach, D., and Stewart, M., Global frequency and distribution of lighting as observed from space by the optical transient detector, J. Geophys. Res. 108(D1), 4005, 2003.

CIGRE Working Group 01 (Lightning) of Study Committee 33, Guide to procedures for estimating the lightning performance of transmission lines, Technical Brochure 63, Paris, France, 1991.

CIGRE WG C4.404, Cloud-to-ground lightning parameters derived from lightning location systems—The effects of system performance, Technical Brochure 376, CIGRE, Paris, France, 2009.

CIGRE Working Group C4.301, Use of surge arresters for lightning protection of transmission lines, Technical Brochure 440, CIGRE, Paris, France, 2010.

Darveniza, M., Popolansky, F., and Whitehead, E. R., Lightning protection of UHV transmission lines, Electra 41, 39–69, 1975.

EPRI, EPRI Transmission Line Reference Book, 200 kV and Above, 3rd edn., Chapter 6. Lightning and grounding, Chisholm, W. A. and Anderson, J. G., EPRI, Palo Alto, CA, 2005, 1011974.

Heydt, G., Instrumentation, in Handbook of Atmospherics, vol. II, ed. Volland, H., CRC Press, Boca Raton, FL, 1982, pp. 203–256.

Hileman, A. R., Insulation Coordination for Power Systems, CRC Press, Boca Raton, FL, 1999.

IEEE Standard 1243–1997, IEEE Guide for Improving the Lightning Performance of Transmission Lines, IEEE, Piscataway, NJ, December 1997.

IEEE Standard 1410–2010, IEEE Guide for Improving the Lightning Performance of Electric Power Overhead Distribution Lines, IEEE, Piscataway, NJ, January 2011.

Krider, E. P., Noggle, R. C., and Uman, M. A., A gated, wideband direction finder for lightning return strokes, J. Appl. Meteorol. 15, 301, 1976.

MacGorman, D. R., Maier, M. W., and Rust, W. D., Lightning strike density for the contiguous United States from thunderstorm duration records, Report to U.S. Nuclear Regulatory Commission, NUREG/CR-3759, 1984.

NASA High Resolution Full Climatology version 2.2, LIS/OTD 0.5 Degree High Resolution Full Climatology (HRFC) http://gcmd.nasa.gov/records/GCMD_lohrfc.html, 2006 (accessed on December 16, 2011).

Rakov, V. and Uman, M. A., Lightning Physics and Effects, Cambridge University Press, Cambridge, U.K., 2007.

Rizk, F. A. M., Modeling of transmission line exposure to direct lightning strokes, IEEE Trans. PWRD 5(4), 1983, 1990.

Takami, J. and Okabe, S., Observational results of lightning current on transmission towers, IEEE Trans. PWRD 22(1), 547, 2007.

..................Content has been hidden....................

You can't read the all page of ebook, please click here login for view all page.
Reset