This example provides a Safety Integrity Level (SIL) assessment of the proposed flood gate control system (FGCS) at a hydro-electric dam, demonstrating that it meets the identified hardware reliability and minimum configuration requirements in accordance with IEC 61508. In order to identify the SIL requirements, a Layer of Protection Analysis (LOPA) was conducted at a meeting of interested parties. The study considered the hydro-electric plant to determine potential risks associated with the specified hazards.
Table 16.1
Event (hazard) description | Consequence | Safety instrumented function (SIF) requirement (PFD) | SIF requirement (SIL) |
Dam overtopping due to gates failing to open on demand during a major storm (requiring the use of one gate), which spillways are unable to mitigate | Death of more than one person | 5.0 × 10−3 | SIL2 |
Water surge: gates open spuriously at full speed, causing a surge of water which could drown multiple fishermen | Death of more than one person | 2.3 × 10−3 | SIL2 |
Table 16.2
Loop ref. | Input device | Input configuration | Logic device | Logic configuration | Output device | Output configuration | Safety function |
A | Level transmitters microwave (2 off)/radar | 2oo3 | Safety PLC | 1oo1 | Two flood gate drives | 1oo2 | Detection of high loch level opens 1 out of 2 (1oo2) flood gates |
B | Safety timer relay | 1oo1 | N/A | N/A | Line contactor | 1oo1 | If the open contactor is closed for more than 50 s (i.e., the gate is opening too quickly), power is isolated from the motor by opening the line contactor |
Table 16.3
Redundant configuration | CCF β-factor | Justification |
Microwave/radar level transmitters | 5% | Three devices are mounted with separation and utilize two dissimilar technologies |
Flood gate operation mechanism | 2% | The flood gates (and the associated lifting gear) are physically separated from one another |
Power supplies | 10% | The two supplies are of similar technology |
Table 16.4
Failure rates and the calculation of SFF.
Item/function | Dangerous failure mode | λdd | λdu | λs | SFF | Source |
DC motor | Fails to start on demand | 0.0E+00 | 1.8E-06 | 3.3E-06 | 65% | Faradip v.6.1 |
Motor brake | Fails on | 0.0E+00 | 8.4E-08 | 3.6E-08 | 30% | NRPD-85 |
Chain drive | Breaks | 0.0E+00 | 2.7E-06 | 3.0E-07 | 10% | Faradip v.6.1 |
Redundant power supply | Loss of power | 5.5E-05 | 0.0E+00 | 0.0E+00 | 100% | Faradip v.6.1 |
Microwave level transmitter | Fails to detect high loch level | 9.9E-07 | 2.0E-07 | 3.4E-07 | 87% | Manufacturer's data adjusted |
FG PLC AI module | Fails to interpret high loch level | 5.6E-07 | 2.1E-07 | 4.2E-07 | 82% | ESC Failure Rate Database |
Radar level transmitter | Fails to detect high loch level | 1.1E-06 | 3.6E-07 | 4.7E-07 | 82% | Manufacturer's data adjusted |
Resolver | Erroneously detects gate in open position | 1.4E-06 | 1.5E-07 | 1.5E-06 | 95% | Faradip v.6.1 |
FG PLC AI module | Erroneously detects gate in open position | 5.6E-07 | 2.1E-07 | 4.2E-07 | 82% | ESC Failure Rate Database |
FG PLC CPU | Fails to interpret high level or gate closed on demand | 2.7E-07 | 3.0E-08 | 2.6E-06 | 99% | ESC Failure Rate Database |
FG PLC DO (NDE) module | Fail to energize on demand | 1.2E-07 | 7.4E-07 | 3.5E-07 | 39% | ESC Failure Rate Database |
Line contactor (NDE) | Fails to close contacts on demand | 0.0E+00 | 2.1E-07 | 9.0E-08 | 30% | Technis report T219 |
Safety timer relay | Contacts fail to open on demand | 0.0E+00 | 1.5E-08 | 1.5E-06 | 99% | Technis report T219 |
Line contactor (NE) | Contacts fail to open on demand | 0.0E+00 | 9.0E-08 | 2.1E-07 | 70% | Technis report T219 |
Boat movements through the lock | 12/day | Assume a half minute per passage |
Boat situated such as to be trapped | 17% | Based on an assumed 10 ft vessel in a 60 ft lock |
Skipper fails to take avoiding action | 10% | Judgment (noting 2 min closure time) |
Entrapment causes damage to vessel | 90% | Judged likely |
Fatality ensues | 50% | Judgment |