11.6. Quantifying the Model
(a) Ball valve SS1 fails open.
Unavailability = λ MDT = 0.8 × 10−6 × 4000
(b) Ball valve SS2 fails open.
Unavailability = λ MDT = 0.8 × 10−6 × 4000
(c) PES output 1 fails to close valve (Undiagnosed Failure).
Unavailability = 10% λ MDT = 0.025 × 10−6 × 4000
(d) PES output 2 fails to close valve (Undiagnosed Failure).
Unavailability = 10% λ MDT = 0.025 × 10−6 × 4000
(e) PES output 1 fails to close valve (Diagnosed Failure).
Unavailability = 90% λ MDT = 0.225 × 10−6 × 4
(f) PES output 2 fails to close valve (Diagnosed Failure).
Unavailability = 90% λ MDT = 0.225 × 10−6 × 4
(g) Pressure transmitter fails low
Unavailability = λ MDT = 0.5 × 10−6 × 4000
The predicted Unavailability is obtained from the sum of the unavailabilities in (a) to (g)
= 8.6 × 10−3 (Note: the target was 4 × 10−3.).
This is higher than the unavailability target. The argument as to the fact that this is still within the SIL 2 target was discussed in
Chapter 2. We chose to calculate an unavailability target and thus it is NOT met.
74% from items (a) and (b), the valves.
23% from item (g), the pressure transmitter.
Negligible from items (c)–(f), the PES.
11.9. Quantifying the Revised Model
Changed figures are shown in bold.
(a) Ball valve SS1 fails open.
Unavailability = λ MDT = 0.8 × 10−6 × 2000
(b) Ball valve SS2 fails open.
Unavailability = λ MDT = 0.8 × 10−6 × 2000
(c) PES output 1 fails to close valve (Undiagnosed Failure).
Unavailability = 10% λ MDT = 0.025 × 10−6 × 2000
(d) PES output 2 fails to close valve (Undiagnosed Failure).
Unavailability = 10% λ MDT = 0.025 × 10−6 × 2000
(e) PES output 1 fails to close valve (Diagnosed Failure).
Unavailability = 90% λ MDT = 0.225 × 10−6 × 4
(f) PES output 2 fails to close valve (Diagnosed Failure).
Unavailability = 90% λ MDT = 0.225 × 10−6 × 4
(g) Voted pair of pressure transmitters.
Unavailability = λ2 T2/3 = [0.5 × 10−6]2 × 40002/3
(h) Common cause failure (CCF) of pressure transmitters.
Unavailability = 9% λ MDT = 0.09 × 0.05 × 10−6 × 2000
The predicted Unavailability is obtained from the sum of the unavailabilities in (a) to (h) = 3.3 × 10−3, which meets the target.
11.10. ALARP
Assume that further improvements, involving CCF and a further reduction in proof test interval, could be achieved for a total cost of £1000. Assume, also, that this results in an improvement in unavailability, of the safety-related system, from 3.3 × 10−3 to the PFD associated with the Broadly Acceptable limit of 4 × 10−4. It is necessary to consider, applying the ALARP principle, whether this improvement should be implemented.
If the target unavailability of 4 × 10−3 represents a maximum tolerable risk of 10−5 pa, then it follows that 3.3 × 10−3 represents a risk of 10−5 × 3.3/4 = 8.3 × 10−6 pa. If 10−6 pa is taken as the boundary of the negligible risk then the proposal remains within the tolerable range and thus subject to ALARP.
Assuming a two-fatality scenario, the cost per life saved over a 40-year life of the equipment (without cost discounting) is calculated as follows:
3.3 × 10−3 represents a risk of 8.3 × 10−6
4 × 10−4 represents a risk of 10−6
Cost per life saved = £1000/(40 × 2 lives × [8.3 − 1] × 10−6)
The Gross Disproposition Factor, GDF, (see below) for this example is 8.6 Thus, on this basis, if the cost per life saved criterion were £1,000,000 then, with GDF taken into account, it becomes £8,600,000. The proposed further improvement is justified.
11.11. Architectural Constraints
(a) PES
The safe failure fraction for the PESs is given by 90% diagnosis of 5% of the failures, which cause the failure mode in question, PLUS the 95% which are “fail safe.”
Thus (90% × 5%) + 95% = 99.5%.
If the simplex PES is regarded as Type B then SIL 2 can be considered if this design has >90% safe failure fraction.
(b) Pressure transmitters
The safe failure fraction for the transmitters is given by the 75% which are “fail safe.”
If they are regarded as Type A then SIL 2 can be considered since they are voted and require less than 60% safe failure fraction.
Incidentally, in the original proposal, the simplex pressure transmitter would not have met the architectural constraints.
(c) Ball valves
The safe failure fraction for the valves is given by the 90% which are “fail safe.”
If they are regarded as Type A then SIL 2 can be considered since they require more than 60% safe failure fraction.